Example 1: Pulse train 0: ... 10 kHz = output frequency 0 ... 100 Hz
In this configuration, a pulse train is provided at the digital output 1 proportionately to the actual output frequency of the inverter (1 kHz pulse train = 10 Hz output frequency, resolution 0.1 Hz).
|
Parameter
|
Name
|
Setting for this example
|
|
DO1 frequency setup: Minimum frequency
|
0.0 Hz
|
|
|
DO1 frequency setup: Maximum frequency
|
10000.0 Hz
|
|
|
DO1 frequency setup: Function
|
Output frequency [1]
|
|
|
DO1 frequency setup: Minimum signal
|
0
|
|
|
DO1 frequency setup: Maximum signal
|
1000
|
Use pulse train as setpoint source for other inverters (slaves)
The pulse train can be transferred to one or several other i5xx inverters (slaves) and be configured in the respective slave as a frequency setpoint source:
For this purpose, the following settings are required for the i5xx slave:
|
Parameter
|
Name
|
Setting for this example
|
|
Settings for digital inputs: Input function
|
Pulse train [2]
|
|
|
HTL input settings: Minimum frequency
|
0.0 Hz
|
|
|
HTL input settings: Maximum frequency
|
10000.0 Hz
|
|
|
HTL input settings: Minimum motor frequency
|
0.0 Hz
|
|
|
HTL input settings: Maximum motor frequency
|
100.0 Hz
|
|
|
Frequency control: Default setpoint source
|
HTL input [4]
|