Speed limitation
The torque control controls the assigned torque setpoint within the set speed limits. The actual speed results from the load conditions of the application. For example, high speeds may occur in a torque control if no counter torque is available (load-free machine).
When the actual speed reaches the set speed limits, it is kept on the respective limit value. This function is also called "speed limitation".
Details
The lower and upper speed limit for speed limitation can be set independently of each other. The specification can also be made via network or IO-Link ports.
Required parameter setting:
1.
Select the source for the upper speed limit in 0x2946:003.
–
Default setting: Maximum frequency 0x2916
–
In case of selection "Upper frequency limit [4]": Set the upper speed limit in [Hz] in 0x2946:005.
–
In case of selection "Upper speed limit [5]": Set the upper speed limit in [vel. unit] in 0x2946:001.
–
The current upper speed limit is displayed in 0x2946:007.
2.
Select the source for the lower speed limit in 0x2946:004.
–
Default setting: (-) Maximum frequency 0x2916
–
In case of selection "Lower frequency limit [4]": Set the lower speed limit in [Hz] in 0x2946:006.
–
In case of selection "Lower speed limit [5]": Set the lower speed limit in [vel. unit] in 0x2946:002.
–
The output frequency is absolutely limited regardless of the setting 0x2946:003 and 0x2946:004 by 0x2916 in the “Torque mode”.
–
The current lower speed limit is displayed in 0x2946:008.
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x2946:001
|
Speed limitation: Upper speed limit
-480000 ... [0] ... 480000 rpm
|
Upper limit for the speed limitation.
–
Setting is only effective with the selection "Upper speed limit [5]" in 0x2946:003.
–
Entry via Lenze Tools is in rpm!
–
Via RPDO, the unit is vel. unit. and the scaling must be taken into account.
–
± 480000 rpm = ± 2 ^ 31 [n-unit] |
|
|
0x2946:002
|
Speed limitation: Lower speed limit
-480000 ... [0] ... 480000 rpm
|
Lower limit for speed limitation.
–
Setting is only effective with the selection "Lower speed limit [5]" in 0x2946:004.
–
Entry via Lenze Tools is in rpm!
–
Via RPDO, the unit is vel. unit. and the scaling must be taken into account.
–
± 480000 rpm = ± 2 ^ 31 [n-unit] |
|
|
0x2946:003
|
Speed limitation: Upper speed limit source
|
Selection of the source for the upper speed limit.
|
|
|
0
|
Maximum frequency
|
Upper speed limit = Maximum frequency 0x2916.
|
|
|
1
|
Fixed Limit 0.0 Hz
|
Upper speed limit = 0.0 Hz.
|
|
|
2
|
Analog input 1
|
The upper speed limit is defined as analog signal via the analog input 1.
|
|
|
3
|
Analog input 2
|
The upper speed limit is defined as analog signal via the analog input 2.
|
|
|
4
|
Upper frequency limit
|
Upper speed limit = setting in 0x2946:005 in [Hz].
|
|
|
5
|
Upper speed limit
|
Upper speed limit = setting in 0x2946:001 in [vel. unit].
|
|
|
6
|
Network target velocity
|
The upper speed limit is defined as process data object via network.
|
|
|
210
|
IOL1 AI1 scaled value
|
Value is specified as process data object via IO-Link.
–
The function assignment of the connectors must be configured accordingly.
–
The IO-Link ports are only available on the inverter with Application-I/O.
|
|
|
211
|
IOL1 AI2 scaled value
|
||
|
212
|
IOL2 AI1 scaled value
|
||
|
213
|
IOL2 AI2 scaled value
|
||
|
214
|
IOL3 AI1 scaled value
|
||
|
215
|
IOL3 AI2 scaled value
|
||
|
216
|
IOL4 AI1 scaled value
|
||
|
217
|
IOL4 AI2 scaled value
|
||
|
230
|
Scaling1 value
|
Output values of the "Analog signal scaling" function. This function is used to scale internal analog signals (analog parameter values) for use within the inverter.
|
|
|
231
|
Scaling2 value
|
||
|
0x2946:004
|
Speed limitation: Lower speed limit source
|
Selection of the source for the lower speed limit.
|
|
|
0
|
(-) Maximum frequency
|
Lower speed limit = (-) Maximum frequency 0x2916.
|
|
|
1
|
Fixed Limit 0.0 Hz
|
Lower speed limit = 0.0 Hz.
|
|
|
2
|
Analog input 1
|
The lower speed limit is defined as analog signal via the analog input 1.
|
|
|
3
|
Analog input 2
|
The lower speed limit is defined as analog signal via the analog input 2.
|
|
|
4
|
Lower frequency limit
|
Lower speed limit = setting in 0x2946:006 in [Hz].
|
|
|
5
|
Lower speed limit
|
Lower speed limit = setting in 0x2946:002 in [vel. unit].
|
|
|
6
|
Network target velocity
|
The lower speed limit is defined as process data object via network.
|
|
|
210
|
IOL1 AI1 scaled value
|
Value is specified as process data object via IO-Link.
–
The function assignment of the connectors must be configured accordingly.
–
The IO-Link ports are only available on the inverter with Application-I/O.
|
|
|
211
|
IOL1 AI2 scaled value
|
||
|
212
|
IOL2 AI1 scaled value
|
||
|
213
|
IOL2 AI2 scaled value
|
||
|
214
|
IOL3 AI1 scaled value
|
||
|
215
|
IOL3 AI2 scaled value
|
||
|
216
|
IOL4 AI1 scaled value
|
||
|
217
|
IOL4 AI2 scaled value
|
||
|
230
|
Scaling1 value
|
Output values of the "Analog signal scaling" function. This function is used to scale internal analog signals (analog parameter values) for use within the inverter.
|
|
|
231
|
Scaling2 value
|
||
|
0x2946:005
|
Speed limitation: Upper frequency limit
-1000.0 ... [50.0] ... 1000.0 Hz
|
Upper limit for the speed limitation.
|
|
|
0x2946:006
|
Speed limitation: Lower frequency limit
-1000.0 ... [-50.0] ... 1000.0 Hz
|
Lower limit for speed limitation.
|
|
|
0x2946:007
|
Speed limitation: Actual upper speed limit
–
Read only: x.x Hz
|
Display of the current upper limit for speed limitation.
|
|
|
0x2946:008
|
Speed limitation: Actual lower speed limit
–
Read only: x.x Hz
|
Display of the current lower limit for speed limitation.
|
|
Analog input 1