Inverter diagnostics

The following parameters supply some information about the current operating status of the inverter.
 
Some of the following parameters contain bit-coded status words. Each single bit has a certain meaning.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2539:001
Hardware-Diagnose: External supply voltage
–
Read only: x.x V
 
0x2542:001
Power recovery management: Status
–
Read only
 
0
Disabled
1
Enabled
2
Active
3
Fault
0x282A:001
Status words: Cause of disable
–
Read only
 
Bit-coded display of the cause(s) for disabled inverter.
Bit 0
Flexible I/O configuration
1 = the inverter was disabled by the trigger set in 0x2631:001.
Bit 1
Network
1 = the inverter was disabled via network.
Bit 2
Axis command
1 = The inverter was disabled by the engineering tool via an axis command.
Bit 6
Fault DC-bus
1 = The inverter was disabled due to a DC-bus error.
Bit 7
Drive not ready
1 = the inverter was disabled internally since the drive was not ready for operation.
Possible causes:
–
Under/overvoltage in the DC bus
 
–
Defective device hardware
 
Bit 8
Quick stop active
1 = the inverter was disabled by the "Quick stop" function.
Bit 9
Motor data identification
1 = the inverter was disabled by the "Automatic identification of the motor data" function.
Bit 10
Holding brake
1 = the inverter was disabled by the "Holding brake control" function.
Bit 11
DC braking
1 = DC braking active.
Bit 12
CiA402 Inverter disabled
1 = the inverter was disabled by the internal state machine.
The bit is only set if
–
Operating mode 0x6060 = "CiA: Velocity mode (vl) [2]" and
 
–
state machine in the "Switch on disabled" state and
 
–
the state change has not been carried out via the "Disable operation" command.
 
Bit 13
CiA402 Quick stop option code 2
1 = the inverter was disabled by the "Quick stop" function.
Bit 14
Safety
1 = the inverter has been disabled by the integrated safety system.
Bit 15
CiA402 operation mode 0
1 = the inverter has been disabled because the selection "No selection [0]" is set in 0x6060.
0x282A:002
Status words: Cause of quick stop
–
Read only
 
Bit coded display of the cause(s) of quick stop.
Bit 0
Flexible I/O configuration
1 = quick stop was activated by the trigger set in 0x2631:003.
Bit 1
Network
1 = quick stop was activated via network.
Bit 2
Axis command
1 = Quick stop was activated by the engineering tool via an axis command.
Bit 3
SS1 quick stop
1 = Quick stop was activated by the "safe stop 1 (SS1)" safety function.
Bit 6
Error response
1 = quick stop has been activated as a response to an error.
0x282A:003
Status words: Cause of stop
–
Read only
 
Bit coded display of the cause(s) of stop.
Bit 0
Flexible I/O: Start disabled
1 = stop was activated by the trigger set in 0x2631:002.
Bit 1
Flexible I/O: Run forward
1 = stop has been activated due to cancellation of the command "Run forward (CW)".
Bit 2
Flexible I/O: Run reverse
1 = stop has been activated due to cancellation of the command "Run reverse (CCW)".
Bit 3
Flexible I/O: Jog forward
1 = stop has been activated due to cancellation of the command "Jog forward (CW)".
Bit 4
Flexible I/O: Jog reverse
1 = stop has been activated due to cancellation of the command "Jog reverse (CCW)".
Bit 5
Network
1 = stop was activated via network.
Bit 7
Control mode transition
1 = stop has been activated due to a change of the operating mode.
Bit 9
Manual mode
1 = Stop was activated by the "Manual mode" function.
Bit 15
Waiting for start
1 = stop is active as a start command is not yet available (e. g. after enabling the inverter).
0x282A:004
Status words: Extended status word
–
Read only
 
Bit-coded status word.
Bit 8
Reverse rotational direction
1 = reversal active.
Bit 10
Inverter disabled (safety)
1 = The safety system integrated in the inverter has disabled the inverter/drive.
Bit 11
STO active
1 = "Safe Torque Off (STO)" safety function is active. Safe inputs SIA and SIB = LOW (simultaneously).
0x282A:005
Status words: Device status
–
Read only
 
Display of the current inverter device state.
0
Initialisation
2
Not ready to switch on
3
Switch on disabled
4
Ready to switch on
5
Switched on
6
Operation enabled
7
Disable operation
8
Shut down
9
Quick stop active
10
Fault reaction active
11
Fault
0x282B:001
Inverter diagnostics: Active control source
–
Read only
 
Display of the control source that is currently active.
0
Flexible I/O configuration
1
Network
3
Internal
9
Manual mode
0x282B:002
Inverter diagnostics: Active setpoint source
–
Read only
 
