Causes and remedies
|
Cause
|
Remedy
|
Severity/response
|
|
–
Continuous overcurrent on the inverter/motor side.
–
DC bus relay has not been closed due to a malfunction.
|
–
Check motor and wiring for short circuits.
|
Fault
–
The inverter is disabled immediately. The motor has no torque (is coasting).
–
The event can only be reset after a blocking time.
|
|
Blocking time: 2 s
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
–
Short circuit/earth fault of motor cable
–
Capacitive charging current of the motor cable
too high.
|
–
Check motor cable.
–
Check length of the motor cable.
–
Use shorter or lower-capacitance motor cable.
|
Fault
–
The inverter is disabled immediately. The motor has no torque (is coasting).
–
The event can only be reset after a blocking time.
|
|
Blocking time: 2 s
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Short circuit of motor cable
|
Check motor cable for short circuit.
|
Fault
–
The inverter is disabled immediately. The motor has no torque (is coasting).
–
The event can only be reset after a blocking time.
|
|
Blocking time: 2 s
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Motor thermally overloaded, e. g.
by an impermissible continuous current or by frequent or too long acceleration processes.
|
–
Check drive sizing.
–
Check machine/driven mechanics for excessive load.
–
Check settings of the motor data.
–
Reduce values for slip compensation 0x2B09:001, 0x2B09:002 and oscillation damping 0x2B0A:001, 0x2B0A:002.
|
Fault > inverter disabled (configurable)
–
The event can only be reset after a blocking time.
|
|
Blocking time: 2 s
|
||
|
Setting parameters: 0x2D4B:003
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
Device utilisation (ixt) too high by frequent and too long acceleration processes.
|
Fault > inverter disabled (configurable)
–
The event can only be reset after a blocking time.
|
|
|
Blocking time: 2 s
|
||
|
Setting parameters: 0x2D40:005
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
Device utilisation (ixt) too high by frequent and too long acceleration processes.
|
Warning
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
Maximum current of the axis (display in
0x2DDF:002) has been reached
too often in succession.
|
–
Select a flatter speed ramp.
–
Reduce the load.
–
Set Imax controller more dynamically.
|
Fault
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
Overload of the motor with sensorless control for synchronous motors.
|
–
Reduce load at the axis.
–
Check the settings of the parameters for sensorless control.
|
Trouble
–
The inverter is disabled immediately. The motor has no torque (is coasting).
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
Mains phase failure
|
–
Check wiring of the mains connection.
–
Check fuses.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
DC-bus voltage has exceeded the error threshold for overvoltage due to a too high braking energy or a too high mains voltage. The error threshold (display in 0x2540:006) results from the setting of the rated mains voltage in 0x2540:001.
|
–
Reduce dynamic performance of the load profile.
–
Check mains voltage.
–
Check settings for brake energy management.
|
Fault
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
DC-bus voltage has exceeded the warning threshold for overvoltage set in 0x2540:005 due to a too high braking energy or a too high mains voltage.
|
–
Reduce dynamic performance of the load profile.
–
Check mains voltage.
–
Check settings for brake energy management.
|
Warning
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
DC-bus voltage has fallen below the error threshold for undervoltage. The error threshold (display in 0x2540:003) results from the setting of the rated mains voltage in 0x2540:001.
|
Trouble
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
DC-bus voltage
has fallen below the warning threshold for undervoltage set in 0x2540:002.
|
Warning
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
The input voltage is too low to switch on the inverter.
|
–
Check mains voltage.
–
Check mains settings.
–
Check fuses.
|
Warning
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
The heatsink temperature of the power unit (display in 0x2D84:001) has exceeded the fixed error threshold (110 °C).
–
Ambient temperature too high.
–
Fan or ventilation slots are polluted.
–
Fan is defective.
|
–
Check mains voltage.
–
Provide for a sufficient cooling of the device. In case of a 100 % load, 75 °C to 85 °C are normal. Display of the heatsink temperature in 0x2D84:001.
–
Clean fan and ventilation slots. If required, replace fan.
–
Reduce switching frequency in 0x2939.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Sensor for the temperature monitoring of the power unit is defective. The failure of the temperature monitoring function poses the risk of overheating!
|
Hardware error: it is necessary to contact the manufacturer, since
the device must be replaced.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Warning of the heatsink fan.
|
Clean fan and ventilation slots. If required, replace fan. The fans can be unlocked via locking hooks and can then be removed.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The heatsink temperature of the power unit (display in 0x2D84:001) has exceeded the warning threshold set in 0x2D84:002.
