Changing the setpoint source during operation

The inverter receives its setpoint from the selected standard setpoint source. For applications requiring a change-over of the setpoint source during operation, the functions listed below must be configured.
 
Details
If the network control is activated, the functions for the setpoint changeover are not active! If network control is in operation but no setpoint is defined via the network control word, the standard setpoint source is active.
 
Function
Information
Activate network setpoint
Activate network as setpoint source.
Activate preset (bit 0)
Activate parameterizable setpoints (presets) as setpoint source.
–
15 frequency setpoints and 8 PID setpoints can be set as presets.
 
–
A preset can be selected binary-coded via the four functions "Activate preset (bit 0)" ... "Activate preset (bit 3)".
 
 
Activate preset (bit 1)
Activate preset (bit 2)
Activate preset (bit 3)
 
Diagnostic parameters:
–
0x282B:002: Active setpoint source
 
 
Priority of the setpoint sources
Since only one setpoint source can be active at a time, the following priorities apply:
Flexible I/O configuration active
0x2631:037 = FALSE
Network control active
0x2631:037 = TRUE
Prio 1: Functions for setpoint changeover
The priority of the functions results from the assigned triggers (in the order of the selection list):
1.
Constant TRUE [1]
 
2.
Digital input 1 [11]
 
3.
Digital input 2 [12]
 
4.
Digital input 3 [13]
 
5.
...
 
Prio 1: Setpoint source selected via network control word
Prio 2: Standard setpoint source set in 0x2860:001
Prio 2: Standard setpoint source set in 0x2860:001
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2631:014
Function list: Activate AI1 setpoint
–
Setting can only be changed if the inverter is disabled.
 
Assignment of a trigger for the "Activate AI1 setpoint" function.
Trigger = TRUE: analog input 1 is used as setpoint source (if the trigger assigned has the highest setpoint priority).
Trigger = FALSE: no action / deactivate function again.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
1
Constant TRUE
Trigger is constantly TRUE.
11
Digital input 1
State of X3/DI1, taking an inversion set in 0x2632:001 into consideration.
12
Digital input 2
State of X3/DI2, taking an inversion set in 0x2632:002 into consideration.
13
Digital input 3
State of X3/DI3, taking an inversion set in 0x2632:003 into consideration.
14
Digital input 4
State of X3/DI4, taking an inversion set in 0x2632:004 into consideration.
15
Digital input 5
State of X3/DI5, taking an inversion set in 0x2632:005 into consideration.
16
Digital input 6
State of X3/DI6, taking an inversion set in 0x2632:006 into consideration.
17
Digital input 7
State of X3/DI7, taking an inversion set in 0x2632:007 into consideration.
18
Digital input 8
State of X3/DI8, taking an inversion set in 0x2632:008 into consideration.
50
Running
TRUE if inverter and start are enabled and output frequency > 0 Hz. Otherwise FALSE.
Exception, quick stop mode: TRUE if inverter and start are enabled and output frequency > 0.2 Hz. Otherwise FALSE.
51
Ready for operation
TRUE if inverter is ready for operation (no error active, no STO active and DC-bus voltage ok). Otherwise FALSE.
53
Stop active
TRUE if inverter is enabled and motor is not started and output frequency = 0.
54
Quick stop active
TRUE if quick stop is active. Otherwise FALSE.
58
Device warning active
TRUE if warning is active. Otherwise FALSE.
–
A warning has no impact on the operating status of the inverter.
 
–
A warning is reset automatically if the cause has been eliminated.
 
59
Device trouble active
TRUE if a fault is active. Otherwise FALSE.
–
In the event of a fault, the motor is brought to a standstill with the quick stop ramp. The inverter is then disabled.
 
–
Exception: In case of a serious fault, the inverter is disabled immediately. The motor has no torque (coasts).
 
–
The error state will be left automatically if the error condition is not active anymore.
 
