Mains voltage

The rated mains voltage set for the inverter has an impact on the operating range of the inverter.
 
Details
By default, the rated mains voltage in 0x2540:001 is set according to the product code of the inverter.
Check the setting of the rated mains voltage in 0x2540:001.
Ensure that it matches the mains voltage applied!
 
Region
Inverters
Product code
Rated mains voltage
Default setting
Possible settings
EU
i□□□ motec, 230 V, 3-phase
I□□AMxxxCxxxx0xxxx
230 Veff [0]
230 Veff [0]
US
i□□□ motec, 230 V, 3-phase
I□□AMxxxCxxxx1xxxx
230 Veff [0]
230 Veff [0]
EU
i□□□ motec, 400 V, 3-phase
I□□AMxxxFxxxx0xxxx
400 Veff [1]
400 Veff [1], 480 Veff [2]
US
i□□□ motec, 480 V, 3-phase
I□□AMxxxFxxxx1xxxx
480 Veff [2]
400 Veff [1], 480 Veff [2]
Notes regarding the table:
–
The inverter types 400/480 V can be used with different mains voltages. For establishing the internal limit values, the rated mains voltage can be set in 0x2540:001.
 
–
If the inverter is reset to the delivery state, the rated mains voltage is also reset to the default setting (see table).
 
The following results from the rated mains voltage set:
–
the error threshold for monitoring the DC-bus voltage and
 
–
the calculation basis for motor overload monitoring (i2xt).
 
 
Monitoring of the DC-bus voltage
–
The warning thresholds for monitoring are adjustable.
 
–
The error thresholds and reset thresholds for monitoring result from the rated mains voltage set:
 
Rated mains voltage
Undervoltage thresholds
Overvoltage thresholds
Warning threshold
Error threshold
Reset threshold
Warning threshold
Error threshold
Reset threshold
Setting in
Setting in
Display in
Display in
Setting in 0x2540:005
Display in
Display in
–
If the DC-bus voltage of the inverter falls below the undervoltage error threshold, the "Trouble" response is triggered.
 
–
Without external voltage supply DC 24 ... 48 V:
The motor behaves according to 0x2838:002.
 
–
With external voltage supply DC 24 ... 48 V:
The motor behaves according to the fault behavior in case of undervoltage.
 
 
–
If the DC-bus voltage of the inverter exceeds the error threshold for overvoltage, the "Error" response occurs.
 
The motor does not restart automatically after the overvoltage monitoring function has been triggered.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2540:001
Mains settings: Rated mains voltage
–
Setting can only be changed if the inverter is disabled.
 
Selection of the mains voltage for actuating the inverter.
0
230 Veff
1
400 Veff
2
480 Veff
0x2540:002
Mains settings: Undervoltage warning threshold
0 ... [0] ... 800 V
Monitoring for undervoltage (LU) in the DC bus: Setting of the warning threshold.
–
If the DC voltage in the DC bus falls below the threshold set, the inverter outputs a warning.
 
–
The warning is reset with a hysteresis of 10 V.
 
0x2540:003
Mains settings: Undervoltage error threshold
–
Read only: x V
 
Monitoring for undervoltage (LU) in the DC bus: Display of the fixed threshold.
–
If the DC voltage in the DC bus falls below the threshold displayed, the error"" response is triggered.
 
0x2540:004
Mains settings: Undervoltage reset threshold
–
Read only: x V
 
Display of the fixed reset threshold for monitoring DC bus undervoltage.
0x2540:005
Mains settings: Overvoltage warning threshold
0 ... [0] ... 800 V
Monitoring for overvoltage (OU) in the DC bus: Setting of the warning threshold.
–
If the DC bus voltage exceeds the threshold set, the inverter outputs a warning.
 
–
The warning is reset with a hysteresis of 10 V.
 
0x2540:006
Mains settings: Overvoltage error threshold
–
Read only: x V
 
Monitoring for overvoltage (OU) in the DC bus: Display of the fixed threshold.
–
If the DC-bus voltage exceeds the threshold displayed, the "Fault" response is triggered.
 
0x2540:007
Mains settings: Overvoltage reset threshold
–
Read only: x V
 
Display of the fixed reset threshold for monitoring DC bus overvoltage.