–
Ambient temperature too high.
–
Fan or ventilation slots are polluted.
–
Fan is defective.
|
–
Provide for a sufficient cooling of the device.
–
Clean fan and ventilation slots.
–
If required, replace fan.
|
Warning
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
The PTC or thermal contact connected to the motor connector/terminal X105 or terminal 109 measures a too high motor temperature.
–
Motor too hot by impermissibly high currents.
–
Motor too hot by frequent and too long acceleration processes.
|
–
Check drive sizing.
–
Check PTC/thermal contact and wiring.
–
If no PTC or thermal contact is connected to T1 and T2, deactivate motor temperature monitoring: 0x2D49:002 = 0
|
Fault > inverter disabled (configurable)
–
The event can only be reset after a blocking time.
|
|
Blocking time: 2 s
|
||
|
Setting parameters: 0x2D49:002
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, replace the device.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, replace the device.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, replace the device.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, replace the device.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, replace the device.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, replace the device.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
External supply voltage failed or too low.
|
–
Check the optional auxiliary power supply on the X100.1/24E or X5/24E, if connected.
–
Check mains voltage.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, replace the device.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, replace the device.
|
Fault
–
The inverter is disabled immediately. The motor has no torque (is coasting).
–
The event can only be reset by mains switching.
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, replace the device.
|
Fault
–
The inverter is disabled immediately. The motor has no torque (is coasting).
–
The event can only be reset by mains switching.
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Output current at the 24V output or at the digital outputs too high.
|
Check 24V output and digital outputs for earth fault or overload.
|
Fault > inverter disabled (configurable)
|
|
Setting parameters: 0x2630:020
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
An exception has occurred in the PLC application.
|
–
Update PLC application.
–
Restart the device (recommended).
|
Fault > inverter disabled (configurable)
|
|
Setting parameters: 0x5811:002
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
An infinite loop was detected in the PLC application.
|
–
Load a new PLC application into the device.
–
Restart the device (recommended).
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, replace the device.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, replace the device.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Warning of the internal fan.
|
Check/replace internal fan.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, replace the device.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, replace the device.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, replace the device.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, replace the device.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The assignment directives have not been observed.
–
If the "flexible I/O configuration" is active as control source, the "Enable inverter" or "Run" function must be connected to a digital input in order that the motor can be stopped again any time!
–
The use of the "Start forward (CW)" and "Start reverse (CCW)" functions excludes the use of the "Run forward (CW)" and "Run reverse (CCW)" functions, and vice versa.
|
Check and correct the assignment of the triggers to the functions.
–
With network control, the two "Enable inverter 0x2631:001" and "Run 0x2631:002" functions can also be set to "Constant TRUE [1]" to start the motor.
|
Trouble
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
Flexible I/O configuration: the "Activate fault 1" function was activated via the trigger selected in 0x2631:043.
|
Eliminate error cause and then reset error.
|
Fault > inverter disabled (configurable)
|
|
Setting parameters: 0x2842:001
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
Flexible I/O configuration: the "Activate fault 2" function was activated via the trigger selected in 0x2631:044.
|
Eliminate error cause and then reset error.
|
Fault > inverter disabled (configurable)
|
|
Setting parameters: 0x2842:003
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
–
Negative setpoint selection with an active limitation of rotation 0x283A.
–
The "Reverse rotational direction" 0x2631:013 function was requested with an active limitation of rotation 0x283A.
|
Warning
–
The motor is brought to a standstill, since a reversal of the rotating direction is not permissible.
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
The number of permitted restart attempts after a fault set in 0x2839:003 was exceeded. The fault occurred to frequently and could not be reset.
|
Check and the eliminate the fault.
|
Fault
–
The motor remains at a standstill, no automatic restart is executed.
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
The "Activate fault 1" function was triggered via the NetWordIN1 data word 0x4008:001.
|
Eliminate error cause and then reset error.
|
Fault
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
The "Activate fault 2" function was triggered via the NetWordIN1 data word 0x4008:001.
|
Eliminate error cause and then reset error.
|
Fault
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
Two bits of the NetWordIN1 data word 0x4008:001 were assigned to the same function.
|
Check and correct configuration of the NetWordIN1 data word.
