Causes and remedies

8784
0x2250
CiA: Continuous over current (internal)
Cause
Remedy
Severity/response
–
Continuous overcurrent on the inverter/motor side.
 
–
DC bus relay has not been closed due to a malfunction.
 
–
Check motor and wiring for short circuits.
 
Fault
–
The inverter is disabled immediately. The motor has no torque (is coasting).
 
–
The event can only be reset after a blocking time.
 
Blocking time: 2 s
 
8992
0x2320
Short circuit or earth leakage at the motor end
Cause
Remedy
Severity/response
–
Short circuit/earth fault of motor cable
 
–
Capacitive charging current of the motor cable too high.
 
–
Check motor cable.
 
–
Check length of the motor cable.
 
–
Use shorter or lower-capacitance motor cable.
 
Fault
–
The inverter is disabled immediately. The motor has no torque (is coasting).
 
–
The event can only be reset after a blocking time.
 
Blocking time: 2 s
 
9024
0x2340
Short circuit at the motor end
Cause
Remedy
Severity/response
Short circuit of motor cable
Check motor cable for short circuit.
Fault
–
The inverter is disabled immediately. The motor has no torque (is coasting).
 
–
The event can only be reset after a blocking time.
 
Blocking time: 2 s
 
9040
0x2350
CiA: i²xt overload (thermal state)
Cause
Remedy
Severity/response
Motor thermally overloaded, e. g. by an impermissible continuous current or by frequent or too long acceleration processes.
–
Check drive sizing.
 
–
Check machine/driven mechanics for excessive load.
 
–
Check settings of the motor data.
 
–
Reduce values for slip compensation 0x2B09:001, 0x2B09:002 and oscillation damping 0x2B0A:001, 0x2B0A:002.
 
Fault > inverter disabled (configurable)
–
The event can only be reset after a blocking time.
 
Blocking time: 2 s
Setting parameters: 0x2D4B:003
 
9090
0x2382
Fault - Device utilization (ixt) too high
Cause
Remedy
Severity/response
Device utilisation (ixt) too high by frequent and too long acceleration processes.
–
Check drive sizing.
 
–
Reduce the maximum current of the inverter 0x6073.
 
–
In case of high mass inertias, reduce maximum current of the inverter 0x6073 to 150 %.
 
Fault > inverter disabled (configurable)
–
The event can only be reset after a blocking time.
 
Blocking time: 2 s
Setting parameters: 0x2D40:005
 
9091
0x2383
Warning - Device utilization (ixt) too high
Cause
Remedy
Severity/response
Device utilisation (ixt) too high by frequent and too long acceleration processes.
–
Check drive sizing.
 
–
Check the warning threshold settings in 0x2D40:002.
 
Warning
 
9095
0x2387
Clamp responded too often
Cause
Remedy
Severity/response
Maximum current of the axis (display in 0x2DDF:002) has been reached too often in succession.
–
Select a flatter speed ramp.
 
–
Reduce the load.
 
–
Set Imax controller more dynamically.
 
Fault
Related topics
 
9096
0x2388
Sensorless control: stall detection active
Cause
Remedy
Severity/response
Overload of the motor with sensorless control for synchronous motors.
–
Reduce load at the axis.
 
–
Check the settings of the parameters for sensorless control.
 
Trouble
–
The inverter is disabled immediately. The motor has no torque (is coasting).
 
 
12576
0x3120
Mains phase fault
Cause
Remedy
Severity/response
Mains phase failure
–
Check wiring of the mains connection.
 
–
Check fuses.
 
Warning
 
12816
0x3210
Fault - DC bus overvoltage
Cause
Remedy
Severity/response
DC-bus voltage has exceeded the error threshold for overvoltage due to a too high braking energy or a too high mains voltage. The error threshold (display in 0x2540:006) results from the setting of the rated mains voltage in 0x2540:001.
–
Reduce dynamic performance of the load profile.
 
–
Check mains voltage.
 
–
Check settings for brake energy management.
 
Fault
 
12817
0x3211
DC bus overvoltage warning
Cause
Remedy
Severity/response
DC-bus voltage has exceeded the warning threshold for overvoltage set in 0x2540:005 due to a too high braking energy or a too high mains voltage.
–
Reduce dynamic performance of the load profile.
 
–
Check mains voltage.
 
–
Check settings for brake energy management.
 
Warning
 
12832
0x3220
Fault - DC bus undervoltage
Cause
Remedy
Severity/response
DC-bus voltage has fallen below the error threshold for undervoltage. The error threshold (display in 0x2540:003) results from the setting of the rated mains voltage in 0x2540:001.
–
Check mains voltage.
 
–
0x2D87Check DC-bus voltage.
 
–
Check mains settings.
 
–
Check fuses.
 
Trouble
Related topics
 
12833
0x3221
DC bus undervoltage warning
Cause
Remedy
Severity/response
DC-bus voltage has fallen below the warning threshold for undervoltage set in 0x2540:002.
–
Check mains voltage.
 
–
0x2D87 Check DC-bus voltage.
 
–
Check mains settings.
 
–
Check fuses.
 
Warning
Related topics
 
12834
0x3222
DC-bus voltage too low for power up
Cause
Remedy
Severity/response
The input voltage is too low to switch on the inverter.
–
Check mains voltage.
 
–
Check mains settings.
 
–
Check fuses.
 
Warning
Related topics
 
16912
0x4210
Fault - Power unit overtemperature
Cause
Remedy
Severity/response
The heatsink temperature of the power unit (display in 0x2D84:001) has exceeded the fixed error threshold (110 °C).
–
Ambient temperature too high.
 
–
Fan or ventilation slots are polluted.
 
–
Fan is defective.
 
–
Check mains voltage.
 
–
Provide for a sufficient cooling of the device. In case of a 100 % load, 75 °C to 85 °C are normal. Display of the heatsink temperature in 0x2D84:001.
 
–
Clean fan and ventilation slots. If required, replace fan.
 
–
Reduce switching frequency in 0x2939.
 
Fault
 
17024
0x4280
Fault - Heat sink temperature sensor
Cause
Remedy
Severity/response
Sensor for the temperature monitoring of the power unit is defective. The failure of the temperature monitoring function poses the risk of overheating!
Hardware error: it is necessary to contact the manufacturer, since the device must be replaced.
Fault
 
17025
0x4281
Heat sink fan warning
Cause
Remedy
Severity/response
Warning of the heatsink fan.
Clean fan and ventilation slots. If required, replace fan. The fans can be unlocked via locking hooks and can then be removed.
Warning
 
17029
0x4285
PU overtemperature warning
Cause
Remedy
Severity/response
The heatsink temperature of the power unit (display in 0x2D84:001) has exceeded the warning threshold set in 0x2D84:002.
–
Ambient temperature too high.
 
