Setpoint presets

15 different frequency setpoints (presets) can be parameterised for the frequency control. 8 process controller setpoints (presets) can also be parameterised for the optional PID control.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2911:001
Frequency setpoint presets: Preset 1
0.0 ... [20.0] ... 1000.0 Hz
Parameterisable frequency setpoints (presets) for operating mode "MS: Velocity mode".
0x2911:002
Frequency setpoint presets: Preset 2
0.0 ... [40.0] ... 1000.0 Hz
0x2911:003
Frequency setpoint presets: Preset 3
0.0 ... [50.0] ... 1000.0 Hz
0x2911:004
Frequency setpoint presets: Preset 4
0.0 ... [0.0] ... 1000.0 Hz
0x2911:005
Frequency setpoint presets: Preset 5
0.0 ... [0.0] ... 1000.0 Hz
0x2911:006
Frequency setpoint presets: Preset 6
0.0 ... [0.0] ... 1000.0 Hz
0x2911:007
Frequency setpoint presets: Preset 7
0.0 ... [0.0] ... 1000.0 Hz
0x2911:008
Frequency setpoint presets: Preset 8
0.0 ... [0.0] ... 1000.0 Hz
0x2911:009
Frequency setpoint presets: Preset 9
0.0 ... [0.0] ... 1000.0 Hz
0x2911:010
Frequency setpoint presets: Preset 10
0.0 ... [0.0] ... 1000.0 Hz
0x2911:011
Frequency setpoint presets: Preset 11
0.0 ... [0.0] ... 1000.0 Hz
0x2911:012
Frequency setpoint presets: Preset 12
0.0 ... [0.0] ... 1000.0 Hz
0x2911:013
Frequency setpoint presets: Preset 13
0.0 ... [0.0] ... 1000.0 Hz
0x2911:014
Frequency setpoint presets: Preset 14
0.0 ... [0.0] ... 1000.0 Hz
0x2911:015
Frequency setpoint presets: Preset 15
0.0 ... [0.0] ... 1000.0 Hz
0x4022:001
PID setpoint presets: Preset 1
-300.00 ... [0.00] ... 300.00 PID unit
Parameterisable process controller setpoints (presets) for PID control.
0x4022:002
PID setpoint presets: Preset 2
-300.00 ... [0.00] ... 300.00 PID unit
0x4022:003
PID setpoint presets: Preset 3
-300.00 ... [0.00] ... 300.00 PID unit
0x4022:004
PID setpoint presets: Preset 4
-300.00 ... [0.00] ... 300.00 PID unit
0x4022:005
PID setpoint presets: Preset 5
-300.00 ... [0.00] ... 300.00 PID unit
0x4022:006
PID setpoint presets: Preset 6
-300.00 ... [0.00] ... 300.00 PID unit
0x4022:007
PID setpoint presets: Preset 7
-300.00 ... [0.00] ... 300.00 PID unit
0x4022:008
PID setpoint presets: Preset 8
-300.00 ... [0.00] ... 300.00 PID unit
 
A switch-over to a preset during operation is also possible as an alternative to the standard setpoint source setting.