–
The functions that are to be triggered via bits 0 ... 15 of the NetWordIN1 data word are defined in 0x400E:001 ... 0x400E:016.
|
Trouble
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
The data length of the F_CRC in the higher-level controller is faulty.
|
Check safety parameter in the higher-level controller.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The F parameter version is not supported by the device.
|
Select supported F parameter version in the higher-level controller.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Safety parameter set deleted
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
New safety parameter set loaded
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The safe parameter sets on the memory module and in the device are different.
|
Load safe parameter set into the device. Acknowledge modification with confirmation button S82.
|
Warning
–
The inverter is safely switched off.
–
The integrated functional safety is in the service status.
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
No safe parameter set was found in the device.
|
Load safe parameter set into the device. Acknowledge modification with confirmation button S82.
|
Warning
–
The inverter is safely switched off.
–
The integrated functional safety is in the service status.
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
The safe parameter set in the device is faulty.
|
Load safe parameter set into the device. Acknowledge modification with confirmation button S82.
|
Warning
–
The inverter is safely switched off.
–
The integrated functional safety is in the service status.
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
Format error in the safe parameter set.
Warning message of an inverter with Extended Safety in the as-delivered state.
|
Reset the safe parameter set in the device and load it again. Acknowledge modification with confirmation button S82.
|
Warning
–
The inverter is safely switched off.
–
The integrated functional safety is in the service status.
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
The set safety parameters are not plausible.
|
1.
Determine the error number in 0x2115:005 and analyze it using the table of plausibility errors.
2.
Correct error.
3.
Reload safe parameter set.
4.
Acknowledge modification with confirmation button S82.
|
Warning
–
The inverter is safely switched off.
–
The integrated functional safety is in the service status.
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
A communication error has occurred while loading the safe parameter set.
|
–
Check communication settings.
–
Check memory module.
–
Reload safe parameter set. Acknowledge modification with confirmation button S82.
|
Warning
–
The inverter is safely switched off.
–
The integrated functional safety is in the service status.
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
The safety addresses in the device and on the memory module are different.
|
–
Adapt safety addresses.
–
Reload safe parameter set. Acknowledge modification with confirmation button S82.
|
Warning
–
The inverter is safely switched off.
–
The integrated functional safety is in the service status.
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
No release information is available on the memory module.
|
After transferring an application with the "Application Loader", the release information for the safe parameter set must be generated separately for each device with the »EASY Starter« or »PLC Designer« via the +Safety parameter list+ and transferred to the device. After transmission, the safe parameter set must be saved in the device using the "Save" command.
|
Information
–
The inverter is safely switched off.
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
The calculation of speed and position values has led to an internal value limit.
|
Check the parameters for the valid travel range and for setting the gearbox factor.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Calibration data of the control unit not compatible or faulty.
|
–
Update firmware of the inverter to the most recent version.
–
If the error persists, the control unit or the device has to be replaced. In this case, please contact the manufacturer.
|
Fault
–
The event can only be reset by mains switching.
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Calibration data of the power unit not compatible or faulty.
|
–
Update firmware of the inverter to the most recent version.
–
If the error persists, the power unit or the device has to be replaced. In this case, please contact the manufacturer.
|
Fault
–
The event can only be reset by mains switching.
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The power unit installed is not supported by the software.
|
Update firmware of the inverter to the most recent version.
|
Fault
–
The event can only be reset by mains switching.
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The last setting of the connection level differs from the saved setting.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The monitoring function of the input signal configured for analog input 1 in 0x2636:008 and 0x2636:009 has been triggered.
|
–
Check input signal at analog input 1.
–
Check configuration of the monitoring function.
|
Information (configurable)
|
|
Setting parameters: 0x2636:010
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The monitoring function of the input signal configured for analog input 2 in 0x2637:008 and 0x2637:009 has been triggered.
|
–
Check input signal at analog input 2.
–
Check configuration of the monitoring function.
|
Information (configurable)
|
|
Setting parameters: 0x2637:010
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Failure of the process temperature input, caused by:
–
Wire break
–
Short circuit
–
Incorrect setting for the temperature sensor type in 0x2636:002
|
–
Check the wiring of the process temperature input.
