Inverter diagnostics
The following parameters supply some information about the current operating status of the inverter.
Some of the following parameters contain bit-coded status words. Each single bit has a certain meaning.
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x2539:001
|
Hardware-Diagnose: External supply voltage
–
Read only: x.x V
|
||
|
0x2542:001
|
Power recovery management: Status
–
Read only
|
||
|
0
|
Disabled
|
||
|
1
|
Enabled
|
||
|
2
|
Active
|
||
|
3
|
Fault
|
||
|
0x282A:001
|
Status words: Cause of disable
–
Read only
|
Bit-coded display of the cause(s) for disabled inverter.
|
|
|
Bit 0
|
Flexible I/O configuration
|
1 = the inverter was disabled by the trigger set in 0x2631:001.
|
|
|
Bit 1
|
Network
|
1 = the inverter was disabled via network.
|
|
|
Bit 2
|
Axis command
|
1 = The inverter was disabled by the engineering tool via an axis command.
|
|
|
Bit 6
|
Fault DC-bus
|
1 = The inverter was disabled due to a DC-bus error.
|
|
|
Bit 7
|
Drive not ready
|
1 = the inverter was disabled internally since the drive was not ready for operation.
Possible causes:
–
Under/overvoltage in the DC bus
–
Defective device hardware
|
|
|
Bit 8
|
Quick stop active
|
1 = the inverter was disabled by the "Quick stop" function.
|
|
|
Bit 9
|
Motor data identification
|
1 = the inverter was disabled by the "Automatic identification of the motor data" function.
|
|
|
Bit 10
|
Holding brake
|
1 = the inverter was disabled by the "Holding brake control" function.
|
|
|
Bit 11
|
DC braking
|
1 = DC braking active.
|
|
|
Bit 12
|
CiA402 Inverter disabled
|
1 = the inverter was disabled by the internal state machine.
The bit is only set if
–
Operating mode 0x6060 = "CiA: Velocity mode (vl) [2]" and
–
state machine in the "Switch on disabled" state and
–
the state change has not been carried out via the "Disable operation" command.
|
|
|
Bit 13
|
CiA402 Quick stop option code 2
|
1 = the inverter was disabled by the "Quick stop" function.
|
|
|
Bit 14
|
Safety
|
1 = the inverter has been disabled by the integrated safety system.
|
|
|
Bit 15
|
CiA402 operation mode 0
|
1 = the inverter has been disabled because the selection "No selection [0]" is set in 0x6060.
|
|
|
0x282A:002
|
Status words: Cause of quick stop
–
Read only
|
Bit coded display of the cause(s) of quick stop.
|
|
|
Bit 0
|
Flexible I/O configuration
|
1 = quick stop was activated by the trigger set in 0x2631:003.
|
|
|
Bit 1
|
Network
|
1 = quick stop was activated via network.
|
|
|
Bit 2
|
Axis command
|
1 = Quick stop was activated by the engineering tool via an axis command.
|
|
|
Bit 3
|
SS1 quick stop
|
1 = Quick stop was activated by the "safe stop 1 (SS1)" safety function.
|
|
|
Bit 6
|
Error response
|
1 = quick stop has been activated as a response to an error.
|
|
|
0x282A:003
|
Status words: Cause of stop
–
Read only
|
Bit coded display of the cause(s) of stop.
|
|
|
Bit 0
|
Flexible I/O: Start disabled
|
1 = stop was activated by the trigger set in 0x2631:002.
|
|
|
Bit 1
|
Flexible I/O: Run forward
|
1 = stop has been activated due to cancellation of the command "Run forward (CW)".
|
|
|
Bit 2
|
Flexible I/O: Run reverse
|
1 = stop has been activated due to cancellation of the command "Run reverse (CCW)".
|
|
|
Bit 3
|
Flexible I/O: Jog forward
|
1 = stop has been activated due to cancellation of the command "Jog forward (CW)".
|
|
|
Bit 4
|
Flexible I/O: Jog reverse
|
1 = stop has been activated due to cancellation of the command "Jog reverse (CCW)".