–
The restart behaviour after trouble can be configured. Automatic restart after a fault 
 
60
Heatsink temperature warning active
TRUE if current heatsink temperature > warning threshold for temperature monitoring. Otherwise FALSE.
–
Display of the current heatsink temperature in 0x2D84:001.
 
–
Setting of the warning threshold in 0x2D84:002.
 
68
Stop command active
TRUE if delay to standstill active. Otherwise FALSE.
69
Rotational direction reversed
TRUE if output frequency is negative. Otherwise FALSE.
70
Frequency threshold exceeded
TRUE if current output frequency > frequency threshold. Otherwise FALSE.
–
Display of the current output frequency in 0x2DDD.
 
–
Setting Frequency threshold in 0x4005.
 
71
Actual speed = 0
TRUE if actual output frequency = 0 Hz (
±
0.3 Hz), irrespective of the operating mode. Otherwise FALSE.
–
Display of the current output frequency in 0x2DDD.
 
78
Current limit reached
TRUE if current motor current
≥
maximum current. Otherwise FALSE.
–
Display of the present motor current in 0x2D88.
 
–
Setting for the maximum current in 0x6073.
 
79
Torque limit reached
TRUE if torque limit has been reached or exceeded. Otherwise FALSE.
–
Setting "Actual positive torque limit" in 0x2949:003.
 
–
Setting "Actual negative torque limit" in 0x2949:004.
 
81
Error of analog input 1 active
TRUE if the monitoring of the input signal at the analog input 1 has responded. Otherwise FALSE.
This trigger is set as a function of the following settings:
–
Monitoring threshold 0x2636:008
 
–
Monitoring condition 0x2636:009
 
The setting of the Error response in 0x2636:010 has no effect on this trigger.
82
Error of analog input 2 active
TRUE if the monitoring of the input signal at the analog input 2 has responded. Otherwise FALSE.
This trigger is set as a function of the following settings:
–
Monitoring threshold 0x2637:008
 
–
Monitoring condition 0x2637:009
 
The setting of the Error response in 0x2637:010 has no effect on this trigger.
83
Load loss detected
TRUE if actual motor current < threshold for load loss detection after delay time of the load loss detection has elapsed. Otherwise FALSE.
–
Display of the actual current in 0x6078.
 
–
Setting Threshold in 0x4006:001.
 
–
Setting Delay time in 0x4006:002.
 
84
Heavy load monitoring
TRUE if the actual apparent current of the motor exceeds the threshold for longer than the delay time.
FALSE if the actual apparent current of the motor falls below the threshold value minus 5 % (hysteresis).
120
Homing active
Status signals output by the "Table positioning" function.
–
These selection options are only available for the I65AMxxxxxxxxxP product variant.
 
121
Homing done
122
Manual jog active
123
Halt active
124
Motor control in limitation
125
Set position reached
126
Abort active
127
Standstill
128
Active profile (bit 1)
129
Active profile (bit 2)
130
Active profile (bit 3)
131
Active profile (bit 4)
132
Positioning profile active
133
Positioning profile done
134
Negative hardware limit switch active
135
Positive hardware limit switch active
136
Touch probe detected
137
External position active
169
Logic PLC Out bit 0
Binary values output by the integrated Logic PLC.
–
These selection options are only available for the I65AMxxxxxxxxxP product variant.
 
170
Logic PLC Out bit 1
171
Logic PLC Out bit 2
172
Logic PLC Out bit 3
173
Logic PLC Out bit 4
174
Logic PLC Out Bit 5
175
Logic PLC Out Bit 6
176
Logic PLC Out bit 7
177
Logic PLC Out bit 8
178
Logic PLC Out bit 9
179
Logic PLC Out bit 10
180
Logic PLC Out bit 11
181
Logic PLC Out bit 12
182
Logic PLC Out bit 13
183
Logic PLC Out bit 14
184
Logic PLC Out bit 15
224
IOL1 BI1 value
Binary values received via IO-Link corresponding to the binary input configuration for the respective IO-Link port.
–
The function assignment of the connectors must be configured accordingly.
 
–
The IO-Link ports are only available on the inverter with Application-I/O.
 