–
Fan or ventilation slots are polluted.
 
–
Fan is defective.
 
–
Provide for a sufficient cooling of the device.
 
–
Clean fan and ventilation slots.
 
–
If required, replace fan.
 
Warning
 
17168
0x4310
Motor overtemperature
Cause
Remedy
Severity/response
The PTC or thermal contact connected to the motor connector/terminal X105 or terminal 109 measures a too high motor temperature.
–
Motor too hot by impermissibly high currents.
 
–
Motor too hot by frequent and too long acceleration processes.
 
–
Check drive sizing.
 
–
Check PTC/thermal contact and wiring.
 
–
If no PTC or thermal contact is connected to T1 and T2, deactivate motor temperature monitoring: 0x2D49:002 = 0
 
Fault > inverter disabled (configurable)
–
The event can only be reset after a blocking time.
 
Blocking time: 2 s
Setting parameters: 0x2D49:002
Related topics
 
20608
0x5080
Internal error - AIS
Cause
Remedy
Severity/response
Internal error
Restart the device. If the error persists, replace the device.
Warning
 
20609
0x5081
Internal error - AIE
Cause
Remedy
Severity/response
Internal error
Restart the device. If the error persists, replace the device.
Warning
 
20610
0x5082
Internal error - Button S82
Cause
Remedy
Severity/response
Internal error
Restart the device. If the error persists, replace the device.
Warning
 
20619
0x508B
SD-Inx/CLx - Error
Cause
Remedy
Severity/response
Internal error
Restart the device. If the error persists, replace the device.
Warning
 
20620
0x508C
Internal switch-off path - Error
Cause
Remedy
Severity/response
Internal error
Restart the device. If the error persists, replace the device.
Warning
 
20621
0x508D
Internal switch-off path - Test pulse error
Cause
Remedy
Severity/response
Internal error
Restart the device. If the error persists, replace the device.
Warning
 
20754
0x5112
External supply voltage critical
Cause
Remedy
Severity/response
External supply voltage failed or too low.
–
Check the optional auxiliary power supply on the X100.1/24E or X5/24E, if connected.
 
–
Check mains voltage.
 
Warning
 
20756
0x5114
Reference voltage error
Cause
Remedy
Severity/response
Internal error
Restart the device. If the error persists, replace the device.
Warning
 
20757
0x5115
6 V voltage error
Cause
Remedy
Severity/response
Internal error
Restart the device. If the error persists, replace the device.
Fault
–
The inverter is disabled immediately. The motor has no torque (is coasting).
 
–
The event can only be reset by mains switching.
 
 
20759
0x5117
3.3 V voltage error
Cause
Remedy
Severity/response
Internal error
Restart the device. If the error persists, replace the device.
Fault
–
The inverter is disabled immediately. The motor has no torque (is coasting).
 
–
The event can only be reset by mains switching.
 
 
20864
0x5180
Overload 24 V supply
Cause
Remedy
Severity/response
Output current at the 24V output or at the digital outputs too high.
Check 24V output and digital outputs for earth fault or overload.
Fault > inverter disabled (configurable)
Setting parameters: 0x2630:020
 
24704
0x6080
Logic PLC exception error
Cause
Remedy
Severity/response
An exception has occurred in the PLC application.
–
Update PLC application.
 
–
Restart the device (recommended).
 
Fault > inverter disabled (configurable)
Setting parameters: 0x5811:002
 
24705
0x6081
Logic PLC endless loop
Cause
Remedy
Severity/response
An infinite loop was detected in the PLC application.
–
Load a new PLC application into the device.
 
–
Restart the device (recommended).
 
Fault
 
24960
0x6180
Internal error - STO activated
Cause
Remedy
Severity/response
Internal error
Restart the device. If the error persists, replace the device.
Warning
 
24965
0x6185
Communication error - Basic device
Cause
Remedy
Severity/response
Internal error
Restart the device. If the error persists, replace the device.
Fault
 
24966
0x6186
Synchronization error - Basic device
Cause
Remedy
Severity/response
Internal error
Restart the device. If the error persists, contact the manufacturer.
Information
 
24970
0x618A
Warning - Internal fan
Cause
Remedy
Severity/response
Warning of the internal fan.
Check/replace internal fan.
Warning
 
24984
0x6198
Internal error
Cause
Remedy
Severity/response
Internal error
Restart the device. If the error persists, replace the device.
Fault
 
24985
0x6199
Internal error
Cause
Remedy
Severity/response
Internal error
Restart the device. If the error persists, replace the device.
Fault
 
24986
0x619A
Internal error
Cause
Remedy
Severity/response
Internal error
Restart the device. If the error persists, replace the device.
Fault
 
24987
0x619B
Internal error
Cause
Remedy
Severity/response
Internal error
Restart the device. If the error persists, replace the device.
Fault
 
25216
0x6280
Trigger/functions connected incorrectly
Cause
Remedy
Severity/response
The assignment directives have not been observed.
–
If the "flexible I/O configuration" is active as control source, the "Enable inverter" or "Run" function must be connected to a digital input in order that the motor can be stopped again any time!
 
–
The use of the "Start forward (CW)" and "Start reverse (CCW)" functions excludes the use of the "Run forward (CW)" and "Run reverse (CCW)" functions, and vice versa.
 
Check and correct the assignment of the triggers to the functions.
–
With network control, the two "Enable inverter 0x2631:001" and "Run 0x2631:002" functions can also be set to "Constant TRUE [1]" to start the motor.
 
Trouble
 
25217
0x6281
User-defined fault 1
Cause
Remedy
Severity/response
Flexible I/O configuration: the "Activate fault 1" function was activated via the trigger selected in 0x2631:043.
Eliminate error cause and then reset error.
Fault > inverter disabled (configurable)
Setting parameters: 0x2842:001
 
25218
0x6282
User-defined fault 2
Cause
Remedy
Severity/response
Flexible I/O configuration: the "Activate fault 2" function was activated via the trigger selected in 0x2631:044.
Eliminate error cause and then reset error.
Fault > inverter disabled (configurable)
Setting parameters: 0x2842:003
 
25232
0x6290
Warning invert rotation
Cause
Remedy
Severity/response
–
Negative setpoint selection with an active limitation of rotation 0x283A.
 
–
The "Reverse rotational direction" 0x2631:013 function was requested with an active limitation of rotation 0x283A.
 
–
Check setpoint selection and trigger.
 
–
Check setting in 0x283A.
 
Warning
–
The motor is brought to a standstill, since a reversal of the rotating direction is not permissible.
 
 
25233
0x6291
Maximuml allowed troubles exceeded
Cause
Remedy
Severity/response
The number of permitted restart attempts after a fault set in 0x2839:003 was exceeded. The fault occurred to frequently and could not be reset.
Check and the eliminate the fault.
Fault
–
The motor remains at a standstill, no automatic restart is executed.
 
