Standard setpoint source
The selected "setpoint source" serves to provide the inverter with its setpoint. The setpoint source can be selected individually for each operating mode.
Possible setpoint sources:
–
Parameterizable setpoints (presets)
–
Network
–
IO-Link ports
–
"Motor potentiometer" function
–
"Analog signal scaling" function
Details
–
For applications only requiring one setpoint, it is sufficient to define the standard setpoint source in 0x2860:003.
–
For applications requiring a change-over of the setpoint source during operation, the functions for setpoint change-over have to be configured accordingly.
Changing the setpoint source during operation
Configure setpoint sources
Changing the setpoint source during operation
Configure setpoint sources Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x2860:003
|
Torque control: Default setpoint source
|
Selection of the standard setpoint source for operating mode "MS: Torque mode".
–
The selected standard setpoint source is always active in the operating mode 0x6060 = "MS: Torque mode [-1]" when no setpoint change-over to another setpoint source via corresponding triggers/functions is active.
|
|
|
2
|
Analog input 1
|
The setpoint is defined as analog signal via the analog input 1.
|
|
|
3
|
Analog input 2
|
The setpoint is defined as analog signal via the analog input 2.
|
|
|
5
|
Network
|
The setpoint is defined as process data object via the network.
|
|
|
11
|
Torque preset 1
|
For the setpoint selection, preset values can be parameterised and selected.
|
|
|
12
|
Torque preset 2
|
||
|
13
|
Torque preset 3
|
||
|
14
|
Torque preset 4
|
||
|
15
|
Torque preset 5
|
||
|
16
|
Torque preset 6
|
||
|
17
|
Torque preset 7
|
||
|
18
|
Torque preset 8
|
||
|
50
|
Motor potentiometer
|
The setpoint is generated by the "motor potentiometer" function. This function can be used as an alternative setpoint control which is controlled via two signals: "MOP setpoint up" and "MOP setpoint down".
|
|
|
190
|
Logic PLC output value 1
|
Output values of the integrated Logic PLC.
–
These selection options are only available for the I65AMxxxxxxxxxP product variant.
|
|
|
191
|
Logic PLC output value 2
|
||
|
210
|
IOL1 AI1 scaled value
|
Value is specified as process data object via IO-Link.
–
The function assignment of the connectors must be configured accordingly.
–
The IO-Link ports are only available on the inverter with Application-I/O.
|
|
|
211
|
IOL1 AI2 scaled value
|
||
|
212
|
IOL2 AI1 scaled value
|
||
|
213
|
IOL2 AI2 scaled value
|
||
|
214
|
IOL3 AI1 scaled value
|
||
|
215
|
IOL3 AI2 scaled value
|
||
|
216
|
IOL4 AI1 scaled value
|
||
|
217
|
IOL4 AI2 scaled value
|
||
|
230
|
Scaling1 value
|
Output values of the "Analog signal scaling" function. This function is used to scale internal analog signals (analog parameter values) for use within the inverter.
|
|
|
231
|
Scaling2 value
|
||
Analog input 1