225
IOL1 BI2 value
226
IOL1 BI3 value
227
IOL1 BI4 value
228
IOL1 BI5 value
229
IOL1 BI6 value
230
IOL1 BI7 value
231
IOL1 BI8 value
232
IOL2 BI1 value
233
IOL2 BI2 value
234
IOL2 BI3 value
235
IOL2 BI4 value
236
IOL2 BI5 value
237
IOL2 BI6 value
238
IOL2 BI7 value
239
IOL2 BI8 value
240
IOL3 BI1 value
241
IOL3 BI2 value
242
IOL3 BI3 value
243
IOL3 BI4 value
244
IOL3 BI5 value
245
IOL3 BI6 value
246
IOL3 BI7 value
247
IOL3 BI8 value
248
IOL4 BI1 value
249
IOL4 BI2 value
250
IOL4 BI3 value
251
IOL4 BI4 value
252
IOL4 BI5 value
253
IOL4 BI6 value
254
IOL4 BI7 value
255
IOL4 BI8 value
0x2631:015
Function list: Activate AI2 setpoint
–
Setting can only be changed if the inverter is disabled.
 
–
For further possible settings, see parameter 0x2631:014.
 
Assignment of a trigger for the "Activate AI2 setpoint" function.
Trigger = TRUE: analog input 2 is used as setpoint source (if the trigger assigned has the highest setpoint priority).
Trigger = FALSE: no action / deactivate function again.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2631:017
Function list: Activate network setpoint
–
Further possible settings: Trigger list 
 
Assignment of a trigger for the "Activate network setpoint" function.
Trigger = TRUE: the network is used as setpoint source (if the trigger assigned has the highest setpoint priority).
Trigger = FALSE: no action / deactivate function again.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
116
Network setpoint active
TRUE if a change-over to network setpoint is requested via bit 6 of the AC drive control word 0x400B:001. Otherwise FALSE.
Notes:
–
This setting is used if bit 6 of the AC drive control word is to be used independently of bit 5 AC drive control word.
 
–
The AC drive control word can be used with any communication protocol.
 
0x2631:018
Function list: Activate preset (bit 0)
–
Further possible settings: Trigger list 
 
Assignment of a trigger for the "Activate preset (bit 0)" function.
The bit with the valency 20 for bit-coded selection and the activation of a parameterised setpoint (preset).
Trigger = FALSE: bit = "0".
Trigger = TRUE: bit = "1".
14
Digital input 4
State of X3/DI4, taking an inversion set in 0x2632:004 into consideration.
0x2631:019
Function list: Activate preset (bit 1)
–
Further possible settings: Trigger list 
 
Assignment of a trigger for the "Activate preset (bit 1)" function.
The bit with the valency 21 for bit-coded selection and the activation of a parameterised setpoint (preset).
Trigger = FALSE: bit = "0".
Trigger = TRUE: bit = "1".
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2631:020
Function list: Activate preset (bit 2)
–
Further possible settings: Trigger list 
 
Assignment of a trigger for the "Activate preset (bit 2)" function.
The bit with the valency 22 for bit-coded selection and the activation of a parameterised setpoint (preset).
Trigger = FALSE: bit = "0".
Trigger = TRUE: bit = "1".
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2631:021
Function list: Activate preset (bit 3)
–
Further possible settings: Trigger list 
 
Assignment of a trigger for the "Activate preset (bit 3)" function.
Selection bit with the valency 23 for the bit-coded selection and activation of a parameterised setpoint (preset value).
Trigger = FALSE: selection bit = "0".
Trigger = TRUE: selection bit = "1".
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2631:025
Function list: Activate MOP setpoint
–
Further possible settings: Trigger list 
 
Assignment of a trigger for the "Activate MOP setpoint" function.
Trigger = TRUE: the "Motor potentiometer" function is used as setpoint source (if the trigger assigned has the highest setpoint priority).
Trigger = FALSE: no action / deactivate function again.
0
Not connected
No trigger assigned (trigger is constantly FALSE).