 
25249
0x62A1
Network: user fault 1
Cause
Remedy
Severity/response
The "Activate fault 1" function was triggered via the NetWordIN1 data word 0x4008:001.
Eliminate error cause and then reset error.
Fault
 
25250
0x62A2
Network: user fault 2
Cause
Remedy
Severity/response
The "Activate fault 2" function was triggered via the NetWordIN1 data word 0x4008:001.
Eliminate error cause and then reset error.
Fault
 
25265
0x62B1
NetWordIN1 configuration incorrect
Cause
Remedy
Severity/response
Two bits of the NetWordIN1 data word 0x4008:001 were assigned to the same function.
Check and correct configuration of the NetWordIN1 data word.
–
The functions that are to be triggered via bits 0 ... 15 of the NetWordIN1 data word are defined in 0x400E:001 ... 0x400E:016.
 
Trouble
 
25478
0x6386
F_CRC_Length error
Cause
Remedy
Severity/response
The data length of the F_CRC in the higher-level controller is faulty.
Check safety parameter in the higher-level controller.
Information
 
25479
0x6387
Wrong F-parameter version
Cause
Remedy
Severity/response
The F parameter version is not supported by the device.
Select supported F parameter version in the higher-level controller.
Information
 
25481
0x6389
Safety parameter set deleted
Cause
Remedy
Severity/response
Safety parameter set deleted
For information only. No remedy necessary.
Information
 
25482
0x638A
New safety parameter set loaded
Cause
Remedy
Severity/response
New safety parameter set loaded
For information only. No remedy necessary.
Information
 
25484
0x638C
Different safety parameter sets
Cause
Remedy
Severity/response
The safe parameter sets on the memory module and in the device are different.
Load safe parameter set into the device. Acknowledge modification with confirmation button S82.
Warning
–
The inverter is safely switched off.
 
–
The integrated functional safety is in the service status.
 
Related topics
 
25485
0x638D
Extended Safety - No safety parameter set
Cause
Remedy
Severity/response
No safe parameter set was found in the device.
Load safe parameter set into the device. Acknowledge modification with confirmation button S82.
Warning
–
The inverter is safely switched off.
 
–
The integrated functional safety is in the service status.
 
Related topics
 
25486
0x638E
Extended Safety - Safety parameter set defect
Cause
Remedy
Severity/response
The safe parameter set in the device is faulty.
Load safe parameter set into the device. Acknowledge modification with confirmation button S82.
Warning
–
The inverter is safely switched off.
 
–
The integrated functional safety is in the service status.
 
Related topics
 
25487
0x638F
Safety parameter set - Format error
Cause
Remedy
Severity/response
Format error in the safe parameter set.
Warning message of an inverter with Extended Safety in the as-delivered state.
Reset the safe parameter set in the device and load it again. Acknowledge modification with confirmation button S82.
Warning
–
The inverter is safely switched off.
 
–
The integrated functional safety is in the service status.
 
Related topics
 
25488
0x6390
Safety parameter set - Plausibility error
Cause
Remedy
Severity/response
The set safety parameters are not plausible.
1.
Determine the error number in 0x2115:005 and analyze it using the table of plausibility errors.
 
2.
Correct error.
 
3.
Reload safe parameter set.
 
4.
Acknowledge modification with confirmation button S82.
 
Warning
–
The inverter is safely switched off.
 
–
The integrated functional safety is in the service status.
 
Related topics
 
25489
0x6391
Safety parameter set - Communication error
Cause
Remedy
Severity/response
A communication error has occurred while loading the safe parameter set.
–
Check communication settings.
 
–
Check memory module.
 
–
Reload safe parameter set. Acknowledge modification with confirmation button S82.
 
Warning
–
The inverter is safely switched off.
 
–
The integrated functional safety is in the service status.
 
Related topics
 
25490
0x6392
Different safety addresses detected
Cause
Remedy
Severity/response
The safety addresses in the device and on the memory module are different.
–
Adapt safety addresses.
 
–
Reload safe parameter set. Acknowledge modification with confirmation button S82.
 
Warning
–
The inverter is safely switched off.
 
–
The integrated functional safety is in the service status.
 
Related topics
 
25492
0x6394
Memory module release information - access error
Cause
Remedy
Severity/response
No release information is available on the memory module.
After transferring an application with the "Application Loader", the release information for the safe parameter set must be generated separately for each device with the »EASY Starter« or »PLC Designer« via the +Safety parameter list+ and transferred to the device. After transmission, the safe parameter set must be saved in the device using the "Save" command.
Information
–
The inverter is safely switched off.
 
Related topics
 
25493
0x6395
Internal limitation active
Cause
Remedy
Severity/response
The calculation of speed and position values has led to an internal value limit.
Check the parameters for the valid travel range and for setting the gearbox factor.
Warning
 
25505
0x63A1
CU: load error ID tag
Cause
Remedy
Severity/response
Calibration data of the control unit not compatible or faulty.
–
Update firmware of the inverter to the most recent version.
 
–
If the error persists, the control unit or the device has to be replaced. In this case, please contact the manufacturer.
 
Fault
–
The event can only be reset by mains switching.
 
 
25506
0x63A2
PU: load error ID tag
Cause
Remedy
Severity/response
Calibration data of the power unit not compatible or faulty.
–
Update firmware of the inverter to the most recent version.
 
–
If the error persists, the power unit or the device has to be replaced. In this case, please contact the manufacturer.
 
Fault
–
The event can only be reset by mains switching.
 
 
25507
0x63A3
Power unit unknown
Cause
Remedy
Severity/response
The power unit installed is not supported by the software.
Update firmware of the inverter to the most recent version.
Fault
–
The event can only be reset by mains switching.
 
 
28800
0x7080
Assertion level monitoring (Low/High)
Cause
Remedy
Severity/response
The last setting of the connection level differs from the saved setting.
1.
Execute device command "Save user data" 0x2022:003.
 
2.
Switch inverter off and on again.
 
Fault
 
28801
0x7081
Analog input 1 fault
Cause
Remedy
Severity/response
The monitoring function of the input signal configured for analog input 1 in 0x2636:008 and 0x2636:009 has been triggered.
–
Check input signal at analog input 1.
 
–
Check configuration of the monitoring function.
 
Information (configurable)
Setting parameters: 0x2636:010
 
28802
0x7082
Analog input 2 fault
Cause
Remedy
Severity/response
The monitoring function of the input signal configured for analog input 2 in 0x2637:008 and 0x2637:009 has been triggered.
–
Check input signal at analog input 2.
 
–
Check configuration of the monitoring function.
 
