Status messages
Status message via network
This status message is sent via non-secure interfaces. The status message must not be used to control other safety functions!
 
The inverter status word (0x282A:004) and the CiA status word (0x6041 (P780.00)) contain the status of the STO function according to the following truth table. These two parameter objects can be read via non-secure network interfaces.
Status
Status message
Safe input / channel
Inverter device state
Inverter status word
(Object 0x282A:004)
CiA status word
(Object 0x6041)
SIA
SIB
Bit 10
Bit 11
Bit 15
LOW
LOW
STO active
1
1
0
LOW
HIGH
Inverter disabled (safety)
1
0
0
HIGH
LOW
1
0
0
HIGH
HIGH
Drive enabled
0
0
1
Note: A discrepancy at the SIA and SIB inputs is not diagnosed. A discrepancy exists if bit 10 = 1 and bit 11 = 0 in the inverter status word (0x282A:004).
 
Status message via digital outputs
This status message is sent via non-secure interfaces. The status message must not be used to control other safety functions!
 
In 0x2634:xxx you set the function of the digital outputs. By selecting [55], you can output the “Inverter disabled (safety)” status and by selecting [155], you can output the “STO active” status via a non-safe output (e.g. digital output 1).
Status
Status message
Safe input / channel
Inverter device state
Function of digital outputs
0x2634:xxx
SIA
SIB
"Inverter disabled (safety)" [55]
"STO active" [155]
LOW
LOW
STO active
1
1
LOW
HIGH
Inverter disabled (safety)
1
0
HIGH
LOW
1
0
HIGH
HIGH
Drive enabled
0
0