Example 1: Pulse train 0: ... 10 kHz = output frequency 0 ... 100 Hz
In this configuration, a pulse train is provided at the digital output 1 proportionately to the actual output frequency of the inverter (1 kHz pulse train = 10 Hz output frequency, resolution 0.1 Hz).
Parameter
Name
Setting for this example
DO1 frequency setup: Minimum frequency
0.0 Hz
DO1 frequency setup: Maximum frequency
10000.0 Hz
DO1 frequency setup: Function
Output frequency [1]
DO1 frequency setup: Minimum signal
0
DO1 frequency setup: Maximum signal
1000
 
Use pulse train as setpoint source for other inverters (slaves)
The pulse train can be transferred to one or several other i5xx inverters (slaves) and be configured in the respective slave as a frequency setpoint source:
For this purpose, the following settings are required for the i5xx slave:
Parameter
Name
Setting for this example
Settings for digital inputs: Input function
Pulse train [2]
HTL input settings: Minimum frequency
0.0 Hz
HTL input settings: Maximum frequency
10000.0 Hz
HTL input settings: Minimum motor frequency
0.0 Hz
HTL input settings: Maximum motor frequency
100.0 Hz
Frequency control: Default setpoint source
HTL input [4]