Torque limits

The necessary parameterizations can be found in the table.
 
Details
The positive and negative torque limit can be set independently of each other. The torque limit must be set to the maximum torque. 0x6072
 
–
Display of the current positive torque limit in 0x2949:004.
 
–
Display of the current negative torque limit in 0x2949:003.
 
The torque limits are also active in the "Velocity Mode" with the "Servo control (SC-ASM)" motor control mode.
Regardless of the setting in 0x2949:001 and 0x2949:002, the maximum torque does not exceed the value configured in 0x6072.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2949:001
Torque limit source selection: Positive torque limit source
Selection of the source for the positive torque limit source.
0
Max torque
Positive torque limit source = Max. torque 0x6072.
1
Fixed Limit 0.0 %
Positive torque limit source = 0.0 %.
2
Analog Input 1
The positive torque limit source is defined as analog signal via the analog input 1.
3
Analog Input 2
The positive torque limit source is defined as analog signal via the analog input 2.
4
Positive torque limit
Positive torque limit source = Positive torque limit 0x60E0.
5
Network target torque
The positive torque limit source is defined as process data object via network.
210
IOL1 AI1 scaled value
Value is specified as process data object via IO-Link.
–
The function assignment of the connectors must be configured accordingly.
 
–
The IO-Link ports are only available on the inverter with Application-I/O.
 
211
IOL1 AI2 scaled value
212
IOL2 AI1 scaled value
213
IOL2 AI2 scaled value
214
IOL3 AI1 scaled value
215
IOL3 AI2 scaled value
216
IOL4 AI1 scaled value
217
IOL4 AI2 scaled value
230
Scaling1 value
Output values of the "Analog signal scaling" function. This function is used to scale internal analog signals (analog parameter values) for use within the inverter.
231
Scaling2 value
0x2949:002
Torque limit source selection: Negative torque limit source
Selection of the source for the negative torque limit source.
0
(-) Max torque
Negative torque limit source = (-) Max. torque 0x6072.
1
Fixed Limit 0.0 %
Negative torque limit source = 0.0 %.
2
Analog Input 1
The negative torque limit source is defined as analog signal via the analog input 1.
3
Analog Input 2
The negative torque limit source is defined as analog signal via the analog input 2.
4
Negative torque limit
Negative torque limit source = Negative torque limit 0x60E1.
5
Network target torque
The negative torque limit source is defined as process data object via network.
210
IOL1 AI1 scaled value
Value is specified as process data object via IO-Link.
–
The function assignment of the connectors must be configured accordingly.
 
–
The IO-Link ports are only available on the inverter with Application-I/O.
 
211
IOL1 AI2 scaled value
212
IOL2 AI1 scaled value
213
IOL2 AI2 scaled value
214
IOL3 AI1 scaled value
215
IOL3 AI2 scaled value
216
IOL4 AI1 scaled value
217
IOL4 AI2 scaled value
230
Scaling1 value
Output values of the "Analog signal scaling" function. This function is used to scale internal analog signals (analog parameter values) for use within the inverter.
231
Scaling2 value
0x60E0
Positive torque limit
0.0 ... [250.0] ... 3276.7 %
Positive torque limit source for speed control with torque limitation.
–
100 % = Rated motor torque 0x6076
 
0x60E1
Negative torque limit
0.0 ... [250.0] ... 3276.7 %
Negative torque limit source for speed control with torque limitation.
–
100 % = Rated motor torque 0x6076