Mappable parameters for exchanging setpoints and actual values

The parameters listed in the following can also be mapped to network registers, in order to transfer set points and actual values via the network.
 
–
The parameters are always available irrespective of the network option.
 
–
Several parameters with different resolutions are available for selection to transfer the frequency setpoint and actual value.
 
–
The use of these parameters for the transmission of process data is optional. It is also possible to use only a selection of the parameters.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x400B:003
Process input data: Network setpoint frequency (0.1)
0.0 ... [0.0] ... 1000.0 Hz
Mappable parameter for specifying the frequency setpoint in [0.1 Hz] via network.
–
The specification is made without sign (irrespective of the rotating direction).
 
–
The rotating direction is specified via the control word.
 
–
Example: 456 = 45.6 Hz
 
0x400B:004
Process input data: Network setpoint speed
0 ... [0] ... 65535 rpm
Mappable parameter for specifying the setpoint as speed in [rpm] via network.
–
The specification is made without sign (irrespective of the rotating direction).
 
–
The rotating direction is specified via the control word.
 
–
Example: 456 ≡ 456 rpm
 
0x400B:005
Process input data: Network setpoint frequency (0.01)
0.00 ... [0.00] ... 655.35 Hz
Mappable parameter for specifying the frequency setpoint in [0.01 Hz] via network.
–
The specification is made without sign (irrespective of the rotating direction).
 
–
The rotating direction is specified via the control word.
 
–
Example: 456 = 4.56 Hz
 
0x400B:009
Process input data: Torque scaling
-128 ... [0] ... 127
Scaling factor for torque setpoint 0x400B:008 and actual torque value 0x400C:007 via network.
–
With the setting 0, no scaling takes place.
 
Example:
–
Scaled actual torque value (0x400C:007) = 345 [Nm]
 
–
Scaling factor (0x400B:009) = 3
 
–
Actual torque value = 345 [Nm] / 23 = 43.125 [Nm]
 
0x400B:013
Process input data: Network frequency setpoint [+/-16384]
-16384 ... [0] ... 16384
Mappable parameter for specifying the frequency setpoint via network.
–
±
16384 =
±
100 % Maximum frequency 0x2916
 
0x400C:003
Process output data: Frequency (0.1)
–
Read only: x.x Hz
 
Mappable parameter for the output of the actual frequency value in [0.1 Hz] via network.
–
The output is effected without sign (irrespective of the rotating direction).
 
–
The rotating direction is specified via the status word.
 
–
Example: 456 = 45.6 Hz
 
0x400C:004
Process output data: Motor speed
–
Read only: x rpm
 
Mappable parameter for the output of the actual value as speed in [rpm] via network.
–
The output is made without sign (irrespective of the rotating direction).
 
–
The rotating direction is specified via the status word.
 
–
Example: 456 ≡ 456 rpm
 
0x400C:006
Process output data: Frequency (0.01)
–
Read only: x.xx Hz
 
Mappable parameter for the output of the actual frequency value in [0.01 Hz] via network.
–
The output is made without sign (irrespective of the rotating direction).
 
–
The rotating direction is specified via the status word.
 
–
Example: 456 = 4.56 Hz
 
0x400C:007
Process output data: Torque scaled
–
Read only
 
Mappable parameter for the output of the actual torque value in [Nm / 2scaling factor] via network.
–
The scaling factor can be set in 0x400B:009.
 
–
Actual torque value = scaled actual torque value (0x400C:007) / 2scaling factor
 
Example:
–
Scaled actual torque value (0x400C:007) = 345 [Nm]
 
–
Scaling factor (0x400B:009) = 3
 
–
Actual torque value = 345 [Nm] / 23 = 43.125 [Nm]
 
0x400C:009
Process output data: Frequency [+/-16384]
–
Read only
 
Mappable parameter for the output of the actual frequency value via network.
–
±
16384 =
±
100 % Maximum frequency 0x2916