–
Check the temperature sensor type setting in 0x2636:002.
|
Warning
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
The process temperature has exceeded the lower monitoring threshold set in 0x2638:003.
|
–
Check the process temperature.
–
Check the set monitoring threshold.
|
No response (configurable)
–
The event can only be reset after a blocking time.
|
|
Blocking time: 5 s
|
||
|
Setting parameters: 0x2638:006
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
The process temperature has exceeded the upper monitoring threshold set in 0x2638:004.
|
–
Check the process temperature.
–
Check the set monitoring threshold.
|
No response (configurable)
–
The event can only be reset after a blocking time.
|
|
Blocking time: 5 s
|
||
|
Setting parameters: 0x2638:007
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
An error was detected on analog input 1 (0x2DA4:016, bits 9, 10, 11).
|
Check the signal at analog input 1.
|
Information (configurable)
|
|
Setting parameters: 0x2636:015
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
An error was detected on analog input 2 (0x2DA5:016, bits 9, 10, 11).
|
Check the signal at analog input 2.
|
Information (configurable)
|
|
Setting parameters: 0x2637:015
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
Open circuit
or short circuit at analog output 1.
|
Warning
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
–
Too many deviations during the pole position identification.
–
Compared to the inverter, the rated motor current is too high or too low.
|
–
Check setting of the motor data.
–
Ensure that the motor is at a standstill during the pole position identification process.
–
Ensure that the motor and inverter match each other in terms of power.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The motor current has exceeded the warning/error threshold for the motor current monitoring set in 0x2D46:001.
|
–
Check motor load.
–
Check drive dimensioning.
–
Check warning threshold or error threshold set in 0x2D46:001.
|
Fault > inverter disabled (configurable)
–
The event can only be reset after a blocking time.
|
|
Blocking time: 1 s
|
||
|
Setting parameters: 0x2D46:002
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
The encoder signal loss monitoring function has detected a failure of the encoder signal.
|
–
Check the encoder connection.
–
Check encoder cable for wire breakage.
–
Check encoder current supply.
|
Warning (configurable)
|
|
Setting parameters: 0x2C45
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
The feedback system exceeds the maximum permissible frequency range of the digital inputs.
|
Check feedback system.
|
Information
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
The user parameter settings in the memory module are invalid.
|
Fault
–
The user parameter settings are lost.
–
The default settings were automatically loaded.
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The active network is not compatible with the configured security protocol for the safety bus.
|
Configure the network for the safety bus and restart the device.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The OEM memory contains invalid parameter settings or is empty.
|
Warning
–
The user parameter settings were automatically loaded.
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
There are no parameter settings preconfigured by the OEM/machine builder in the OEM memory.
|
Execute the "Save OEM data" (0x2022:006) device command to save the current parameter settings in the OEM memory in a power-failure-proof manner.
|
Fault
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
The parameter settings saved in the memory module
are incompatible with the firmware version.
|
1.
Execute device command "Load default settings" 0x2022:001.
2.
Execute "Save user data" 0x2022:003 or "Save OEM data" 0x2022:006 device command.
|
Fault
–
The data have been loaded into the RAM memory, but they are incompatible.
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
One or more parameters can no longer be used for the "Parameter change-over" function.
|
1.
Check error message for parameter change-over in 0x4047:001.
2.
Correct the list entry shown in 0x4047:002.
|
Warning
–
The parameter change-over function is deactivated.
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
–
Within the time-out period for explicit messages, which has been parameterised by the scanner, no "explicit message" was received.
–
The connection to the scanner has been interrupted.
–
Failure of an explicit connection.
|
–
Check cables and terminals.
–
Plug network cables into the Ethernet port.
–
Check the requested package interval (RPI) of the explicit connection.
–
Increase time limit for explicit messages in the scanner.
|
Warning (configurable)
|
|
Setting parameters: 0x2859:006
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
–
EtherNet/IP: the maximum permissible time-out period for the CIP communication set in 0x23A1:010 has been exceeded.
–
Modbus TCP/IP: the maximum permissible time-out period for the TCP communication set in 0x23B1:010 has been exceeded.
|
–
Check cables and terminals.
