Status LEDs

You can quickly obtain information on some operating states via the large "DRIVE" LED status display on the inverter. This status display is composed of a blue LED "RDY" and a red LED "ERR", which emit specific blinking patterns depending on the operating status:
 
"RDY" LED (blue)
"ERR" LED (red)
Status/meaning
off
off
No supply voltage
on
on
Initialisation (inverter is started)
blinking (1 Hz)
off
Safe torque off (STO) active. The inverter has been disabled by the integrated functional safety.
blinking fast (4 Hz)
Safe torque off (STO) active, warning present. The inverter has been disabled by the integrated functional safety.
blinking (2 Hz)
off
Inverter disabled
blinking fast (4 Hz)
Inverter disabled, warning present.
on
Inverter disabled, error active.
on briefly every 1.5 s
Inverter disabled, no DC-bus voltage.
on
off
Inverter enabled. The motor rotates according to the specified setpoint or quick stop active.
blinking fast (4 Hz)
Inverter enabled, warning present. The motor rotates according to the specified setpoint or quick stop active.
blinking (1 Hz)
Inverter enabled, quick stop as response to fault active.
Both LEDs are blinking in a rapidly alternating mode
Firmware update is active
Both LEDs are blinking in a very rapidly synchronous mode
"Visual tracking" function is active