Configure setpoint sources
The standard setpoint source for torque control can be selected in 0x2860:003. This chapter describes the setting options for the various setpoint sources.
–
Preset torque setpoint source: Torque preset 1 (0x2912:001)
–
Except for the network, the torque setpoint must be given in percent with regard to the 0x6076 rated motor torque.
–
Via network the torque setpoint is selected via the mappable parameter 0x400B:008 in [Nm / 2scaling factor]. The scaling factor can be set in 0x400B:009.
–
Corresponding functions make it possible to change over to other setpoint sources during operation. More detailed information on this can be found in the chapter "Configuring frequency control”
Changing the setpoint source during operation
Changing the setpoint source during operation The following setpoint sources are described in this chapter:
–
–
Other setpoint source descriptions can be found here:
–
Network: Define setpoint via network
–
IO-Link ports: Configure IO-Link ports
–
Function "Analog signal scaling"