Status LEDs
You can quickly obtain information on some operating states via the large "DRIVE" LED status display on the inverter. This status display is composed of a blue LED "RDY" and a red LED "ERR", which emit specific blinking patterns depending on the operating status:
|
"RDY" LED (blue)
|
"ERR" LED (red)
|
Status/meaning
|
|
off
|
off
|
No supply voltage
|
|
on
|
on
|
Initialisation (inverter is started)
|
|
blinking (1 Hz)
|
off
|
Safe torque off (STO) active. The inverter has been disabled by the integrated functional safety.
|
|
blinking fast (4 Hz)
|
Safe torque off (STO) active, warning present. The inverter has been disabled by the integrated functional safety.
|
|
|
blinking (2 Hz)
|
off
|
Inverter disabled
|
|
blinking fast (4 Hz)
|
Inverter disabled, warning present.
|
|
|
on
|
Inverter disabled, error active.
|
|
|
on briefly every 1.5 s
|
Inverter disabled, no DC-bus voltage.
|
|
|
on
|
off
|
Inverter enabled. The motor rotates according to the specified setpoint or quick stop active.
|
|
blinking fast (4 Hz)
|
Inverter enabled, warning present. The motor rotates according to the specified setpoint or quick stop active.
|
|
|
blinking (1 Hz)
|
Inverter enabled, quick stop as response to fault active.
|
|
|
Both LEDs are blinking in a rapidly alternating mode
|
Firmware update is active
|
|
|
Both LEDs are blinking in a very rapidly synchronous mode
|
"Visual tracking" function is active
|
|
Safe torque off (STO)