Define setpoint via network

The network setpoint must be explicitly selected if the setpoint is to be specified via the network.
 
Mappable parameters
The following mappable parameter 0x400B:006 is available, among others, for specifying the setpoint.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x400B:006
Process input data: Velocity mode setpoint
-1000.0 ... [0.0] ... 1000.0 Hz
Mappable parameter for defining the setpoint for operating mode "MS: Velocity mode" via network.
–
If this parameter is to be used as standard setpoint source, the selection "Network [5]" must be set in 0x2860:001.
 
–
If this bipolar setpoint is used, the direction of rotation cannot be controlled via the network control word. The direction of rotation is determined by the sign of the setpoint.
 
0x400B:007
Process input data: PID setpoint
-300.00 ... [0.00] ... 300.00 PID unit
Mappable parameter for defining the setpoint for the PID control via network.
–
If this parameter is to be used as standard setpoint source, the selection "Network [5]" must be set in 0x2860:002.
 
0x400B:008
Process input data: Torque mode setpoint
-32768 ... [0] ... 32767 Nm
Mappable parameter for defining the setpoint for operating mode "MS: Torque mode" via network.
–
If this parameter is to be used as standard setpoint source, the selection "Network [5]" must be set in 0x2860:003.
 
–
The scaling factor can be set in 0x400B:009.
 
–
Scaled torque setpoint = torque setpoint (0x400B:008) / 2scaling factor
 
Example:
–
Torque setpoint (0x400B:008) = 345 [Nm]
 
–
Scaling factor (0x400B:009) = 3
 
–
Scaled torque setpoint = 345 [Nm] / 23 = 43.125 [Nm]
 
 
In addition, further mappable parameters with different resolutions are available for the transmission of the frequency setpoint and actual frequency values.