Required commissioning steps
1.
2.
Activate motor control type: 0x2C00 (P300.00) = "V/f characteristic control (VFC closed loop) [7]".
3.
Set limiting factors for the V/f characteristic:
1.
Rated mains voltage 0x2540:001 (P208.01)
2.
Minimum frequency 0x2915 (P210.00)
3.
Maximum frequency 0x2916 (P211.00)
4.
Set V/f characteristic data:
5.
Select a characteristic shape suitable for the application in 0x2B00 (P302.00).
6.
Optional settings:
7.
Optional: carry out optimisation of the control circuits.
–
A optimisation of the control loops is not mandatory for this motor control type but may lead to a better control mode.
–
Options for optimizing the control loops