|
|
|
Bit 5
|
Network
|
1 = stop was activated via network.
|
|
|
Bit 7
|
Control mode transition
|
1 = stop has been activated due to a change of the operating mode.
|
|
|
Bit 9
|
Manual mode
|
1 = Stop was activated by the "Manual mode" function.
|
|
|
Bit 15
|
Waiting for start
|
1 = stop is active as a start command is not yet available (e. g. after enabling the inverter).
|
|
|
0x282A:004
|
Status words: Extended status word
–
Read only
|
Bit-coded status word.
|
|
|
Bit 8
|
Reverse rotational direction
|
1 = reversal active.
|
|
|
Bit 10
|
Inverter disabled (safety)
|
1 = The safety system integrated in the inverter has disabled the inverter/drive.
|
|
|
Bit 11
|
STO active
|
1 = "Safe Torque Off (STO)" safety function is active. Safe inputs SIA and SIB = LOW (simultaneously).
|
|
|
0x282A:005
|
Status words: Device status
–
Read only
|
Display of the current inverter device state.
|
|
|
0
|
Initialisation
|
||
|
2
|
Not ready to switch on
|
||
|
3
|
Switch on disabled
|
||
|
4
|
Ready to switch on
|
||
|
5
|
Switched on
|
||
|
6
|
Operation enabled
|
||
|
7
|
Disable operation
|
||
|
8
|
Shut down
|
||
|
9
|
Quick stop active
|
||
|
10
|
Fault reaction active
|
||
|
11
|
Fault
|
||
|
0x282B:001
|
Inverter diagnostics: Active control source
–
Read only
|
Display of the control source that is currently active.
|
|
|
0
|
Flexible I/O configuration
|
||
|
1
|
Network
|
||
|
3
|
Internal
|
||
|
9
|
Manual mode
|
||
|
0x282B:002
|
Inverter diagnostics: Active setpoint source
–
Read only
|
Display of the setpoint source that is currently active.
|
|
|
0
|
Not selected
|
||
|
1
|
Analog input 1
|
||
|
2
|
Analog input 2
|
||
|
5
|
Network Setpoint
|
||
|
9
|
Manual mode: setpoint
|
||
|
11
|
Setpoint preset 1
|
||
|
12
|
Setpoint preset 2
|
||
|
13
|
Setpoint preset 3
|
||
|
14
|
Setpoint preset 4
|
||
|
15
|
Setpoint preset 5
|
||
|
16
|
Setpoint preset 6
|
||
|
17
|
Setpoint preset 7
|
||
|
18
|
Setpoint preset 8
|
||
|
19
|
Setpoint preset 9
|
||
|
20
|
Setpoint preset 10
|
||
|
21
|
Setpoint preset 11
|
||
|
22
|
Setpoint preset 12
|
||
|
23
|
Setpoint preset 13
|
||
|
24
|
Setpoint preset 14
|
||
|
25
|
Setpoint preset 15
|
||
|
50
|
Motor potentiometer
|
||
|
190
|
Logic PLC output value 1
|
Output values of the integrated Logic PLC.
–
These selection options are only available for the I65AMxxxxxxxxxP product variant.
|
|
|
191
|
Logic PLC output value 2
|
||
|
210
|
IOL1 AI1 scaled value
|
Value is specified as process data object via IO-Link.
–
The function assignment of the connectors must be configured accordingly.
