Motor torque monitoring

This function limits the motor torque during operation.
 
Preconditions
The motor torque monitoring can only be used for the following motor control types with speed controller:
–
Servo control (SC ASM)
 
–
Sensorless vector control (SLVC)
 
–
Sensorless control for synchronous motors (SLSM-PSM)
 
 
Details
This function sets the internal status signal "Torque limit reached [79]" = TRUE when the maximum possible torque has been reached.
The limits of the monitoring function are selected via 0x2949:001 (positive torque limit) and 0x2949:002 (negative torque limit). The actual limits can be seen in 0x2949:003 (actual positive torque limit), 0x2949:004 (actual negative torque limit).
–
The status signal is set irrespective of the response 0x2D67:001 and the delay time 0x2D67:002 set for this monitoring.
 
–
The status signal can be used by the user to
 
–
activate certain functions. Flexible I/O configuration 
 
–
set a digital output. Configure digital outputs 
 
–
set a bit of the NetWordOUT1 mappable data word. Motor speed monitoring 
 
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2D67:001
Maximum torque monitoring: Response
Selection of response to reaching the maximum possible torque.
–
The selected response takes place if the status signal "Torque limit reached [79]" = TRUE and the deceleration time set in 0x2D67:002 has elapsed.
 
Associated event ID:
–
33553 | 0x8311 - Torque limit reached
 
0
No response
11
Information
12
Warning
16
Trouble
23
Fault > inverter disabled
0x2D67:002
Maximum torque monitoring: Triggering delay
0.000 ... [0.000] ... 10.000 s
Optional setting of a deceleration for triggering the response selected in 0x2D67:001.
Typical application:
–
The motor should be driven at the torque limit for a short time without triggering the selected response.
 
–
Only after a longer operation (> set deceleration) at the torque limit, the selected response is to take place.
 
0x6072
Max. torque
0.0 ... [250.0] ... 3000.0 %
Symmetrical selection of the maximum permissible torque.
–
100 % =  Rated motor torque 0x6076
 
–
This parameter serves to implement a static and bipolar torque limitation. This can be used, for instance, as overload protection of the mechanical transmission path/elements starting at the motor shaft.
 
–
This limitation acts irrespective of the torque limitations acting in unipolar mode that are set in 0x60E0 and 0x60E1.