Configure function assignment
The inverter's control connections are designed as configurable M12 connectors.
–
For Standard-I/O and Application-I/O, all control connections are configured as digital inputs by default.
–
In Extended-I/O mode, a different function assignment is preset for control connections X3.3 and X3.4:
–
X3.3: Analog input AI1 + Digital input DI5
–
X3.4: Analog output AO1
Details
The function assignment of the plug connectors X3 can be configured via the parameters listed below.
|
M12 connectors (A coded)
|
Pin
|
Assignment
|
|||
|
X3.1
|
X3.2
|
X3.3
|
X3.4
|
||
|
|
1
|
24 V or L+ (for IO-Link devices, only for Application-I/O)
|
|||
|
2
|
DI2
|
configurable in 0x2630:011
|
DI6
|
DI8
|
|
|
3
|
GND or L- (for IO-Link devices, only for Application-I/O)
|
||||
|
4
|
configurable in 0x2630:010
|
configurable in 0x2630:011
|
configurable in 0x2630:012
|
configurable in 0x2630:013
|
|
|
5
|
Not assigned
|
||||
|
|
Housing is connected to functional earth
|
||||
The possible function assignment depends on the design of the control connections:
|
Category
|
Function assignment
|
Version
|
||
|
Standard-I/O
|
Application-I/O
|
Extended-I/O
|
||
|
Digital inputs
|
DI1
|
●
|
●
|
●
|
|
DI2
|
●
|
●
|
●
|
|
|
DI3
|
●
|
●
|
●
|
|
|
DI4
|
●
|
●
|
●
|
|
|
DI5
|
|
●
|
●
|
|
|
DI6
|
|
●
|
|
|
|
DI7
|
|
●
|
|
|
|
DI8
|
|
●
|
|
|
|
Digital outputs
|
DO1
|
●
|
●
|
●
|
|
DO2
|
|
●
|
|
|
|
DO3
|
|
●
|
●
|
|
|
DO4
|
|
●
|
|
|
|
IO-Link
|
IO-Link Port 1
|
|
●
|
|
|
IO-Link Port 2
|
|
●
|
|
|
|
IO-Link Port 3
|
|
●
|
|
|
|
IO-Link Port 4
|
|
●
|
|
|
|
HTL output
|
Pulse train
|
●
|
●
|
●
|
|
Encoder interface X3.2
|
Encoder
|
●
|
●
|
●
|
|
Low-resolution HTL-encoder
|
●
|
●
|
●
|
|
|
Pulse-In/Pulse-Direction
|
●
|
●
|
●
|
|
|
Encoder interface X3.3
|
Encoder
|
|
●
|
|
|
Low-resolution HTL-encoder
|
|
●
|
|
|
|
Pulse-In/Pulse-Direction
|
|
●
|
|
|
|
Table positioning
|
Touch probe
|
|
●
|
|
|
Analog inputs
|
AI1 -
|
|
|
●
|
|
AI2
|
|
|
●
|
|
|
Analog output
|
AO1
|
|
|
●
|
|
Temperature sensor
|
|
|
●
|
|
"DIx" function assignment:
–
Standard digital inputs for control tasks.
–
Logic level "HIGH-active" or "LOW-active", debounce time, and inversion can be parameterized.
"DOx" function assignment:
–
Standard digital outputs.
–
Switch-on delay and switch-off delay can be parameterized.
"IO-Link" function assignment:
–
For communicating with sensors and actuators (IO-Link Devices) with port class A.
–
The inverter (IO-Link Master) supports IO-Link version 1.1.
–
IO-Link Devices with IO-Link version 1.0 are not supported.
"Encoder" function assignment:
–
For connecting a single-track or two-track HTL encoder (max. 200 kHz).
–
A single-track HTL encoder (track A) cannot be used for motor speed feedback.
–
A two-track HTL encoder (track A and B) must have a phase offset of exactly 90° between track A and B (error ≤ ± 10°). Inverted tracks are not required.
–
Encoder increments: ≤ 16384 increments per revolution
"Pulse-In" function assignment:
–
To evaluate the signal of a low-cost HTL encoder or a reference frequency ("Pulse-Train") and to accept it as a setpoint signal.
–
The detection of a direction signal ("Pulse-Direction") is also supported.
"Pulse-Train" function assignment:
–
For output of a reference frequency ("Pulse Train"). Other inverters can interpret this signal as a setpoint signal, for example.
"Touch Probe" function assignment:
–
For evaluating a reference switch for positioning using a touch probe (remaining-distance positioning). For more information about this function, see the "Table Positioning" manual.
"AIx" function assignment:
–
For acquiring an analog signal (for example, for the process controller).
–
Can be configured as a voltage input or current input.
Function assignment "AO1":
–
To output an analog signal.
–
Can be configured as a voltage source or a current source.
"Temperature Sensor" function assignment:
–
For measuring temperature via a connected temperature sensor
(e.g., PT100 or PT1000).
(e.g., PT100 or PT1000).
Parameter
Configure digital inputs