–
Connect network cable.
|
Warning (configurable)
|
|
Setting parameters: 0x2859:007
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
No valid messages have been received by the Modbus master for a time longer than the time-out period set in 0x23B6:001.
|
Check communication with the master.
|
Fault > inverter disabled (configurable)
|
|
Setting parameters: 0x2859:008
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
For a time longer than the time-out period set in 0x23B6:002, no value was entered into the Keep alive register 0x23B6:005.
|
Check communication with the master.
|
Fault > inverter disabled (configurable)
|
|
Setting parameters: 0x2859:009
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
Error in the PROFIsafe communication
PROFIsafe was passivated.
|
Check PROFIsafe component.
Check network cable.
Analyze the error history of the higher-level controller.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The F-Parameter-CRC is faulty.
|
Check F-Parameter-CRC (CRC1) in the higher-level controller.
Check device description file (GSDML).
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Time-out during cyclic data reception, e.g. due to an interrupted communication link to the master or missing cyclic data.
|
–
Check wiring of the network.
–
Eliminate EMC interferences.
|
Trouble (configurable)
|
|
Setting parameters: 0x2859:001
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The communication partner has interrupted the cyclic data exchange.
|
–
Check wiring of the network.
–
The slave must receive new parameterisation and configuration files by the master, in order to be able to exchange data again.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The initialisation of the communication stack has been interrupted due to an incorrect address setting or communication configuration.
|
Check master/slave configuration and restart the devices.
|
Trouble (configurable)
|
|
Setting parameters: 0x2859:004
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The cyclic process data received are invalid.
|
Check cyclic process data sent by the master.
|
Trouble (configurable)
|
|
Setting parameters: 0x2859:005
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Unexpected FSoE command received.
|
Check FSoE configuration.
Restart communication.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Unknown FSoE command received.
|
Check FSoE configuration.
Restart communication.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
FSoE frame with invalid connection ID received.
|
Check FSoE configuration.
Restart communication.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The check of the CRC in the FSoE frames reports errors.
|
Check FSoE configuration.
Restart communication.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
FSoE watchdog elapsed.
|
Check set watchdog time in FSoE master and adapt if necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Invalid communication parameter data received.
|
Check setting of the communication parameters.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The length of the application parameters transmitted by the FSoE master differs from the expected length.
|
Check setting of the communication parameters.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Invalid application parameter data received.
|
Check setting of the communication parameters.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Due to an error, FSoE was passivated.
|
Check FSoE configuration.
Reset error.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
No valid messages have been received via the Modbus for a longer time than the time-out time set in 0x2326:001.
|
–
Check communication with the master.
–
Check wiring.
–
Check bus termination.
|
Fault > inverter disabled (configurable)
|
|
Setting parameters: 0x2859:012
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The request by the master is invalid, e. g. invalid CRC checksum, non-supported function code, or impermissible data access.
|
Check request by the master:
–
Value in the valid range?
–
Function code valid?
–
No impermissible write access? (e. g. with regard to read-only parameters)
|
Warning
The inverter (slave) responds to the master with an error code:
–
0x01 = invalid function code
–
0x02 = invalid data address
–
0x03 = invalid data value
–
0x04 = slave device failure
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The slave address transmitted by the FSoE master differs from the slave address set in the device.
|
Check slave address in the FSoE master.
Check parameter setting in the device.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The length of the communication parameter transmitted by the FSoE master differs from the expected length.
|
Check setting of the communication parameters.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
In a safety open request of a multicast input connection, the value for the "Requested Packet Interval" (RPI) is invalid.
|
Set identical RPI values for each of the multicast input connections in the configuration software of the originator.
|
Information
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
Mismatch in the network connection parameters T->O within one of the safety open requests of a multicast connection.
|
Check the configured connection parameters in the configuration software of the originator (safety master), e.g. RPI (Requested Packet Interval) and maximum number of consumers.
|
Information
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
"Max Consumer Number" is invalid, the maximum number of consumer connections has been exceeded.
|
Check the number of supported consumers. See documentation for the originator (safety master).
|
Information
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
The "Output Connection Point" (OCPUNID) of the received safety open request belongs to another originator.
|
Check whether the correct originator (safety master) is being used.
If a new originator (safety master) is to be used:
1.
Reset previous OCPUNID: In the parameterization dialog for safety parameters execute the "Reset CIP Safety Output Connection Ownership" command via the CIP Safety menu.
2.
