Configure process temperature monitoring
With the "Temperature Sensor" function assignment for connector X3.4, the inverter can evaluate a connected temperature sensor. A typical application is monitoring a process temperature. For monitoring, a lower and an upper monitoring threshold with adjustable response can be configured.
–
PT100 and PT1000 measurement resistors are supported.
–
The measured temperature values (displayed in 0x2638:001) can be mapped to process data and thus transmitted over the network.
–
The connected temperature sensor is monitored for wire breaks.
–
The cable resistance to the temperature sensor can be compensated for by adjusting a correction factor.
Preconditions
–
The function assignment of connector X3.4 must be configured accordingly.
Configure function assignment
Configure function assignment –
The "temperature sensor" function is available only on drives with Extended-I/O.
–
To directly connect a standard temperature sensor with an M12 connector, a 3-wire cable is required to prevent a short circuit between pin 1 and pin 2. Such a cable is available in the standard product line of various cable manufacturers.
Details
Fig. 1: Connecting a temperature sensor (PT100/PT1000) with standard assignment to X3.4
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x2638:001
|
Prozess temperature monitoring: Actual temperature
–
Read only: x.x °C
|
||
|
0x2638:002
|
Prozess temperature monitoring: Temperature sensor type
|
||
|
0
|
PT100
|
||
|
1
|
PT1000
|
||
|
0x2638:003
|
Prozess temperature monitoring: Lower monitoring threshold
-50.0 ... [80.0] ... 300.0 °C
|
If the lower monitoring threshold is exceeded, the error response configured at 0x2638:006 is triggered.
|
|
|
0x2638:004
|
Prozess temperature monitoring: Upper monitoring threshold
-50.0 ... [100.0] ... 300.0 °C
|
If the upper monitoring threshold is exceeded, the error response configured at 0x2638:007 is triggered.
|
|
|
0x2638:005
|
Prozess temperature monitoring: Correction factor
0.00 ... [0.00] ... 10.00 Ω
|
Correction factor for compensating for the cable resistance to the temperature sensor.
|
|
|
0x2638:006
|
Prozess temperature monitoring: Fault reaction lower monitoring threshold
|
||
|
0
|
No response
|
||
|
11
|
Information
|
||
|
12
|
Warning
|
||
|
16
|
Trouble
|
||
|
23
|
Fault > inverter disabled
|
||
|
0x2638:007
|
Prozess temperature monitoring: Fault reaction upper monitoring threshold
|
||
|
0
|
No response
|
||
|
11
|
Information
|
||
|
12
|
Warning
|
||
|
16
|
Trouble
|
||
|
23
|
Fault > inverter disabled
|
||
|
0x2638:008
|
Prozess temperature monitoring: Status
–
Read only
|
||
|
Bit 0
|
Lower threshold reached
|
||
|
Bit 1
|
Upper threshold reached
|
||
Severity