Changing the setpoint source during operation
The inverter receives its setpoint from the selected standard setpoint source. For applications requiring a change-over of the setpoint source during operation,
the functions listed below must be configured.
Details
If the network control is activated, the functions for the setpoint changeover are not active! If network control is in operation but no setpoint is defined via the network control word, the standard setpoint source is active.
|
Function
|
Information
|
|
Activate network setpoint
|
Activate network as setpoint source.
|
|
Activate preset (bit 0)
|
Activate parameterizable setpoints (presets) as setpoint source.
–
15 frequency setpoints and 8 PID setpoints can be set as presets.
–
A preset can be selected binary-coded via the four functions "Activate preset (bit 0)" ... "Activate preset (bit 3)".
|
|
Activate preset (bit 1)
|
|
|
Activate preset (bit 2)
|
|
|
Activate preset (bit 3)
|
Priority of the setpoint sources
Since only one setpoint source can be active at a time, the following priorities apply:
|
Flexible I/O configuration active
0x2631:037 = FALSE
|
Network control active
0x2631:037 = TRUE
|
|
Prio 1: Functions for setpoint changeover
The priority of the functions results from the assigned triggers (in the order of the selection list):
1.
Constant TRUE [1]
2.
Digital input 1 [11]
3.
Digital input 2 [12]
4.
Digital input 3 [13]
5.
...
|
Prio 1: Setpoint source selected via network control word
|
|
Prio 2: Standard setpoint source set in 0x2860:001
|
Prio 2: Standard setpoint source set in 0x2860:001
|
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x2631:014
|
Function list: Activate AI1 setpoint
–
Setting can only be changed if the inverter is disabled.
|
Assignment of a trigger for the "Activate AI1 setpoint" function.
Trigger = TRUE: analog input 1 is used as setpoint source (if the trigger assigned has the highest setpoint priority).
Trigger = FALSE: no action / deactivate function again.
|
|
|
0
|
Not connected
|
No trigger assigned (trigger is constantly FALSE).
|
|
|
1
|
Constant TRUE
|
Trigger is constantly TRUE.
|
|
|
11
|
Digital input 1
|
State of X3/DI1, taking an inversion set in 0x2632:001 into consideration.
|
|
|
12
|
Digital input 2
|
State of X3/DI2, taking an inversion set in 0x2632:002 into consideration.
|
|
|
13
|
Digital input 3
|
State of X3/DI3, taking an inversion set in 0x2632:003 into consideration.
|
|
|
14
|
Digital input 4
|
State of X3/DI4, taking an inversion set in 0x2632:004 into consideration.
|
|
|
15
|
Digital input 5
|
State of X3/DI5, taking an inversion set in 0x2632:005 into consideration.
|
|
|
16
|
Digital input 6
|
State of X3/DI6, taking an inversion set in 0x2632:006 into consideration.
|
|
|
17
|
Digital input 7
|
State of X3/DI7, taking an inversion set in 0x2632:007 into consideration.
|
|
|
18
|
Digital input 8
|
State of X3/DI8, taking an inversion set in 0x2632:008 into consideration.
|
|
|
50
|
Running
|
TRUE if inverter and start are enabled and output frequency > 0 Hz. Otherwise FALSE.
Exception, quick stop mode: TRUE if inverter and start are enabled and output frequency > 0.2 Hz. Otherwise FALSE.
|
|
|
51
|
Ready for operation
|
TRUE if inverter is ready for operation (no error active, no STO active and DC-bus voltage ok). Otherwise FALSE.
|
|
|
53
|
Stop active
|
TRUE if inverter is enabled and motor is not started and output frequency = 0.
|
|
|
54
|
Quick stop active
|
TRUE if quick stop is active. Otherwise FALSE.
|
|
|
58
|
Device warning active
|
TRUE if warning is active. Otherwise FALSE.
–
A warning has no impact on the operating status of the inverter.
–
A warning is reset automatically if the cause has been eliminated.
|
|
|
59
|
Device trouble active
|
TRUE if a fault is active. Otherwise FALSE.
–
In the event of a fault, the motor is brought to a standstill with the quick stop ramp. The inverter is then disabled.
–
Exception: In case of a serious fault, the inverter is disabled immediately. The motor has no torque (coasts).
–
The error state will be left automatically if the error condition is not active anymore.
–
The restart behaviour after trouble can be configured.
Automatic restart after a fault |
|
|
60
|
Heatsink temperature warning active
|
TRUE if current heatsink temperature > warning threshold for temperature monitoring. Otherwise FALSE.
–
Display of the current heatsink temperature in 0x2D84:001.
