Configure digital outputs

With the "DOx" function assignment for the X3 connectors, the inverter provides normal digital outputs.
 
Preconditions
–
The function assignment of the connectors must be configured accordingly. Configure function assignment 
 
–
The digital outputs available depend on the type of control connections:
 
–
Standard-I/O: Digital output 1 (DO1)
 
–
Application-I/O: Digital output 1 ... digital output 4 (DO1 ... DO4)
 
–
Extended-I/O: Digital output 1 and digital output 3 (DO1 and DO3)
 
 
 
Details
The digital outputs are controlled by the triggers selected in 0x2634:002 ... 0x2634:005 are used to control the digital outputs.
The following settings are possible for the digital outputs:
–
Inversion ①
 
–
Switch-on delay ②
 
–
Cutout delay ③
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2634:002
Digital outputs function: Digital output 1
Assignment of a trigger to digital output 1.
Trigger = FALSE: X3/DO1 set to LOW level.
Trigger = TRUE: X3/DO1 set to HIGH level.
Notes:
–
An inversion set in 0x2635:002 is taken into consideration here.
 
0
Not connected
No trigger assigned (trigger is constantly FALSE).
1
Constant TRUE
Trigger is constantly TRUE.
11
Digital input 1
State of X3/DI1, taking an inversion set in 0x2632:001 into consideration.
12
Digital input 2
State of X3/DI2, taking an inversion set in 0x2632:002 into consideration.
13
Digital input 3
State of X3/DI3, taking an inversion set in 0x2632:003 into consideration.
14
Digital input 4
State of X3/DI4, taking an inversion set in 0x2632:004 into consideration.
15
Digital input 5
State of X3/DI5, taking an inversion set in 0x2632:005 into consideration.
16
Digital input 6
State of X3/DI6, taking an inversion set in 0x2632:006 into consideration.
17
Digital input 7
State of X3/DI7, taking an inversion set in 0x2632:007 into consideration.
18
Digital input 8
State of X3/DI8, taking an inversion set in 0x2632:008 into consideration.
30
NetWordIN1 - bit 12
State of NetWordIN1/bit 12 ... 15.
–
Display of NetWordIN1 in 0x4008:001.
 
–
For implementing an individual control word format, NetWordIN1 can be mapped to a process data input word.
 
31
NetWordIN1 - bit 13
32
NetWordIN1 - bit 14
33
NetWordIN1 - bit 15
34
NetWordIN2 - bit 0
State of NetWordIN2/bit 0 ... bit 15.
–
Display of NetWordIN2 in 0x4008:002.
 
–
For controlling the digital outputs via network, NetWordIN2 can be mapped to a process data input word.
 
35
NetWordIN2 - bit 1
36
NetWordIN2 - bit 2
37
NetWordIN2 - bit 3
38
NetWordIN2 - bit 4
39
NetWordIN2 - bit 5
40
NetWordIN2 - bit 6
41
NetWordIN2 - bit 7
42
NetWordIN2 - bit 8
43
NetWordIN2 - bit 9
44
NetWordIN2 - bit 10
45
NetWordIN2 - bit 11
46
NetWordIN2 - bit 12
47
NetWordIN2 - bit 13
48
NetWordIN2 - bit 14
49
NetWordIN2 - bit 15
50
Running
TRUE if inverter and start are enabled and output frequency > 0 Hz. Otherwise FALSE.
Exception, quick stop mode: TRUE if inverter and start are enabled and output frequency > 0.2 Hz. Otherwise FALSE.
51
Ready for operation
TRUE if inverter is ready for operation (no error active, no STO active and DC-bus voltage ok). Otherwise FALSE.
52
Operation enabled
TRUE if inverter and start are enabled. Otherwise FALSE.
53
Stop active
TRUE if inverter is enabled and motor is not started and output frequency = 0.
54
Quick stop active
TRUE if quick stop is active. Otherwise FALSE.
55
Inverter disabled (safety)
TRUE if the integrated safety system has inhibited the inverter. Otherwise FALSE.
56
Fault active
TRUE if error is active. Otherwise FALSE.
57
Error (non-resettable) active
TRUE if non-resettable error is active. Otherwise FALSE.
58
Device warning active
TRUE if warning is active. Otherwise FALSE.
–
A warning has no impact on the operating status of the inverter.
 
–
A warning is reset automatically if the cause has been eliminated.
 
59
Device trouble active
TRUE if a fault is active. Otherwise FALSE.
–
In the event of a fault, the motor is brought to a standstill with the quick stop ramp. The inverter is then disabled.
 
–
Exception: In case of a serious fault, the inverter is disabled immediately. The motor has no torque (coasts).
 
–
The error state will be left automatically if the error condition is not active anymore.
 
–
The restart behaviour after trouble can be configured. Automatic restart after a fault 
 
60
Heatsink temperature warning active
TRUE if current heatsink temperature > warning threshold for temperature monitoring. Otherwise FALSE.
–
Display of the current heatsink temperature in 0x2D84:001.
 
–
Setting of the warning threshold in 0x2D84:002.
 
65
Motor PTC error active
TRUE if an error of the motor PTC has been detected. Otherwise FALSE.
–
The trigger is set irrespective of the response set in 0x2D49:002 when the motor temperature monitoring is triggered.
 