The OCPUNID of the new originator is transferred with the next safety open request.
|
Information
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
Type 2a Safety open request received with mismatched SCID.
|
Copy the correct SCID from the parameterization dialog for safety parameters into the configuration software of the originator.
|
Information
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
The "Requested Packet Interval" (RPI) for the outputs in the safety open request is invalid.
|
–
Check whether the appropriate EDS file from the Application Knowledge Base (AKB) is used for this device.
–
If it is not possible to use an EDS file, use the relevant connection data from the corresponding EDS file instead.
|
Information
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
Error in the connection path (EPATH) of the received safety open request.
|
–
Check whether the appropriate EDS file from the Application Knowledge Base (AKB) is used for this device.
–
If it is not possible to use an EDS file, use the relevant connection data from the corresponding EDS file instead.
|
Information
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
Error in the connection management of the received safety open request.
|
Check the configured connection parameters in the configuration software of the originator (safety master).
|
Information
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
Mismatch in the device identification in the electronic key data of the received safety open request.
|
Check whether the appropriate EDS file from the Application Knowledge Base (AKB) is used for this device.
|
Information
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
Error in a received time coordination message.
|
Check the connection parameters configured for the output data in the configuration software of the originator (safety master), e.g. timeout multiplier and network delay.
|
Information
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
Error in a received output message, e.g. CRC error, data aging error, error in the complementary data.
|
Restart the device. If the error persists, contact the manufacturer.
|
Information
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
Error in a received time correction message.
|
Check the connection parameters configured for the output data in the configuration software of the originator (safety master), e.g. timeout multiplier and network delay.
|
Information
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
Error in a received timestamp message.
|
Check the connection parameters configured for the output data in the configuration software of the originator (safety master), e.g. timeout multiplier and network delay.
|
Information
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal communication error between safety option and basic device.
Termination of a CIP Safety connection by the originator (safety master).
|
Restart the device. If the error persists, contact the manufacturer.
|
Information
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
The safety protocol selected in 0x2128 is not supported by the safety option.
|
–
Check whether the selected safety protocol is supported by the safety option (display parameter 0x212C:003).
–
Use device/safety option with an activated safety protocol license.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
An event of the type "Error" has occurred at IO-Link port 1.
|
–
Check connected IO-Link device.
–
Check configuration of the IO-Link port.
|
No response (configurable)
|
|
Setting parameters: 0x24A1:047
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
An event of the type "Error" has occurred at IO-Link port 2.
|
–
Check connected IO-Link device.
–
Check configuration of the IO-Link port.
|
No response (configurable)
|
|
Setting parameters: 0x24A2:047
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
An event of the type "Error" has occurred at IO-Link port 3.
|
–
Check connected IO-Link device.
–
Check configuration of the IO-Link port.
|
No response (configurable)
|
|
Setting parameters: 0x24A3:047
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
An event of the type "Error" has occurred at IO-Link port 4.
|
–
Check connected IO-Link device.
–
Check configuration of the IO-Link port.
|
No response (configurable)
|
|
Setting parameters: 0x24A4:047
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
An event of the type “Warning" has occurred at IO-Link port 1.
|
–
Check connected IO-Link device.
–
Check configuration of the IO-Link port.
|
No response (configurable)
|
|
Setting parameters: 0x24A1:048
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
An event of the type “Warning" has occurred at IO-Link port 2.
|
–
Check connected IO-Link device.
–
Check configuration of the IO-Link port.
|
No response (configurable)
|
|
Setting parameters: 0x24A2:048
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
An event of the type “Warning" has occurred at IO-Link port 3.
|
–
Check connected IO-Link device.
–
Check configuration of the IO-Link port.
|
No response (configurable)
|
|
Setting parameters: 0x24A3:048
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
An event of the type “Warning" has occurred at IO-Link port 4.
|
–
Check connected IO-Link device.
–
Check configuration of the IO-Link port.
|
No response (configurable)
|
|
Setting parameters: 0x24A4:048
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
–
Invalid PDO assignment by the master.
–
Internal PDO assignment was changed and does not comply with the configuration available in the master.
|
Check data mapping in the master and slave.
|
Trouble (configurable)
|
|
Setting parameters: 0x2859:003
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Various data sources can be selected, such as the network, IO-Link, or the Logic PLC. However, receivable objects may be selected only once. When the assignment is activated, this is checked, and this error message appears if an object has been assigned more than once.
|
Correct duplicate assignments of receivable objects.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Motor has reached the torque limit:
|
–
Observe load requirements.