Display of the setpoint source that is currently active.
0
Not selected
1
Analog input 1
2
Analog input 2
5
Network Setpoint
9
Manual mode: setpoint
11
Setpoint preset 1
12
Setpoint preset 2
13
Setpoint preset 3
14
Setpoint preset 4
15
Setpoint preset 5
16
Setpoint preset 6
17
Setpoint preset 7
18
Setpoint preset 8
19
Setpoint preset 9
20
Setpoint preset 10
21
Setpoint preset 11
22
Setpoint preset 12
23
Setpoint preset 13
24
Setpoint preset 14
25
Setpoint preset 15
50
Motor potentiometer
190
Logic PLC output value 1
Output values of the integrated Logic PLC.
–
These selection options are only available for the I65AMxxxxxxxxxP product variant.
 
191
Logic PLC output value 2
210
IOL1 AI1 scaled value
Value is specified as process data object via IO-Link.
–
The function assignment of the connectors must be configured accordingly.
 
–
The IO-Link ports are only available on the inverter with Application-I/O.
 
211
IOL1 AI2 scaled value
212
IOL2 AI1 scaled value
213
IOL2 AI2 scaled value
214
IOL3 AI1 scaled value
215
IOL3 AI2 scaled value
216
IOL4 AI1 scaled value
217
IOL4 AI2 scaled value
230
Scaling1 value
Output values of the "Analog signal scaling" function. This function is used to scale internal analog signals (analog parameter values) for use within the inverter.
231
Scaling2 value
0x282B:004
Inverter diagnostics: Active drive mode
–
Read only
 
Display of the active drive mode.
0
Velocity mode
"Velocity mode" active.
1
PID control
PID control active.
2
Torque mode
"Torque mode" active.
3
Test mode (internal)
Test mode active.
4
Jog operation
"Jog forward (CW)" or "Jog reverse (CCW)" function active.
5
Table positioning
"Table Positioning" function is enabled.
0x2831
Inverter status word
–
Read only
 
Bit coded status word of the internal motor control.
Bit 1
Speed setpoint 1 limited
1 = input of speed controller 1 in limitation.
Bit 2
Speed controller in limitation
1 = output of speed controller 1 in limitation.
Bit 3
Torque setpoint limited
1 = setpoint torque in limitation.
Bit 4
Q-current setpoint limited
1 = setpoint current in limitation.
Bit 5
Speed setpoint 2 limited
1 = input of speed controller
2 in "torque mode" in limitation.
Bit 6
Upper speed limit active
1 = in "torque mode", the speed is limited to upper
speed limit 0x2946:001
.
Bit 7
Lower speed limit active
1 = in "torque mode", the speed is limited to lower
speed limit 0x2946:002
.
Bit 8
Flying restart active
-
Bit 9
Flying restart completed
Bit 10
Output frequency limited
1 = setpoint frequency with V/f operation in limitation.
Bit 11
Magnetization completed
1 = Magnetisation completed during V/f operation.
Otherwise 0.
Bit 12
Motor phase error
1 = motor phase failure detection active.
0x2833
Inverter status word 2
–
Read only
 
Bit-coded status word 2 of the inverter.
Bit 1
Manual test mode active
1 = manual test mode active.
Bit 2
Manual control active
1 = manual control active.
Bit 6
DC braking active
1 = DC braking
active.
0x293A
Actual switching frequency
–
Read only
 
Display of the currently active switching frequency of the inverter.
Example:
–
In 0x2939, "16 kHz variable / min. Pv [13]" is set as switching frequency.
 
–
The increase in ambient temperature and/or load has resulted in a reduction in the switching frequency to 8 kHz. In this case, this parameter displays the selection "8 kHz drive-optimized [3]".
 
1
2 kHz drive-optimized
2
4 kHz drive-optimized
3
8 kHz drive-optimized
4
16 kHz drive-optimized
5
2 kHz power loss-optimized
6
4 kHz power loss-optimized
7
8 kHz power loss-optimized
8
16 kHz power loss-optimized
9
12 kHz drive-optimised
10
12 kHz power loss-optimised
0x603F
Error code
–
Read only
 
Error message
0x6061
CiA: Active operation mode
–
Read only
 
CiA: Active operation mode
-11
Identification
-10
Test mode
-3
MS: Position mode
-2
MS: Velocity mode
Vendor specific velocity mode
-1
MS: Torque mode
Manufacturer-specific torque mode
0
No selection
No selection
2
CiA: Velocity mode (vl)
CiA: Velocity mode