Information (configurable)
Setting parameters: 0x2637:010
 
28803
0x7083
HTL input fault
Cause
Remedy
Severity/response
No response (configurable)
Setting parameters: 0x2641:006
 
28804
0x7084
HTL input fault IN2
Cause
Remedy
Severity/response
No response (configurable)
Setting parameters: 0x2641:016
 
28805
0x7085
Process temperature invalid
Cause
Remedy
Severity/response
Failure of the process temperature input, caused by:
–
Wire break
 
–
Short circuit
 
–
Incorrect setting for the temperature sensor type in 0x2636:002
 
–
Check the wiring of the process temperature input.
 
–
Check the temperature sensor type setting in 0x2636:002.
 
Warning
 
28806
0x7086
Process temperature lower threshold
Cause
Remedy
Severity/response
The process temperature has exceeded the lower monitoring threshold set in 0x2638:003.
–
Check the process temperature.
 
–
Check the set monitoring threshold.
 
No response (configurable)
–
The event can only be reset after a blocking time.
 
Blocking time: 5 s
Setting parameters: 0x2638:006
 
28807
0x7087
Process temperature upper threshold
Cause
Remedy
Severity/response
The process temperature has exceeded the upper monitoring threshold set in 0x2638:004.
–
Check the process temperature.
 
–
Check the set monitoring threshold.
 
No response (configurable)
–
The event can only be reset after a blocking time.
 
Blocking time: 5 s
Setting parameters: 0x2638:007
 
28808
0x7088
Analog input 1 fault
Cause
Remedy
Severity/response
An error was detected on analog input 1 (0x2DA4:016, bits 9, 10, 11).
Check the signal at analog input 1.
Information (configurable)
Setting parameters: 0x2636:015
Related topics
 
28809
0x7089
Analog input 2 fault
Cause
Remedy
Severity/response
An error was detected on analog input 2 (0x2DA5:016, bits 9, 10, 11).
Check the signal at analog input 2.
Information (configurable)
Setting parameters: 0x2637:015
Related topics
 
28833
0x70A1
Analog output 1 fault
Cause
Remedy
Severity/response
Open circuit or short circuit at analog output 1.
–
Check wiring of analog output 1.
 
–
Check definition of the output range in 0x2639:001.
 
Warning
Related topics
 
28961
0x7121
Fault - Pole position identification
Cause
Remedy
Severity/response
–
Too many deviations during the pole position identification.
 
–
Compared to the inverter, the rated motor current is too high or too low.
 
–
Check setting of the motor data.
 
–
Ensure that the motor is at a standstill during the pole position identification process.
 
–
Ensure that the motor and inverter match each other in terms of power.
 
Fault
 
29056
0x7180
Motor overcurrent
Cause
Remedy
Severity/response
The motor current has exceeded the warning/error threshold for the motor current monitoring set in 0x2D46:001.
–
Check motor load.
 
–
Check drive dimensioning.
 
–
Check warning threshold or error threshold set in 0x2D46:001.
 
Fault > inverter disabled (configurable)
–
The event can only be reset after a blocking time.
 
Blocking time: 1 s
Setting parameters: 0x2D46:002
Related topics
 
29445
0x7305
Encoder open circuit
Cause
Remedy
Severity/response
The encoder signal loss monitoring function has detected a failure of the encoder signal.
–
Check the encoder connection.
 
–
Check encoder cable for wire breakage.
 
–
Check encoder current supply.
 
Warning (configurable)
Setting parameters: 0x2C45
Related topics
 
29573
0x7385
Feedback system: speed limit
Cause
Remedy
Severity/response
The feedback system exceeds the maximum permissible frequency range of the digital inputs.
Check feedback system.
Information
Related topics
 
30338
0x7682
Invalid user data
Cause
Remedy
Severity/response
The user parameter settings in the memory module are invalid.
1.
Execute user parameter settings again.
 
2.
Execute device command "Save user data" 0x2022:003.
 
Fault
–
The user parameter settings are lost.
 
–
The default settings were automatically loaded.
 
 
30341
0x7685
Safety - Network/safety bus configuration inconsistent
Cause
Remedy
Severity/response
The active network is not compatible with the configured security protocol for the safety bus.
Configure the network for the safety bus and restart the device.
Warning
 
30345
0x7689
Memory module: invalid OEM data
Cause
Remedy
Severity/response
The OEM memory contains invalid parameter settings or is empty.
–
Execute device command "Save OEM data" 0x2022:006.
 
–
Thus, the user parameter settings get lost!
 
Warning
–
The user parameter settings were automatically loaded.
 
 
30347
0x768B
OEM data are missing
Cause
Remedy
Severity/response
There are no parameter settings preconfigured by the OEM/machine builder in the OEM memory.
Execute the "Save OEM data" (0x2022:006) device command to save the current parameter settings in the OEM memory in a power-failure-proof manner.
Fault
 
30352
0x7690
EPM firmware version incompatible
Cause
Remedy
Severity/response
The parameter settings saved in the memory module are incompatible with the firmware version.
1.
Execute device command "Load default settings" 0x2022:001.
 
2.
Execute "Save user data" 0x2022:003 or "Save OEM data" 0x2022:006 device command.
 
Fault
–
The data have been loaded into the RAM memory, but they are incompatible.
 
 
30357
0x7695
Invalid parameter changeover configuration
Cause
Remedy
Severity/response
One or more parameters can no longer be used for the "Parameter change-over" function.
1.
Check error message for parameter change-over in 0x4047:001.
 
2.
Correct the list entry shown in 0x4047:002.
 
Warning
–
The parameter change-over function is deactivated.
 
 
33042
0x8112
Network - Time-out explicit message
Cause
Remedy
Severity/response
–
Within the time-out period for explicit messages, which has been parameterised by the scanner, no "explicit message" was received.
 
–
The connection to the scanner has been interrupted.
 
–
Failure of an explicit connection.
 
–
Check cables and terminals.
 
–
Plug network cables into the Ethernet port.
 
–
Check the requested package interval (RPI) of the explicit connection.
 
–
Increase time limit for explicit messages in the scanner.
 
Warning (configurable)
Setting parameters: 0x2859:006
 
33044
0x8114
Network - Overall communication time-out
Cause
Remedy
Severity/response
–
EtherNet/IP: the maximum permissible time-out period for the CIP communication set in 0x23A1:010 has been exceeded.
 
–
Modbus TCP/IP: the maximum permissible time-out period for the TCP communication set in 0x23B1:010 has been exceeded.
 
–
Check cables and terminals.
 
–
Connect network cable.
 