–
Reduce motor load.
–
Check set torque limits and sources for the torque limits.
|
No response (configurable)
|
|
Setting parameters: 0x2D67:001
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
The selected function is not permissible in the chosen operating mode.
|
–
Check settings of operation modes.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The monitoring of the software end positions is active and the positive software limit position has been overridden.
|
–
Check the setting of the software limit positions.
–
Check movement specifications.
|
Warning (configurable)
|
|
Setting parameters: 0x500A:105
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The monitoring of the software end positions is active and the negative software limit position has been overridden.
|
–
Check the setting of the software limit positions.
–
Check movement specifications.
|
Warning (configurable)
|
|
Setting parameters: 0x500A:105
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The positive hardware limit switch has been overridden.
|
Check movement specifications.
|
Warning (configurable)
|
|
Setting parameters: 0x500A:104
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The negative hardware limit switch has been overridden.
|
Check movement specifications.
|
Warning (configurable)
|
|
Setting parameters: 0x500A:104
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The warning threshold for the following error has been exceeded.
|
Check controller settings, encoder parameterization and mechanics.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The error threshold for the following error has been exceeded.
|
Check controller settings, encoder parameterization and mechanics.
|
Warning (configurable)
|
|
Setting parameters: 0x500A:059
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Invalid profile parameters.
|
Check profile parameters.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
An invalid positioning mode has been selected.
|
Check profile parameters for positioning mode.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Specification of an invalid acceleration (at standstill).
|
Check profile parameters for acceleration.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Specification of an invalid deceleration (at standstill).
|
Check profile parameters for deceleration.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Specification of an invalid speed (at standstill).
|
Check profile parameters for speed.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
For the axis, no home position is known.
|
Execute homing.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The profile parameter for speed, acceleration or jerk exceeds the respective maximum value.
|
–
Check profile parameters.
–
Adjust the maximum values for speed, acceleration and jerk.
|
Warning (configurable)
|
|
Setting parameters: 0x500A:106
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The target position is outside the software limit positions.
|
–
Check the setting of the software limit positions.
–
Check profile parameters.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
In the first driving cycle, the profile parameters result in a mathematically longer braking distance than the total distance. When braking during an overchange profile, the final speed to which deceleration is to take place is greater than the speed currently being generated.
|
Adapt profile parameters.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Signal error at safe input SD-In1.
|
Check parameter setting.
Check wiring.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Signal error at safe input SD-In2.
|
Check parameter setting.
Check wiring.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Initialization error or parameterization error.
HIGH level detected at the deactivated safe input.
|
Check parameter setting.
Check wiring.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Initialization error or parameterization error.
HIGH level detected at the deactivated safe input.
|
Check parameter setting.
Check wiring.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Channel A of SD_Out1 cannot be deactivated.
|
Check wiring for short circuit.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Channel A of SD_Out1 cannot be activated.
|
Check wiring.
Check supply voltage.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Channel B of SD_Out1 cannot be deactivated.
|
Check wiring for short circuit.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Channel B of SD_Out1 cannot be activated.
|
Check wiring.
Check supply voltage.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Channel A of SD_In1 cannot be deactivated.
|
Check wiring for short circuit.
Check configuration of the safe input.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Channel B of SD_In1 cannot be deactivated.
|
Check wiring for short circuit.
Check configuration of the safe input.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Channel A of SD_In2 cannot be deactivated.
|
Check wiring for short circuit.
Check configuration of the safe input.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Channel B of SD_In2 cannot be deactivated.
|
Check wiring for short circuit.
Check configuration of the safe input.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Short circuit at the CLA/CLB clock outputs.
|
Check wiring.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Brake failure due to a short circuit, cable break, or power fluctuations/outages.
|
–
Check the brake wiring for short circuits or cable breaks.
–
Check the connection cable used (low-capacitance shielding).
–
Check the power supply wiring.
–
Ensure a stable power supply.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
"Safe Torque Off (STO)" has been activated via Safety. The movement is interrupted although the controller is still enabled.
Note: The event ID 0xFF05 has a different meaning for the i550 cabinet and i550 protec inverters: The integrated safety technology is defective. (The device must be replaced.)
|
Enable "Safe Torque Off (STO)" again or disable controller.