–
Setting of the warning threshold in 0x2D84:002.
|
|
|
68
|
Stop command active
|
TRUE if delay to standstill active. Otherwise FALSE.
|
|
|
69
|
Rotational direction reversed
|
TRUE if output frequency is negative. Otherwise FALSE.
|
|
|
70
|
Frequency threshold exceeded
|
TRUE if current output frequency > frequency threshold. Otherwise FALSE.
|
|
|
71
|
Actual speed = 0
|
TRUE if actual output frequency = 0 Hz (
± 0.3 Hz), irrespective of the operating mode. Otherwise FALSE. |
|
|
78
|
Current limit reached
|
TRUE if current motor current
≥ maximum current. Otherwise FALSE. |
|
|
79
|
Torque limit reached
|
TRUE if torque limit has been reached or exceeded. Otherwise FALSE.
–
Setting "Actual positive torque limit" in 0x2949:003.
–
Setting "Actual negative torque limit" in 0x2949:004.
|
|
|
81
|
Error of analog input 1 active
|
TRUE if the monitoring of the input signal at the analog input 1 has responded. Otherwise FALSE.
This trigger is set as a function of the following settings:
–
Monitoring threshold 0x2636:008
–
Monitoring condition 0x2636:009
The setting of the Error response in 0x2636:010 has no effect on this trigger.
|
|
|
82
|
Error of analog input 2 active
|
TRUE if the monitoring of the input signal at the analog input 2 has responded. Otherwise FALSE.
This trigger is set as a function of the following settings:
–
Monitoring threshold 0x2637:008
–
Monitoring condition 0x2637:009
The setting of the Error response in 0x2637:010 has no effect on this trigger.
|
|
|
83
|
Load loss detected
|
TRUE if actual motor current < threshold for load loss detection after delay time of the load loss detection has elapsed. Otherwise FALSE.
–
Display of the actual current in 0x6078.
–
Setting Threshold in 0x4006:001.
–
Setting Delay time in 0x4006:002.
|
|
|
84
|
Heavy load monitoring
|
TRUE if the actual apparent current of the motor exceeds the threshold for longer than the delay time.
FALSE if the actual apparent current of the motor falls below the threshold value minus 5 % (hysteresis).
|
|
|
120
|
Homing active
|
Status signals output by the "Table positioning" function.
–
These selection options are only available for the I65AMxxxxxxxxxP product variant.
|
|
|
121
|
Homing done
|
||
|
122
|
Manual jog active
|
||
|
123
|
Halt active
|
||
|
124
|
Motor control in limitation
|
||
|
125
|
Set position reached
|
||
|
126
|
Abort active
|
||
|
127
|
Standstill
|
||
|
128
|
Active profile (bit 1)
|
||
|
129
|
Active profile (bit 2)
|
||
|
130
|
Active profile (bit 3)
|
||
|
131
|
Active profile (bit 4)
|
||
|
132
|
Positioning profile active
|
||
|
133
|
Positioning profile done
|
||
|
134
|
Negative hardware limit switch active
|
||
|
135
|
Positive hardware limit switch active
|
||
|
136
|
Touch probe detected
|
||
|
137
|
External position active
|
||
|
169
|
Logic PLC Out bit 0
|
Binary values output by the integrated Logic PLC.
–
These selection options are only available for the I65AMxxxxxxxxxP product variant.
|
|
|
170
|
Logic PLC Out bit 1
|
||
|
171
|
Logic PLC Out bit 2
|
||
|
172
|
Logic PLC Out bit 3
|
||
|
173
|
Logic PLC Out bit 4
|
||
|
174
|
Logic PLC Out Bit 5
|
||
|
175
|
Logic PLC Out Bit 6
|
||
|
176
|
Logic PLC Out bit 7
|
||
|
177
|
Logic PLC Out bit 8
|
||
|
178
|
Logic PLC Out bit 9
|
||
|
179
|
Logic PLC Out bit 10
|
||
|
180
|
Logic PLC Out bit 11
|
||
|
181
|
Logic PLC Out bit 12
|
||
|
182
|
Logic PLC Out bit 13
|
||
|
183
|
Logic PLC Out bit 14
|
||
|
184
|
Logic PLC Out bit 15
|
||
|
224
|
IOL1 BI1 value
|
Binary values received via IO-Link corresponding to the binary input configuration for the respective IO-Link port.
–
The function assignment of the connectors must be configured accordingly.