Warning (configurable)
Setting parameters: 0x2859:007
 
33046
0x8116
Modbus TCP master time-out
Cause
Remedy
Severity/response
No valid messages have been received by the Modbus master for a time longer than the time-out period set in 0x23B6:001.
Check communication with the master.
Fault > inverter disabled (configurable)
Setting parameters: 0x2859:008
Related topics
 
33047
0x8117
Modbus TCP Keep Alive time-out
Cause
Remedy
Severity/response
For a time longer than the time-out period set in 0x23B6:002, no value was entered into the Keep alive register 0x23B6:005.
Check communication with the master.
Fault > inverter disabled (configurable)
Setting parameters: 0x2859:009
Related topics
 
33162
0x818A
PROFIsafe passivated
Cause
Remedy
Severity/response
Error in the PROFIsafe communication
PROFIsafe was passivated.
Check PROFIsafe component.
Check network cable.
Analyze the error history of the higher-level controller.
Information
 
33165
0x818D
PROFIsafe - CRC1 error
Cause
Remedy
Severity/response
The F-Parameter-CRC is faulty.
Check F-Parameter-CRC (CRC1) in the higher-level controller.
Check device description file (GSDML).
Information
 
33168
0x8190
Network - Watchdog time-out
Cause
Remedy
Severity/response
Time-out during cyclic data reception, e.g. due to an interrupted communication link to the master or missing cyclic data.
–
Check wiring of the network.
 
–
Eliminate EMC interferences.
 
Trouble (configurable)
Setting parameters: 0x2859:001
 
33169
0x8191
Network - Disruption of cyclic data exchange
Cause
Remedy
Severity/response
The communication partner has interrupted the cyclic data exchange.
–
Check wiring of the network.
 
–
The slave must receive new parameterisation and configuration files by the master, in order to be able to exchange data again.
 
Fault
 
33170
0x8192
Network - Initialization error
Cause
Remedy
Severity/response
The initialisation of the communication stack has been interrupted due to an incorrect address setting or communication configuration.
Check master/slave configuration and restart the devices.
Trouble (configurable)
Setting parameters: 0x2859:004
 
33171
0x8193
Network - Invalid cyclic process data
Cause
Remedy
Severity/response
The cyclic process data received are invalid.
Check cyclic process data sent by the master.
Trouble (configurable)
Setting parameters: 0x2859:005
 
33173
0x8195
FSoE - Unexpected command
Cause
Remedy
Severity/response
Unexpected FSoE command received.
Check FSoE configuration.
Restart communication.
Information
 
33174
0x8196
FSoE - Unknown command
Cause
Remedy
Severity/response
Unknown FSoE command received.
Check FSoE configuration.
Restart communication.
Information
 
33175
0x8197
FSoE - Invalid connection ID
Cause
Remedy
Severity/response
FSoE frame with invalid connection ID received.
Check FSoE configuration.
Restart communication.
Information
 
33176
0x8198
FSoE - CRC error
Cause
Remedy
Severity/response
The check of the CRC in the FSoE frames reports errors.
Check FSoE configuration.
Restart communication.
Information
 
33177
0x8199
FSoE - Watchdog expired
Cause
Remedy
Severity/response
FSoE watchdog elapsed.
Check set watchdog time in FSoE master and adapt if necessary.
Information
 
33180
0x819C
FSoE - Invalid communication parameter data
Cause
Remedy
Severity/response
Invalid communication parameter data received.
Check setting of the communication parameters.
Information
 
33181
0x819D
FSoE - Invalid application parameter length
Cause
Remedy
Severity/response
The length of the application parameters transmitted by the FSoE master differs from the expected length.
Check setting of the communication parameters.
Information
 
33182
0x819E
FSoE - Invalid application parameter data
Cause
Remedy
Severity/response
Invalid application parameter data received.
Check setting of the communication parameters.
Information
 
33183
0x819F
FSoE - Passivated
Cause
Remedy
Severity/response
Due to an error, FSoE was passivated.
Check FSoE configuration.
Reset error.
Information
 
33185
0x81A1
Modbus: network time-out
Cause
Remedy
Severity/response
No valid messages have been received via the Modbus for a longer time than the time-out time set in 0x2326:001.
–
Check communication with the master.
 
–
Check wiring.
 
–
Check bus termination.
 
Fault > inverter disabled (configurable)
Setting parameters: 0x2859:012
 
33186
0x81A2
Modbus: incorrect request by master
Cause
Remedy
Severity/response
The request by the master is invalid, e. g. invalid CRC checksum, non-supported function code, or impermissible data access.
Check request by the master:
–
Value in the valid range?
 
–
Function code valid?
 
–
No impermissible write access? (e. g. with regard to read-only parameters)
 
Warning
The inverter (slave) responds to the master with an error code:
–
0x01 = invalid function code
 
–
0x02 = invalid data address
 
–
0x03 = invalid data value
 
–
0x04 = slave device failure
 
 
33192
0x81A8
FSoE - Invalid slave address
Cause
Remedy
Severity/response
The slave address transmitted by the FSoE master differs from the slave address set in the device.
Check slave address in the FSoE master.
Check parameter setting in the device.
Information
 
33193
0x81A9
FSoE - Invalid communication parameter length
Cause
Remedy
Severity/response
The length of the communication parameter transmitted by the FSoE master differs from the expected length.
Check setting of the communication parameters.
Information
 
33201
0x81B1
CIP Safety - Invalid Requested Packet Interval (RPI) of safety inputs
Cause
Remedy
Severity/response
In a safety open request of a multicast input connection, the value for the "Requested Packet Interval" (RPI) is invalid.
Set identical RPI values for each of the multicast input connections in the configuration software of the originator.
Information
Related topics
 
33202
0x81B2
CIP Safety - Invalid multicast input connection parameters
Cause
Remedy
Severity/response
Mismatch in the network connection parameters T->O within one of the safety open requests of a multicast connection.
Check the configured connection parameters in the configuration software of the originator (safety master), e.g. RPI (Requested Packet Interval) and maximum number of consumers.
Information
Related topics
 
33203
0x81B3
CIP Safety - Invalid max. number of multicast input connections
Cause
Remedy
Severity/response
"Max Consumer Number" is invalid, the maximum number of consumer connections has been exceeded.
Check the number of supported consumers. See documentation for the originator (safety master).
Information
Related topics
 
33204
0x81B4
CIP Safety - Different originator ID of the output connection (OCPUNID)
Cause
Remedy
Severity/response
The "Output Connection Point" (OCPUNID) of the received safety open request belongs to another originator.
Check whether the correct originator (safety master) is being used.
If a new originator (safety master) is to be used:
1.
Reset previous OCPUNID: In the parameterization dialog for safety parameters execute the "Reset CIP Safety Output Connection Ownership" command via the CIP Safety menu.
 
