Configure encoder input 2

In the Application-I/O version, the X3.3 connector can be configured as a second encoder input.
 
Preconditions
–
Single-track or two-track HTL encoder.
 
–
A two-track HTL encoder (tracks A and B) must have a phase offset of exactly 90° between tracks A and B (error  10°). Inverted tracks are not required.
 
 
–
Encoder increments: ≤ 16384 increments per revolution
 
–
For the supply of the encoder, the maximum supply current of the inverter must be observed. If necessary, an external 24 V voltage supply is required for the encoder.
 
–
The function assignment for connector X3.3 must be configured to "Encoder [0]". Configure function assignment 
 
 
Restrictions
–
If the "Encoder [0]" function assignment is enabled, the corresponding digital inputs or the HTL input are no longer available for detecting a reference frequency ("pulse train").
 
–
The maximum input frequency is 200 kHz. If this frequency is exceeded, an error is triggered.
 
 
Connection
Connection of a single-track HTL encoder
(without external 24 V voltage supply)
Connection of a two-track HTL encoder
(without external 24 V voltage supply)
 
Details
Encoder design: Calculate the maximum number of increments per revolution of the encoder
Max. encoder increments = fmax [Hz] * 60 s / nmax [rpm]
Max. encoder increments = 200,000 [Hz] * 60 s / 1,500 [rpm] = 8,000 increments per revolution
fmax
Maximum input frequency of the encoder inputs = 200 kHz = 200000 Hz
nmax
Maximum encoder speed (in this example: 1500 rpm)
Max. encoder increments
Maximum number of increments per encoder revolution
Select an encoder with a maximum number of increments per revolution that is less than or equal to the calculated number. The higher the number of increments per revolution, the more stable the system becomes.
 
 
Basic steps for configuring the encoder in the »EASY Starter«:
1.
In 0x2630:012, select "Encoder [0]" to configure connector X3.3 as an encoder input.
 
2.
Set the encoder number of increments per revolution in 0x2C52:001 according to the manufacturer data/encoder data sheet.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2C52:001
Load encoder/master encoder settings (encoder): Increments/revolution
1 ... [128] ... 16384
–
Setting can only be changed if the inverter is disabled.
 
Setting of the encoder number of increments (according to manufacturer data/encoder data sheet).
0x2C52:006
Load encoder/master encoder settings (encoder): Actual velocity
–
Read only: x rpm
 
Display of the current speed.
0x2C52:007
Load encoder/master encoder settings (encoder): Status
0 ... [0] ... 4294967295
Display of the encoder status.
Bit 0
Maximum encoder speed reached
Maximum encoder speed reached.
Bit 4
No signal detected
No pulses detected.