Error history buffer
For diagnostic purposes, the error history memory contains the last 32 error and warning messages of the inverter that occurred during operation. The error history memory represents a limited view of the logbook.
Details
–
For each event that is recorded, the error history buffer contains the message text, the error code, the time of occurrence as well as a counter for successive, identical events. If an event that has already been recorded occurs repeatedly, only the counter is incremented.
–
The error history buffer can be reset by the user. In order to prevent the buffer from being reset by the user, this function can be protected by means of a password.
–
Observe that the error history buffer only presents a snapshot at the time the data are read out. If a new event occurs, the error history buffer must be read out again via the parameters listed below so that the new event becomes visible.
Parameter
Structure of the messages
The following example shows the detailed structure of one of the following messages (parameter 0x2006:006 ... 0x2006:037):
|
Message:
|
|
|||||
|
|
|
|
|
|
|
|
|
Meaning:
|
Diag code
|
Message type
|
Text ID
|
Time stamp in [ns]
|
Flag param. 1
|
Parameter 1
|
|
Data type:
|
U32
|
U16
|
U16
|
U64
|
U16
|
U8
|
|
Hex value:
|
0x4310 E000
|
0x0112
|
0x0099
|
0x0001 FC73 040B 5200
|
0x0005
|
0x01
|
Notes:
–
The upper 16 bits of the "Diag Code" contain the error code (in the example "0x4310").
–
Bit 0 ... 3 of the message type contain the error type (0: Info, 1: Warning, 2: Trouble, 3: Fault).
–
Convert time stamp: 0x0001 FC73 040B 5200 = 559045896000000 ns = 6 days, 11 hours, 17 minutes, 25 seconds
–
The flag for parameter 1 has no meaning for decoding the message.
–
The parameter 1 contains the counter for successive, identical events.