2.
The OCPUNID of the new originator is transferred with the next safety open request.
 
Information
Related topics
 
33205
0x81B5
CIP Safety - Different safety configuration signature (SCID)
Cause
Remedy
Severity/response
Type 2a Safety open request received with mismatched SCID.
Copy the correct SCID from the parameterization dialog for safety parameters into the configuration software of the originator.
Information
Related topics
 
33206
0x81B6
CIP Safety - Invalid Requested Packet Interval (RPI) of outputs
Cause
Remedy
Severity/response
The "Requested Packet Interval" (RPI) for the outputs in the safety open request is invalid.
–
Check whether the appropriate EDS file from the Application Knowledge Base (AKB) is used for this device.
 
–
If it is not possible to use an EDS file, use the relevant connection data from the corresponding EDS file instead.
 
Information
Related topics
 
33207
0x81B7
CIP Safety - Error in connection path (EPATH)
Cause
Remedy
Severity/response
Error in the connection path (EPATH) of the received safety open request.
–
Check whether the appropriate EDS file from the Application Knowledge Base (AKB) is used for this device.
 
–
If it is not possible to use an EDS file, use the relevant connection data from the corresponding EDS file instead.
 
Information
Related topics
 
33208
0x81B8
CIP Safety - Connection management error
Cause
Remedy
Severity/response
Error in the connection management of the received safety open request.
Check the configured connection parameters in the configuration software of the originator (safety master).
Information
Related topics
 
33209
0x81B9
CIP Safety - Device identification error
Cause
Remedy
Severity/response
Mismatch in the device identification in the electronic key data of the received safety open request.
Check whether the appropriate EDS file from the Application Knowledge Base (AKB) is used for this device.
Information
Related topics
 
33210
0x81BA
CIP Safety - Time Coordination Message error
Cause
Remedy
Severity/response
Error in a received time coordination message.
Check the connection parameters configured for the output data in the configuration software of the originator (safety master), e.g. timeout multiplier and network delay.
Information
Related topics
 
33211
0x81BB
CIP Safety - Output error
Cause
Remedy
Severity/response
Error in a received output message, e.g. CRC error, data aging error, error in the complementary data.
Restart the device. If the error persists, contact the manufacturer.
Information
Related topics
 
33212
0x81BC
CIP Safety - Time Correction Message error
Cause
Remedy
Severity/response
Error in a received time correction message.
Check the connection parameters configured for the output data in the configuration software of the originator (safety master), e.g. timeout multiplier and network delay.
Information
Related topics
 
33213
0x81BD
CIP Safety - Timestamp Message error
Cause
Remedy
Severity/response
Error in a received timestamp message.
Check the connection parameters configured for the output data in the configuration software of the originator (safety master), e.g. timeout multiplier and network delay.
Information
Related topics
 
33214
0x81BE
CIP Safety - Internal communication error between safety option and basic device
Cause
Remedy
Severity/response
Internal communication error between safety option and basic device.
Termination of a CIP Safety connection by the originator (safety master).
Restart the device. If the error persists, contact the manufacturer.
Information
Related topics
 
33215
0x81BF
The safety protocol is not supported
Cause
Remedy
Severity/response
The safety protocol selected in 0x2128 is not supported by the safety option.
–
Check whether the selected safety protocol is supported by the safety option (display parameter 0x212C:003).
 
–
Use device/safety option with an activated safety protocol license.
 
Fault
 
33217
0x81C1
IO-Link port 1 error
Cause
Remedy
Severity/response
An event of the type "Error" has occurred at IO-Link port 1.
–
Check connected IO-Link device.
 
–
Check configuration of the IO-Link port.
 
No response (configurable)
Setting parameters: 0x24A1:047
Related topics
 
33218
0x81C2
IO-Link port 2 error
Cause
Remedy
Severity/response
An event of the type "Error" has occurred at IO-Link port 2.
–
Check connected IO-Link device.
 
–
Check configuration of the IO-Link port.
 
No response (configurable)
Setting parameters: 0x24A2:047
Related topics
 
33219
0x81C3
IO-Link port 3 error
Cause
Remedy
Severity/response
An event of the type "Error" has occurred at IO-Link port 3.
–
Check connected IO-Link device.
 
–
Check configuration of the IO-Link port.
 
No response (configurable)
Setting parameters: 0x24A3:047
Related topics
 
33220
0x81C4
IO-Link port 4 error
Cause
Remedy
Severity/response
An event of the type "Error" has occurred at IO-Link port 4.
–
Check connected IO-Link device.
 
–
Check configuration of the IO-Link port.
 
No response (configurable)
Setting parameters: 0x24A4:047
Related topics
 
33221
0x81C5
IO-Link port 1 warning
Cause
Remedy
Severity/response
An event of the type “Warning" has occurred at IO-Link port 1.
–
Check connected IO-Link device.
 
–
Check configuration of the IO-Link port.
 
No response (configurable)
Setting parameters: 0x24A1:048
Related topics
 
33222
0x81C6
IO-Link port 2 warning
Cause
Remedy
Severity/response
An event of the type “Warning" has occurred at IO-Link port 2.
–
Check connected IO-Link device.
 
–
Check configuration of the IO-Link port.
 
No response (configurable)
Setting parameters: 0x24A2:048
Related topics
 
33223
0x81C7
IO-Link port 3 warning
Cause
Remedy
Severity/response
An event of the type “Warning" has occurred at IO-Link port 3.
–
Check connected IO-Link device.
 
–
Check configuration of the IO-Link port.
 
No response (configurable)
Setting parameters: 0x24A3:048
Related topics
 
33224
0x81C8
IO-Link port 4 warning
Cause
Remedy
Severity/response
An event of the type “Warning" has occurred at IO-Link port 4.
–
Check connected IO-Link device.
 
–
Check configuration of the IO-Link port.
 
No response (configurable)
Setting parameters: 0x24A4:048
Related topics
 
33414
0x8286
Network - PDO mapping error
Cause
Remedy
Severity/response
–
Invalid PDO assignment by the master.
 
–
Internal PDO assignment was changed and does not comply with the configuration available in the master.
 
Check data mapping in the master and slave.
Trouble (configurable)
Setting parameters: 0x2859:003
 
33418
0x828A
Invalid Mapping: duplicate Rx-Entries present
Cause
Remedy
Severity/response
Various data sources can be selected, such as the network, IO-Link, or the Logic PLC. However, receivable objects may be selected only once. When the assignment is activated, this is checked, and this error message appears if an object has been assigned more than once.
Correct duplicate assignments of receivable objects.
Warning
 
33553
0x8311
Torque limit reached
Cause
Remedy
Severity/response
Motor has reached the torque limit:
–
0x2949:003: Actual positive torque limit
 
–
0x2949:004: Actual negative torque limit
 
–
Observe load requirements.
 
–
Reduce motor load.
 
–
Check set torque limits and sources for the torque limits.
 
No response (configurable)
Setting parameters: 0x2D67:001
Related topics
 
33664
0x8380
Function not allowed in selected operating mode
Cause
Remedy
Severity/response
The selected function is not permissible in the chosen operating mode.
–
Selection of torque mode [-1] in 0x6060 with incompatible motor control in 0x2C00.
 
