Diagnostic parameters

The inverter provides many diagnostic parameters which are helpful for operation, maintenance, error diagnosis, error correction, etc.
 
–
The following overview lists the most common diagnostic parameters.
 
–
Further parameters for more specific diagnostic purposes are described in the following subchapters.
 
–
The diagnostic parameters can only be read and cannot be written to.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2012:015
Device information: Supported functions
–
Read only
 
0x2030
CRC parameter set
–
Read only
 
Display of the 32-bit hash sum for the integrity check of the parameter set.
0x2B0B
Ramp generator frequency
–
Read only: x.x Hz
 
Display of the current frequency setpoint. The frequency setpoint is internally transferred to the motor control (based on scaling and ramp generator).
The frequency setpoint is internally transferred to the motor control (based on scaling and ramp generator).
0x2B0E
Frequency setpoint
–
Read only: x.x Hz
 
Display of the frequency setpoint currently assigned.
–
Depending on the present operating conditions, this value may differ from the current output frequency 0x2DDD.
 
0x2B0F
Output frequency motor
–
Read only: x.x Hz
 
The inverter controls the motor so that the motor output frequency 0x2B0F corresponds to the frequency setpoint 0x2B0E. (Motor output frequency = output frequency of inverter - motor slip)
0x2D4F
Motor utilisation (i²xt)
–
Read only: x %
 
Display of the current thermal motor utilisation.
0x2D87
DC-bus voltage
–
Read only: x V
 
Display of the current DC-bus voltage.
0x2D88
Motor current
–
Read only: x.x A
 
Display des present current-r.m.s. value.
0x2D89
Motor voltage
–
Read only: x VAC
 
Display of the current motor voltage.
0x2DA2:001
Output power: Effective power
–
Read only: x.xxx kW
 
Display of the active output power for an energy analysis in the respective application.
0x2DA2:002
Output power: Apparent power
–
Read only: x.xxx kVA
 
Display of the apparent output power for an energy analysis in the respective application.
0x2DA3:001
Output energy: Motor
–
Read only: x.xx kWh
 
Display of the output power in motor mode for an energy analysis in the respective application.
0x2DA3:002
Output energy: Generator
–
Read only: x.xx kWh
 
Display of the output power in generator mode for an energy analysis in the respective application.
0x2DD1:001
Motor currents: Actual D-current (id)
–
Read only: x.xx A
 
Display of the actual D current.
0x2DD1:002
Motor currents: Actual Q-current (iq)
–
Read only: x.xx A
 
Display of the actual Q current.
0x2DD1:003
Motor currents: Setpoint D-current (id)
–
Read only: x.xx A
 
Display of the setpoint D current.
0x2DD1:004
Motor currents: Setpoint Q-current (iq)
–
Read only: x.xx A
 
Display of the setpoint Q current.
0x2DD1:005
Motor currents: Motor current (Ieff)
–
Read only: x.xx A
 
Display of the effective motor current.
0x2DD3:001
Speed setpoints: Speed setpoint
–
Read only: x rpm
 
Display of the speed setpoint value 1.
0x2DD3:003
Speed setpoints: Speed setpoint limited
–
Read only: x rpm
 
Display of the limited speed setpoint.
0x2DD4:001
Speed controller output signals: Output signal 1
–
Read only: x.x %
 
Display of the output signal 1 from the speed controller.
0x2DD4:002
Speed controller output signals: Output signal 2
–
Read only: x.x %
 
Display of the output signal 2 from the speed controller.
0x2DDC
Actual slip value
–
Read only: x.x Hz
 
Display of the actual slip.
0x2DDD
Output frequency
–
Read only: x.x Hz
 
Display of the current output frequency of the inverter.
0x2DDF:001
Axis information: Rated current
–
Read only: x.xx A
 
Display of the rated current of the axis.
0x2DDF:002
Axis information: Maximum current
–
Read only: x.xx A
 
Display of the maximum current of the axis.
0x6077
Actual torque
–
Read only: x.x %
 
Display of the actual torque.
–
100 % = Rated motor torque 0x6076
 
0x6078
Actual current
–
Read only: x.x %
 
Display of the motor actual current.
–
100 % =  Rated motor current 0x6075
 
0x6079
DC-bus voltage
–
Read only: x.xxx V
 
Display of the current DC-bus voltage.