Service life diagnostics

The following parameters provide some information about the use of the inverter.
 
This includes the following information:
–
Operating and power-on time of the inverter/control unit
 
–
Operating time of the internal fan
 
–
Number of switching cycles of the mains voltage
 
–
Number of switching cycles of the relay
 
–
Number of short-circuits and earth faults that have occurred
 
–
Display of the number of "Clamp responded too often" errors that have occurred.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2D81:001
(P151.01)
Life-diagnosis: Operating time
(Life-diagnosis: Operating time)
–
Read only: x s
 
Display showing for how long the device has been running so far (device status “operation enabled”).
0x2D81:002
(P151.02)
Life-diagnosis: Power-on time
(Life-diagnosis: Power-on time)
–
Read only: x s
 
Display showing for how long the device has been supplied with line voltage so far.
0x2D81:003
(P151.03)
Life-diagnosis: Control unit operating time
(Life-diagnosis: CU oper. time)
–
Read only: x ns
 
Display showing for how long the control unit has been supplied with voltage so far. This includes the external 24-V supply and voltage supply via USB module.
0x2D81:004
(P151.04)
Life-diagnosis: Main switching cycles
(Life-diagnosis: Switching cycles)
–
Read only
 
Display of the number of switching cycles of the mains voltage.
0x2D81:005
(P151.05)
Life-diagnosis: Relay switching cycles
(Life-diagnosis: Relay cycles)
–
Read only
 
Display of the number of switching cycles of the relay.
0x2D81:006
(P151.06)
Life-diagnosis: Short-circuit counter
(Life-diagnosis: Short-circ.count)
–
Read only
 
Display of the number of short circuits that have occurred.
0x2D81:007
(P151.07)
Life-diagnosis: Earth fault counter
(Life-diagnosis: Earthfault count)
–
Read only
 
Display of the number of earth faults that have occurred.
0x2D81:008
(P151.08)
Life-diagnosis: Clamp active
(Life-diagnosis: Clamp active)
–
Read only
 
Display of the number of "Clamp responded too often" errors that have occurred.
–
"Clamp" = short-time inhibit of the inverter in V/f operation when the current limit shown in 0x2DDF:002 is reached.
 
0x2D81:009
(P151.09)
Life-diagnosis: Fan operating time
(Life-diagnosis: Fan oper. time)
–
Read only: x s
 
Display showing for how long the internal fan has been running so far.