–
Selection of invalid drive mode [0] in 0x6060.
 
–
Note: selection of torque mode [-1] in 0x6060 with incompatible motor control in 0x2C00.
 
–
Check settings of operation modes.
 
–
 
Warning
 
34432
0x8680
Overrun positive software limit
Cause
Remedy
Severity/response
The monitoring of the software end positions is active and the positive software limit position has been overridden.
–
Check the setting of the software limit positions.
 
–
Check movement specifications.
 
Warning (configurable)
Setting parameters: 0x500A:105
 
34433
0x8681
Overrun negative software limit
Cause
Remedy
Severity/response
The monitoring of the software end positions is active and the negative software limit position has been overridden.
–
Check the setting of the software limit positions.
 
–
Check movement specifications.
 
Warning (configurable)
Setting parameters: 0x500A:105
 
34434
0x8682
Overrun positive hardware limit switch
Cause
Remedy
Severity/response
The positive hardware limit switch has been overridden.
Check movement specifications.
Warning (configurable)
Setting parameters: 0x500A:104
 
34435
0x8683
Overrun negative hardware limit switch
Cause
Remedy
Severity/response
The negative hardware limit switch has been overridden.
Check movement specifications.
Warning (configurable)
Setting parameters: 0x500A:104
 
34436
0x8684
Following error - Warning level exceeded
Cause
Remedy
Severity/response
The warning threshold for the following error has been exceeded.
Check controller settings, encoder parameterization and mechanics.
Warning
 
34437
0x8685
Following error - Error level exceeded
Cause
Remedy
Severity/response
The error threshold for the following error has been exceeded.
Check controller settings, encoder parameterization and mechanics.
Warning (configurable)
Setting parameters: 0x500A:059
 
34448
0x8690
Invalid profile parameters
Cause
Remedy
Severity/response
Invalid profile parameters.
Check profile parameters.
Warning
 
34449
0x8691
Invalid positioning mode
Cause
Remedy
Severity/response
An invalid positioning mode has been selected.
Check profile parameters for positioning mode.
Warning
 
34450
0x8692
Invalid acceleration
Cause
Remedy
Severity/response
Specification of an invalid acceleration (at standstill).
Check profile parameters for acceleration.
Warning
 
34451
0x8693
Invalid deceleration
Cause
Remedy
Severity/response
Specification of an invalid deceleration (at standstill).
Check profile parameters for deceleration.
Warning
 
34452
0x8694
Invalid velocity
Cause
Remedy
Severity/response
Specification of an invalid speed (at standstill).
Check profile parameters for speed.
Warning
 
34453
0x8695
Axis not homed
Cause
Remedy
Severity/response
For the axis, no home position is known.
Execute homing.
Fault
 
34454
0x8696
Maximum value exceeded
Cause
Remedy
Severity/response
The profile parameter for speed, acceleration or jerk exceeds the respective maximum value.
–
Check profile parameters.
 
–
Adjust the maximum values for speed, acceleration and jerk.
 
Warning (configurable)
Setting parameters: 0x500A:106
 
34455
0x8697
Target position outside software limits
Cause
Remedy
Severity/response
The target position is outside the software limit positions.
–
Check the setting of the software limit positions.
 
–
Check profile parameters.
 
Warning
 
34456
0x8698
Parameterization of positioning is implausible
Cause
Remedy
Severity/response
In the first driving cycle, the profile parameters result in a mathematically longer braking distance than the total distance. When braking during an overchange profile, the final speed to which deceleration is to take place is greater than the speed currently being generated.
Adapt profile parameters.
Warning
 
36992
0x9080
Discrepancy check or function check error - SD-In1
Cause
Remedy
Severity/response
Signal error at safe input SD-In1.
Check parameter setting.
Check wiring.
Warning
 
36993
0x9081
Discrepancy check or function check error - SD-In2
Cause
Remedy
Severity/response
Signal error at safe input SD-In2.
Check parameter setting.
Check wiring.
Warning
 
36996
0x9084
Disabled SD-In1 = HIGH
Cause
Remedy
Severity/response
Initialization error or parameterization error.
HIGH level detected at the deactivated safe input.
Check parameter setting.
Check wiring.
Warning
 
36997
0x9085
Disabled SD-In2 = HIGH
Cause
Remedy
Severity/response
Initialization error or parameterization error.
HIGH level detected at the deactivated safe input.
Check parameter setting.
Check wiring.
Warning
 
37000
0x9088
SD-Out1 - Channel A remains stuck at HIGH
Cause
Remedy
Severity/response
Channel A of SD_Out1 cannot be deactivated.
Check wiring for short circuit.
Warning
 
37001
0x9089
SD-Out1 - Channel A remains stuck at LOW
Cause
Remedy
Severity/response
Channel A of SD_Out1 cannot be activated.
Check wiring.
Check supply voltage.
Warning
 
37002
0x908A
SD-Out1 - Channel B remains stuck at HIGH
Cause
Remedy
Severity/response
Channel B of SD_Out1 cannot be deactivated.
Check wiring for short circuit.
Warning
 
37003
0x908B
SD-Out1 - Channel B remains stuck at LOW
Cause
Remedy
Severity/response
Channel B of SD_Out1 cannot be activated.
Check wiring.
Check supply voltage.
Warning
 
37004
0x908C
SD-In1 - Channel A remains stuck at HIGH
Cause
Remedy
Severity/response
Channel A of SD_In1 cannot be deactivated.
Check wiring for short circuit.
Check configuration of the safe input.
Warning
 
37005
0x908D
SD-In1 - Channel B remains stuck at HIGH
Cause
Remedy
Severity/response
Channel B of SD_In1 cannot be deactivated.
Check wiring for short circuit.
Check configuration of the safe input.
Warning
 
37006
0x908E
SD-In2 - Channel A remains stuck at HIGH
Cause
Remedy
Severity/response
Channel A of SD_In2 cannot be deactivated.
Check wiring for short circuit.
Check configuration of the safe input.
Warning
 
37007
0x908F
SD-In2 - Channel B remains stuck at HIGH
Cause
Remedy
Severity/response
Channel B of SD_In2 cannot be deactivated.
Check wiring for short circuit.
Check configuration of the safe input.
Warning
 
37012
0x9094
CLA/CLB - Short circuit
Cause
Remedy
Severity/response
Short circuit at the CLA/CLB clock outputs.
Check wiring.
Warning
 
65282
0xFF02
Fault - Motor holding brake
Cause
Remedy
Severity/response
Brake failure due to a short circuit, cable break, or power fluctuations/outages.
–
Check the brake wiring for short circuits or cable breaks.
 
–
Check the connection cable used (low-capacitance shielding).
 
–
Check the power supply wiring.
 