–
The IO-Link ports are only available on the inverter with Application-I/O.
|
|
|
211
|
IOL1 AI2 scaled value
|
||
|
212
|
IOL2 AI1 scaled value
|
||
|
213
|
IOL2 AI2 scaled value
|
||
|
214
|
IOL3 AI1 scaled value
|
||
|
215
|
IOL3 AI2 scaled value
|
||
|
216
|
IOL4 AI1 scaled value
|
||
|
217
|
IOL4 AI2 scaled value
|
||
|
230
|
Scaling1 value
|
Output values of the "Analog signal scaling" function. This function is used to scale internal analog signals (analog parameter values) for use within the inverter.
|
|
|
231
|
Scaling2 value
|
||
|
0x282B:004
|
Inverter diagnostics: Active drive mode
–
Read only
|
Display of the active drive mode.
|
|
|
0
|
Velocity mode
|
"Velocity mode" active.
|
|
|
1
|
PID control
|
PID control active.
|
|
|
2
|
Torque mode
|
"Torque mode" active.
|
|
|
3
|
Test mode (internal)
|
Test mode active.
|
|
|
4
|
Jog operation
|
"Jog forward (CW)" or "Jog reverse (CCW)" function active.
|
|
|
5
|
Table positioning
|
"Table Positioning" function is enabled.
|
|
|
0x2831
|
Inverter status word
–
Read only
|
Bit coded status word of the internal motor control.
|
|
|
Bit 1
|
Speed setpoint 1 limited
|
1 = input of speed controller 1 in limitation.
|
|
|
Bit 2
|
Speed controller in limitation
|
1 = output of speed controller 1 in limitation.
|
|
|
Bit 3
|
Torque setpoint limited
|
1 = setpoint torque in limitation.
|
|
|
Bit 4
|
Q-current setpoint limited
|
1 = setpoint current in limitation.
|
|
|
Bit 5
|
Speed setpoint 2 limited
|
1 = input of speed controller
2 in "torque mode" in limitation. |
|
|
Bit 6
|
Upper speed limit active
|
||
|
Bit 7
|
Lower speed limit active
|
||
|
Bit 8
|
Flying restart active
|
-
|
|
|
Bit 9
|
Flying restart completed
|
||
|
Bit 10
|
Output frequency limited
|
1 = setpoint frequency with V/f operation in limitation.
|
|
|
Bit 11
|
Magnetization completed
|
1 = Magnetisation completed during V/f operation.
Otherwise 0.
|
|
|
Bit 12
|
Motor phase error
|
1 = motor phase failure detection active.
|
|
|
0x2833
|
Inverter status word 2
–
Read only
|
Bit-coded status word 2 of the inverter.
|
|
|
Bit 1
|
Manual test mode active
|
1 = manual test mode active.
|
|
|
Bit 2
|
Manual control active
|
1 = manual control active.
|
|
|
Bit 6
|
DC braking active
|
1 = DC braking
active. |
|
|
0x293A
|
Actual switching frequency
–
Read only
|
Display of the currently active switching frequency of the inverter.
Example:
–
In 0x2939, "16 kHz variable / min. Pv [13]" is set as switching frequency.
–
The increase in ambient temperature and/or load has resulted in a reduction in the switching frequency to 8 kHz. In this case, this parameter displays the selection "8 kHz drive-optimized [3]".
|
|
|
1
|
2 kHz drive-optimized
|
||
|
2
|
4 kHz drive-optimized
|
||
|
3
|
8 kHz drive-optimized
|
||
|
4
|
16 kHz drive-optimized
|
||
|
5
|
2 kHz power loss-optimized
|
||
|
6
|
4 kHz power loss-optimized
|
||
|
7
|
8 kHz power loss-optimized
|
||
|
8
|
16 kHz power loss-optimized
|
||
|
9
|
12 kHz drive-optimised
|
||
|
10
|
12 kHz power loss-optimised
|
||
|
0x603F
|
Error code
–
Read only
|
Error message
|
|
|
0x6061
|
CiA: Active operation mode
–
Read only
|
CiA: Active operation mode
|
|
|
-11
|
Identification
|
||
|
-10
|
Test mode
|
||
|
-3
|
MS: Position mode
|
||
|
-2
|
MS: Velocity mode
|
Vendor specific velocity mode
|
|
|
-1
|
MS: Torque mode
|
Manufacturer-specific torque mode
|
|
|
0
|
No selection
|
No selection
|
|
|
2
|
CiA: Velocity mode (vl)
|
CiA: Velocity mode
|
|
Logic PLC