Manual setting of the motor data

Manually set the motor data in accordance with the manufacturer's information / motor data sheet in the following parameters, provided that a third party motor is connected to the inverter.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2910:001
Inertia settings: Motor moment of inertia
0.00 ... [0.00] ... 20000000.00 kg cm²
Setting of the moment of inertia of the motor, relating to the motor.
0x2C01:001
Motor parameters: Number of pole pairs
–
Read only
 
Display of the number of pole pairs calculated from the rated speed and rated frequency.
0x2C01:002
Motor parameters: Stator resistance
0.0000 ... [0.0000] ... 125.0000 Ω
General motor data.
Carry out settings as specified by manufacturer data/motor data sheet.
 
Note!
When you enter the motor nameplate data, take into account the phase connection implemented for the motor (star or delta connection). Only enter the data applying to the connection type selected.
0x2C01:003
Motor parameters: Stator leakage inductance
0.000 ... [0.000] ... 500.000 mH
0x2C01:004
Motor parameters: Rated speed
50 ... [1450] ... 50000 rpm
General motor data.
Carry out settings as specified by motor nameplate data.
 
Note!
When you enter the motor nameplate data, take into account the phase connection implemented for the motor (star or delta connection). Only enter the data applying to the connection type selected.
0x2C01:005
Motor parameters: Rated frequency
1.0 ... [50.0] ... 1000.0 Hz
0x2C01:006
Motor parameters: Rated power
0.00 ... [0.00] ... 655.35 kW
0x2C01:007
Motor parameters: Rated voltage
0 ... [0] ... 65535 V
0x2C01:008
Motor parameters: Cosine phi
0.00 ... [0.80] ... 1.00
0x2C02:003
Motor parameter (ASM): Magnetising current
0.00 ... [0.00] ... 500.00 A
Equivalent circuit data required for the motor model of the asynchronous machine.
0x2C03:001
Motor parameter (PSM): Back EMF constant
0.0 ... [41.8] ... 100000.0 V/1000rpm
Voltage induced by the motor (rotor voltage / 1000 rpm).
For permanently excited synchronous motors, the e.m.f. constant describes the r.m.s. value of the line-to-line voltage (phase voltage) induced in idle state by the motor (reference: 1000 rpm, 20 °C).
Measured: Line to Line (L - L)
0x6075
Rated motor current
0.001 ... [0.000] ... 500.000 A
–
Setting can only be changed if the inverter is disabled.
 
The rated motor current that needs to be set here serves as a reference value for different parameters that involve a setting for/display of a current value in percent.
Example:
–
Rated motor current = 1.7 A
 
–
Max. current 0x6073 = 200 %
Rated motor current = 3.4 A
 
0x6076
Rated motor torque
0.001 ... [0.000] ... 4294967.295 Nm
–
Setting can only be changed if the inverter is disabled.
 
The rated motor torque to be set here serves as a reference value for different parameters with a setting/display of a torque value in percent.
Example:
–
Rated motor torque = 1.65 Nm
 
–
Max. torque 0x6072 = 250 % Rated motor torque = 4.125 Nm
 
0x6080
Max. motor speed
0 ... [6075] ... 480000 rpm
Limitation of the max. motor speed. Depending on the parameter setting of 0x2D44:001 (Overspeed monitoring: threshold), the speed limitation (0x6080 / Max. motor speed) may become active before speed monitoring.