In the event of false tripping, check the wiring at connection X1.
|
No response (configurable)
|
|
Setting parameters: 0x2024:003
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The motor speed has reached the error threshold for overspeed set in 0x2D44:001.
|
Adapt the maximum motor speed 0x6080 and the warning threshold or error threshold 0x2D44:001.
|
Fault > inverter disabled (configurable)
–
The event can only be reset after a blocking time.
|
|
Blocking time: 1 s
|
||
|
Setting parameters: 0x2D44:002
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
A failure of several motor phases has been detected.
|
–
Check wiring between inverter and motor.
–
In case of a false tripping, adapt the settings for the motor phase failure detection.
|
No response (configurable)
–
The event can only be reset after a blocking time.
|
|
Blocking time: 2 s
|
||
|
Setting parameters: 0x2D45:001
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
A failure of the motor phase U has been detected.
|
–
Check wiring between inverter and motor.
–
In case of a false tripping, adapt the settings for the motor phase failure detection.
|
No response (configurable)
–
The event can only be reset after a blocking time.
|
|
Blocking time: 2 s
|
||
|
Setting parameters: 0x2D45:001
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
A failure of the motor phase V has been detected.
|
–
Check wiring between inverter and motor.
–
In case of a false tripping, adapt the settings for the motor phase failure detection.
|
No response (configurable)
–
The event can only be reset after a blocking time.
|
|
Blocking time: 2 s
|
||
|
Setting parameters: 0x2D45:001
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
No response (configurable)
–
The event can only be reset after a blocking time.
|
||
|
Blocking time: 2 s
|
||
|
Setting parameters: 0x2D45:001
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
During the automatic identification of the motor, an error has occurred.
|
–
Set motor data so that they comply
with the data on the motor nameplate.
–
Check wiring of the motor.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
At mains connection, a start command was already available and the automatic start at power-up is set in 0x2838:002 to "Off [0]".
|
Deactivate starting command and reset error.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
In a running motor, the motor load (current) is monitored. When the motor load falls below the threshold value specified in Load loss detection: threshold (0x4006:001) for the period of time specified in Load loss detection: delay time (0x4006:002), load loss protection is triggered.
|
Check utilisation
|
No response (configurable)
|
|
Setting parameters: 0x4006:003
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
If the apparent motor current exceeds a defined threshold value 0x4007:002 for a certain amount of time 0x4007:001, heavy duty monitoring is triggered.
|
Check the motor load.
|
No response (configurable)
|
|
Setting parameters: 0x4007:003
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
–
The limitation of the maximum motor speed set in 0x6080 is active.
–
The maximum output frequency of the inverter has been reached.
–
Depending on the parameter setting of 0x2D44:001 (Overspeed monitoring: threshold), the speed limitation (0x6080 / Max. motor speed) may become active before speed monitoring.
|
Check application.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Indicates the deactivation of the manual speed control.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Indicates the activation of the manual speed control.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
If "manual operation" is active, an error is generated in case the communication links get lost.
|
The error can be only be reset if the connection is restored or the control mode is changed to a different value than "manual operation".
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The integrated safety technology is defective.
|
The inverter must be replaced.
Note!
The user is not allowed to change inverters that come with integrated safety technology.
–
The safety module must not be removed.
–
The user must not carry out any repairs on the safety module.
–
The safety module is not a spare part.
|
Fault
–
The inverter is disabled immediately. The motor has no torque (is coasting).
–
The event can only be reset by mains switching.
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
A modified safety-related software component (safety firmware or safety boot loader) has been detected.
|
Acknowledge the update of the software component using the parameterization dialog for safety parameters or the confirmation button S82.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Failed to update the internal controller. This controller can only be updated if the device has been switched off for at least 10 seconds.
|
Disconnect the device from all power sources for at least 10 seconds and then switch it on again.
|
Fault
–
The inverter is disabled immediately. The motor has no torque (is coasting).
–
The event can only be reset by mains switching.
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The firmware update of a component has failed due to an interruption or an error.
|
–
Check firmware package.
–
Repeat the device update process after switching off the power.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
MUT - Muting function active
|
For information only. No remedy necessary.
|
Information
–
The activated safety function STO is deactivated in the inverter.
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
MUT - Muting function completed
|
For information only. No remedy necessary.
|
Information
–
The activated safety functions are executed again in the inverter.
|
|
|
Motor overload monitoring (i²xt)