Function codes

The inverter supports the following function codes:
Function code
Function name
Description
3
0x03
Read Holding Registers
Read one or more 16-bit data words.
6
0x06
Preset Single Register
Write a 16-bit data word.
16
0x10
Preset Multiple Registers
Write one or more 16-bit data words.
23
0x17
Read/Write 4X Registers
Within a transaction
–
write into a group of connected 4X holding registers.
 
–
read from a group of connected 4X holding registers.
 
 
Addressing
–
The function codes listed above exclusively refer to 4X registers in Modbus addressing.
 
–
All data in the inverter can only be accessed via 4X registers, i.e. via register addresses from 40001.
 
–
The 4xxxx reference is implicit, i. e. given by the function code used. In the frame therefore the leading 4 is omitted in the addressing process.
 
–
Lenze supports the basic 1 addressing of Modbus, i.e. the numbering of the registers starts with 1 whereas addressing starts with 0. For example, the address 0 is used in the frame when register 40001 is read.
 
 
Frame structure
Communication is established on the basis of the central medium access method. Communication is always started by a master request. The inverter (slave) then either gives a valid response or outputs an error code (provided that the request has been received and evaluated as a valid Modbus frame). Error causes can be invalid CRC checksums, function codes that are not supported, or impermissible data access.
All Modbus frames have the following basic structure:
–
A "frame" consists of a PDU (Protocol Data Unit) and an ADU (Application Data Unit).
 
–
The PDU contains the function code and the data belonging to the function code.
 
–
The ADU serves the purposes of addressing and error detection.
 
–
The data are represented in Big Endian format (most significant byte first).
 
ADU (Application Data Unit)
Slave address
Function code
Data
Checksum (CRC)
PDU (Protocol Data Unit)
 
Error codes
In the event of an error, the Modbus node responds with a function code associated with the message:
Function code
Associated function code in the event of an error
Supported error codes
0x03
0x83
0x01, 0x02, 0x03, 0x04
0x06
0x86
0x01, 0x02, 0x03, 0x04
0x10
0x90
0x01, 0x02, 0x03, 0x04
0x17
0x97
0x01, 0x02, 0x03, 0x04
Error code
Designation
Cause(s)
0x01
Invalid function code
The function code is not supported by the inverter, or the inverter is in a state in which the request is not permissible or in which it cannot be processed.
0x02
Invalid data address
The combination of a start address and the length of the data to be transmitted is invalid.
Example: If you have a slave with 100 registers, the first register has the address 0 and the last register has the address 99. If there is a request of four registers now, from the start address 96, the request can be processed successfully (for registers 96, 97, 98, and 99). If, however, five registers from the start address 96 are queried, this error code is returned, since the slave has no register with the address 100.
0x03
Invalid data value
Error in the reset structure of a complex request, e. g. because the data length that has resulted implicitly is not correct.
The cause, however, is not that a (parameter) value is written outside the valid setting range. As a matter of principle, the Modbus protocol has no information on valid setting ranges of single registers or their meaning.
0x04
Slave device failure
A non-correctable error has occurred while the request was processed in the inverter.