Functional safety".Safe inputs
The components used must comply with the risk reduction required for the
application.
Passive sensors
Passive sensors are 2-channel switching elements with contacts.
Please note the following:
–
The switches must be wired according to the closed-circuit principle.
–
Passive sensors are connected to the inverter via a safety switching device.
–
An external safety component must monitor the connecting cables and the function of the sensors if complete exclusion of faults cannot be guaranteed.
The contacts must switch at the same time (equivalent). Safety functions will be activated if only one channel is switched. Switching of only one channel points to faulty sensors or impermissible wiring.
Examples of passive sensors:
–
Door contact switch
–
Emergency stop control units
Active sensors
Active sensors are units with 2-channel semiconductor outputs (OSSD outputs).
Test pulses for monitoring the outputs and cables are permissible.
P/M-switching sensors switch the positive and negative cable or the signal and ground cable of a sensor signal.
Please note the following:
–
The maximum permissible connection capacity of the outputs.
–
Active sensors are connected directly to the inverter.
–
Monitoring for short circuits must be carried out by the active sensor.
The outputs must switch at the same time (equivalent). Safety functions will be activated if only one channel is switched. The active control of only one channel points to faulty sensors or impermissible wiring.
Examples of active sensors:
–
Lightgrid
–
Laser scanner
–
Controllers
Further information
Information on the electrical connection can be found in the corresponding project planning document in the chapter "Electrical installation