–
The IO-Link ports are only available on the inverter with Application-I/O.
|
|
|
225
|
IOL1 BI2 value
|
||
|
226
|
IOL1 BI3 value
|
||
|
227
|
IOL1 BI4 value
|
||
|
228
|
IOL1 BI5 value
|
||
|
229
|
IOL1 BI6 value
|
||
|
230
|
IOL1 BI7 value
|
||
|
231
|
IOL1 BI8 value
|
||
|
232
|
IOL2 BI1 value
|
||
|
233
|
IOL2 BI2 value
|
||
|
234
|
IOL2 BI3 value
|
||
|
235
|
IOL2 BI4 value
|
||
|
236
|
IOL2 BI5 value
|
||
|
237
|
IOL2 BI6 value
|
||
|
238
|
IOL2 BI7 value
|
||
|
239
|
IOL2 BI8 value
|
||
|
240
|
IOL3 BI1 value
|
||
|
241
|
IOL3 BI2 value
|
||
|
242
|
IOL3 BI3 value
|
||
|
243
|
IOL3 BI4 value
|
||
|
244
|
IOL3 BI5 value
|
||
|
245
|
IOL3 BI6 value
|
||
|
246
|
IOL3 BI7 value
|
||
|
247
|
IOL3 BI8 value
|
||
|
248
|
IOL4 BI1 value
|
||
|
249
|
IOL4 BI2 value
|
||
|
250
|
IOL4 BI3 value
|
||
|
251
|
IOL4 BI4 value
|
||
|
252
|
IOL4 BI5 value
|
||
|
253
|
IOL4 BI6 value
|
||
|
254
|
IOL4 BI7 value
|
||
|
255
|
IOL4 BI8 value
|
||
|
0x2631:015
|
Function list: Activate AI2 setpoint
–
Setting can only be changed if the inverter is disabled.
–
For further possible settings, see parameter 0x2631:014.
|
Assignment of a trigger for the "Activate AI2 setpoint" function.
Trigger = TRUE: analog input 2 is used as setpoint source (if the trigger assigned has the highest setpoint priority).
Trigger = FALSE: no action / deactivate function again.
|
|
|
0
|
Not connected
|
No trigger assigned (trigger is constantly FALSE).
|
|
|
0x2631:017
|
Function list: Activate network setpoint
|
Assignment of a trigger for the "Activate network setpoint" function.
Trigger = TRUE: the network is used as setpoint source (if the trigger assigned has the highest setpoint priority).
Trigger = FALSE: no action / deactivate function again.
|
|
|
0
|
Not connected
|
No trigger assigned (trigger is constantly FALSE).
|
|
|
116
|
Network setpoint active
|
TRUE if a change-over to network setpoint is requested via bit 6 of the AC drive control word 0x400B:001. Otherwise FALSE.
Notes:
–
This setting is used if bit 6 of the AC drive control word is to be used independently of bit 5 AC drive control word.
–
The AC drive control word can be used with any communication protocol.
|
|
|
0x2631:018
|
Function list: Activate preset (bit 0)
|
Assignment of a trigger for the "Activate preset (bit 0)" function.
The bit with the valency 20 for bit-coded selection and the activation of a parameterised setpoint (preset).
Trigger = FALSE: bit = "0".
Trigger = TRUE: bit = "1".
|
|
|
14
|
Digital input 4
|
State of X3/DI4, taking an inversion set in 0x2632:004 into consideration.
|
|
|
0x2631:019
|
Function list: Activate preset (bit 1)
|
Assignment of a trigger for the "Activate preset (bit 1)" function.
The bit with the valency 21 for bit-coded selection and the activation of a parameterised setpoint (preset).
Trigger = FALSE: bit = "0".
Trigger = TRUE: bit = "1".
|
|
|
0
|
Not connected
|
No trigger assigned (trigger is constantly FALSE).
|
|
|
0x2631:020
|
Function list: Activate preset (bit 2)
|
Assignment of a trigger for the "Activate preset (bit 2)" function.
The bit with the valency 22 for bit-coded selection and the activation of a parameterised setpoint (preset).
Trigger = FALSE: bit = "0".
Trigger = TRUE: bit = "1".
|
|
|
0
|
Not connected
|
No trigger assigned (trigger is constantly FALSE).
|
|
|
0x2631:021
|
Function list: Activate preset (bit 3)
|
Assignment of a trigger for the "Activate preset (bit 3)" function.
Selection bit with the valency 23 for the bit-coded selection and activation of a parameterised setpoint (preset value).
Trigger = FALSE: selection bit = "0".
Trigger = TRUE: selection bit = "1".
|
|
|
0
|
Not connected
|
No trigger assigned (trigger is constantly FALSE).
|
|
|
0x2631:025
|
Function list: Activate MOP setpoint
|
Assignment of a trigger for the "Activate MOP setpoint" function.
Trigger = TRUE: the "Motor potentiometer" function is used as setpoint source (if the trigger assigned has the highest setpoint priority).
Trigger = FALSE: no action / deactivate function again.
|
|
|
0
|
Not connected
|
No trigger assigned (trigger is constantly FALSE).
|
|
Define setpoint via network