Minimum response time setting

Some Modbus masters have issues turning around their transceiver at higher baud rates. To resolve integration issues the user may use Modbus: Minimum Response Time (0x2321:004) to set a minimum time delay to be observed between the receipt of a valid Modbus message and the drive’s response. Time is entered in milliseconds 0x2321:004 (P510.04).
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2321:004
(P510.04)
Modbus settings: Minimum response time
(Modbus sett.: Min. resp. time)
0 ... [0] ... 1000 ms
Minimum time delay between the reception of a valid message and the response of the drive.