–
Ensure a stable power supply.
 
Fault
 
65285
0xFF05
Safe torque off (STO) activated
Cause
Remedy
Severity/response
"Safe Torque Off (STO)" has been activated via Safety. The movement is interrupted although the controller is still enabled.
Note: The event ID 0xFF05 has a different meaning for the i550 cabinet and i550 protec inverters: The integrated safety technology is defective. (The device must be replaced.)
Enable "Safe Torque Off (STO)" again or disable controller.
In the event of false tripping, check the wiring at connection X1.
No response (configurable)
Setting parameters: 0x2024:003
 
65286
0xFF06
Motor overspeed
Cause
Remedy
Severity/response
The motor speed has reached the error threshold for overspeed set in 0x2D44:001.
Adapt the maximum motor speed 0x6080 and the warning threshold or error threshold 0x2D44:001.
Fault > inverter disabled (configurable)
–
The event can only be reset after a blocking time.
 
Blocking time: 1 s
Setting parameters: 0x2D44:002
Related topics
 
65289
0xFF09
Motor phase missing
Cause
Remedy
Severity/response
A failure of several motor phases has been detected.
–
Check wiring between inverter and motor.
 
–
In case of a false tripping, adapt the settings for the motor phase failure detection.
 
No response (configurable)
–
The event can only be reset after a blocking time.
 
Blocking time: 2 s
Setting parameters: 0x2D45:001
 
65290
0xFF0A
Motor phase failure phase U
Cause
Remedy
Severity/response
A failure of the motor phase U has been detected.
–
Check wiring between inverter and motor.
 
–
In case of a false tripping, adapt the settings for the motor phase failure detection.
 
–
0x2D45:002 (Current threshold)
 
–
0x2D45:003 (Voltage threshold)
 
 
No response (configurable)
–
The event can only be reset after a blocking time.
 
Blocking time: 2 s
Setting parameters: 0x2D45:001
 
65291
0xFF0B
Motor phase failure phase V
Cause
Remedy
Severity/response
A failure of the motor phase V has been detected.
–
Check wiring between inverter and motor.
 
–
In case of a false tripping, adapt the settings for the motor phase failure detection.
 
–
0x2D45:002 (Current threshold)
 
–
0x2D45:003 (Voltage threshold)
 
 
No response (configurable)
–
The event can only be reset after a blocking time.
 
Blocking time: 2 s
Setting parameters: 0x2D45:001
 
65292
0xFF0C
Motor phase failure phase W
Cause
Remedy
Severity/response
No response (configurable)
–
The event can only be reset after a blocking time.
 
Blocking time: 2 s
Setting parameters: 0x2D45:001
 
65305
0xFF19
Motor parameter identification fault
Cause
Remedy
Severity/response
During the automatic identification of the motor, an error has occurred.
–
Set motor data so that they comply with the data on the motor nameplate.
 
–
Check wiring of the motor.
 
Fault
 
65335
0xFF37
Automatic start disabled
Cause
Remedy
Severity/response
At mains connection, a start command was already available and the automatic start at power-up is set in 0x2838:002 to "Off [0]".
Deactivate starting command and reset error.
Fault
 
65336
0xFF38
Load loss detected
Cause
Remedy
Severity/response
In a running motor, the motor load (current) is monitored. When the motor load falls below the threshold value specified in Load loss detection: threshold (0x4006:001) for the period of time specified in Load loss detection: delay time (0x4006:002), load loss protection is triggered.
Check utilisation
No response (configurable)
Setting parameters: 0x4006:003
 
65337
0xFF39
Motor overload
Cause
Remedy
Severity/response
If the apparent motor current exceeds a defined threshold value 0x4007:002 for a certain amount of time 0x4007:001, heavy duty monitoring is triggered.
Check the motor load.
No response (configurable)
Setting parameters: 0x4007:003
 
65366
0xFF56
Maximum motor frequency reached
Cause
Remedy
Severity/response
–
The limitation of the maximum motor speed set in 0x6080 is active.
 
–
The maximum output frequency of the inverter has been reached.
 
–
Depending on the parameter setting of 0x2D44:001 (Overspeed monitoring: threshold), the speed limitation (0x6080 / Max. motor speed) may become active before speed monitoring.
 
Check application.
Warning
 
65370
0xFF5A
Manual mode disabled
Cause
Remedy
Severity/response
Indicates the deactivation of the manual speed control.
Warning
 
65371
0xFF5B
Manual mode activated
Cause
Remedy
Severity/response
Indicates the activation of the manual speed control.
Warning
 
65372
0xFF5C
Manual mode time-out
Cause
Remedy
Severity/response
If "manual operation" is active, an error is generated in case the communication links get lost.
The error can be only be reset if the connection is restored or the control mode is changed to a different value than "manual operation".
Fault
 
65373
0xFF5D
Safety option - Internal error
Cause
Remedy
Severity/response
The integrated safety technology is defective.
The inverter must be replaced.
Note!
The user is not allowed to change inverters that come with integrated safety technology.
–
The safety module must not be removed.
 
–
The user must not carry out any repairs on the safety module.
 
–
The safety module is not a spare part.
 
Fault
–
The inverter is disabled immediately. The motor has no torque (is coasting).
 
–
The event can only be reset by mains switching.
 
 
65405
0xFF7D
SW update detected
Cause
Remedy
Severity/response
A modified safety-related software component (safety firmware or safety boot loader) has been detected.
Acknowledge the update of the software component using the parameterization dialog for safety parameters or the confirmation button S82.
Warning
 
65408
0xFF80
Internal error
Cause
Remedy
Severity/response
Failed to update the internal controller. This controller can only be updated if the device has been switched off for at least 10 seconds.
Disconnect the device from all power sources for at least 10 seconds and then switch it on again.
Fault
–
The inverter is disabled immediately. The motor has no torque (is coasting).
 
–
The event can only be reset by mains switching.
 
 
65410
0xFF82
Safety firmware update failed
Cause
Remedy
Severity/response
The firmware update of a component has failed due to an interruption or an error.
–
Check firmware package.
 
–
Repeat the device update process after switching off the power.
 
Fault
 
65457
0xFFB1
MUT - Muting function active
Cause
Remedy
Severity/response
MUT - Muting function active
For information only. No remedy necessary.
Information
–
The activated safety function STO is deactivated in the inverter.
 
 
65458
0xFFB2
MUT - Muting function completed
Cause
Remedy
Severity/response
MUT - Muting function completed
For information only. No remedy necessary.
Information
–
The activated safety functions are executed again in the inverter.
 
 
65459
0xFFB3
MUT - Muting function aborted
Cause
Remedy
Severity/response
Communication error. The muting function was canceled.
Reconnect to the device.
Restart the muting function.
Information
–
The activated safety functions are executed again in the inverter.