Function assignment of the digital inputs (default)

By default, the digital inputs are assigned the following control functions:
–
The inverter can be started via digital input 1.
 
–
A resettable error can be reset via digital input 2 (provided the error condition is no longer present).
 
–
No functions are assigned to all other digital inputs.
 
Parameter
Name
Default setting
Control functions
①
Run
Digital input 1 [11]
②
Reset fault
Digital input 2 [12]
Settings for the frequency setpoint
③
Frequency control: Default setpoint source
Frequency preset 1 [11]
Frequency setpoint presets: Preset 1
20 Hz
④
Acceleration time 1
5.00 s
⑤
Deceleration time 1
5.00 s
 
All functional possible settings for controlling the inverter are described in the "Start, stop and rotating direction commands" chapter.