Keypad status display
In the operating mode, the keypad displays information on the status of the inverter.
|
Keypad display
|
Display
|
Meaning
|
|
If the inverter is inhibited, the keypad shows "STOP":
If the inverter is enabled, the keypad shows the output frequency of the inverter:
–
In the process controller mode, instead of the output frequency, the process controller setpoint is displayed.
–
The display can be configured in 0x2864 (P703.00).
–
The language for the keypad display is preset to "English". The language can be changed in 0x2863 (P705.00).
|
① Active control mode:
|
|
|
VEL
|
Speed mode
|
|
|
PID
|
Process controller mode
|
|
|
TRQ
|
Torque mode
|
|
|
JOG
|
Manual mode
|
|
|
② Active control source:
|
||
|
FLEX
|
Flexible I/O configuration
|
|
|
KPD
|
Keypad
|
|
|
KPDF
|
Keypad (complete control via keypad including setpoint selection)
|
|
|
NET
|
Network
|
|
|
③ Active setpoint source:
|
||
|
AINx
|
Analog input x
|
|
|
KPD
|
Keypad
|
|
|
NET
|
Network
|
|
|
FREQ
|
Digital frequency
|
|
|
PRx
|
Preset setpoint x
|
|
|
SEGx
|
Segment x
|
|
|
MOP
|
Motor potentiometer
|
|
|
④ Current direction of rotation:
|
||
|
FWD
|
Motor is rotating forwards
|
|
|
REV
|
Motor is rotating backwards
|
|
|
⑤ Lower status line:
|
||
|
LOC
|
Local keypad control active.
|
|
|
REM
|
Remote control via terminals, network, etc. active.
|
|
|
MAN
|
Manual setpoint selection via keypad active.
|
|
|
AUTO
|
Automatic setpoint selection via terminals, network, etc. active.
|
|
|
SET
|
Blinking if one parameter setting has been changed but has not been saved in the memory module with mains failure protection.
Save settings: Press keypad enter key longer than 3 s.
|
|
|
If an error is pending, the keypad shows the following information:
–
Faults (F) and trouble (T) are displayed continuously.
–
Warnings (W) are only displayed every 2 seconds for a short time.
|
① Error text
|
|
|
② Error type:
|
||
|
F
|
Fault
|
|
|
T
|
Trouble
|
|
|
W
|
Warning
|
|
|
③ Error code (hexadecimal)
|
||
|
|
After a disturbance, a restart is possible if the error condition is not active anymore. The keypad shows this by the "Restart Pending" note. The note is displayed in a 1-second interval alternating with the error text.
|
|
Events, causes and remedies