Basic setting

In the following, the steps required for configuring the torque control are described.
 
1.
Select the motor control mode "Sensorless vector control (SLVC) [4]" or "Servo control (SC ASM) [2]” in 0x2C00.
 
2.
Carry out motor adjustment. Configuring the motor control 
 
3.
Select the operating mode "MS: Torque mode [-1]" in0x6060.
 
4.
Select the standard setpoint source for the torque control in 0x2860:003.
 
5.
Set the rated motor torque in 0x6076.
 
6.
Set the torque limits. Torque limits 
 
7.
Set the speed limitation. Speed limitation 
 
8.
 
9.
Optional: Set the torque setpoint ramp time in 0x2948:002.
 
The following signal flow shows the internal setpoint logics:
 
The torque control with frequency limitation is now active and the inverter responds to the torque setpoint given by the selected setpoint source.