Control connections

The inverter's control connections are designed as configurable M12 connectors.
–
For Standard-I/O and Application-I/O, all control connections are configured as digital inputs by default.
 
–
In Extended-I/O mode, a different function assignment is preset for control connections X3.3 and X3.4:
 
–
X3.3: Analog input AI1 + Digital input DI5
 
–
X3.4: Analog output AO1
 
 
 
Standard-I/O
M12 connectors (A coded)
Pin
Assignment (delivery status)
X3.1
X3.2
X3.3
X3.4
1
24 V
not available
2
DI2
DI4
3
GND
4
DI1
DI3
5
Not assigned
Housing is connected to functional earth
Application-I/O
M12 connectors (A coded)
Pin
Assignment (delivery status)
X3.1
X3.2
X3.3
X3.4
1
24 V
2
DI2
DI4
DI6
DI8
3
GND
4
DI1
DI3
DI5
DI7
5
Not assigned
Housing is connected to functional earth
Extended-I/O
M12 connectors (A coded)
Pin
Assignment (delivery status)
X3.1
X3.2
X3.3
X3.4
1
24 V
AO1
2
DI2
DI4
AI1 -
24 V
3
GND
4
DI1
DI3
DI5
GND
5
Pin 5 and the housing are connected to the functional earth
 
Recommended procedure:
1.
First configure the basic functionality of the control connections (digital input, digital output, encoder inputs, etc.).
 
–
The »EASY Starter« supports you in this via corresponding dialogs.
 
 
2.
Then use the "Flexible I/O configuration" to adapt the control of the inverter to the drive task.
 
–
Digital input signals can be assigned to control functions of the inverter.
 
–
Status signals of the inverter can be assigned to digital output signals.
 
 
 
All functional setting options for the control ports are described in chapter "I/O extensions and control connections".