66
Flying restart circuit active
TRUE if flying restart circuit active is active. Otherwise FALSE.
67
DC braking active
TRUE if DC braking is active. Otherwise FALSE.
68
Stop command active
TRUE if delay to standstill active. Otherwise FALSE.
69
Rotational direction reversed
TRUE if output frequency is negative. Otherwise FALSE.
70
Frequency threshold exceeded
TRUE if current output frequency > frequency threshold. Otherwise FALSE.
–
Display of the current output frequency in 0x2DDD.
 
–
Setting Frequency threshold in 0x4005.
 
71
Actual speed = 0
TRUE if actual output frequency = 0 Hz (
±
0.3 Hz), irrespective of the operating mode. Otherwise FALSE.
–
Display of the current output frequency in 0x2DDD.
 
72
Setpoint speed reached
TRUE if frequency setpoint reached. Otherwise FALSE.
73
PID feedback = setpoint
TRUE if the controlled feedback variable = process controller setpoint (± in 0x404D:003 set hysteresis). Otherwise FALSE.
74
PID sleep mode active
TRUE if the inverter is in "PID sleep mode". Otherwise FALSE.
75
PID MIN alarm active
TRUE if feedback variable (with activated PID control) < MIN alarm threshold. Otherwise FALSE.
–
Setting of MIN alarm threshold in 0x404D:001.
 
76
PID MAX alarm active
TRUE if the feedback variable (with activated PID control) > MAX alarm threshold. Otherwise FALSE.
–
Setting of MAX alarm threshold in 0x404D:002.
 
77
PID MIN-MAX alarm active
TRUE if no PID alarm is active with activated PID control (MIN alarm threshold < feedback variable < MAX alarm threshold). Otherwise FALSE.
–
Setting of MIN alarm threshold in 0x404D:001.
 
–
Setting of MAX alarm threshold in 0x404D:002.
 
78
Current limit reached
TRUE if current motor current
≥
maximum current. Otherwise FALSE.
–
Display of the present motor current in 0x2D88.
 
–
Setting for the maximum current in 0x6073.
 
79
Torque limit reached
TRUE if torque limit has been reached or exceeded. Otherwise FALSE.
–
Setting "Actual positive torque limit" in 0x2949:003.
 
–
Setting "Actual negative torque limit" in 0x2949:004.
 
81
Error of analog input 1 active
TRUE if the monitoring of the input signal at the analog input 1 has responded. Otherwise FALSE.
This trigger is set as a function of the following settings:
–
Monitoring threshold 0x2636:008
 
–
Monitoring condition 0x2636:009
 
The setting of the Error response in 0x2636:010 has no effect on this trigger.
82
Error of analog input 2 active
TRUE if the monitoring of the input signal at the analog input 2 has responded. Otherwise FALSE.
This trigger is set as a function of the following settings:
–
Monitoring threshold 0x2637:008
 
–
Monitoring condition 0x2637:009
 
The setting of the Error response in 0x2637:010 has no effect on this trigger.
83
Load loss detected
TRUE if actual motor current < threshold for load loss detection after delay time of the load loss detection has elapsed. Otherwise FALSE.
–
Display of the actual current in 0x6078.
 
–
Setting Threshold in 0x4006:001.
 
–
Setting Delay time in 0x4006:002.
 
84
Heavy load monitoring
TRUE if the actual apparent current of the motor exceeds the threshold for longer than the delay time.
FALSE if the actual apparent current of the motor falls below the threshold value minus 5 % (hysteresis).
108
Parameter set 1 active
TRUE if parameter set 1 is loaded and active. Otherwise FALSE.
109
Parameter set 2 active
TRUE if parameter set 2 is loaded and active. Otherwise FALSE.
110
Parameter set 3 active
TRUE if parameter set 3 is loaded and active. Otherwise FALSE.
111
Parameter set 4 active
TRUE if parameter set 4 is loaded and active. Otherwise FALSE.
112
Parameter set load OK
TRUE after any parameter set has been loaded. Otherwise FALSE.
113
Parameter set load fail
TRUE if any of the parameter sets could not be loaded. Otherwise FALSE.
115
Release holding brake
Trigger signal for releasing the holding brake (TRUE = release holding brake).
Note!
If this trigger is assigned to the relay or a digital output, the deceleration times set for the respective output are not effective (are internally set to "0"). Only the deceleration time set in 0x2820:012 for closing the holding brake influences in this case the time-dependent behaviour of the output.
117
Motor phase failure
TRUE if a motor phase failure has been detected. Otherwise FALSE.
Note!
In the "SLSM-PSM" motor control mode, detection for motor phase failure is deactivated if HF injection is active in the low-speed range.
119
Holding brake released
TRUE, if holding brake is released. Otherwise FALSE.
120
Homing active
Status signals output by the "Table positioning" function.
–
These selection options are only available for the I65AMxxxxxxxxxP product variant.
 
121
Homing done
122
Manual jog active
123
Halt active
124
Motor control in limitation
125
Set position reached
126
Abort active
127
Standstill
128
Active profile (bit 1)
129
Active profile (bit 2)
130
Active profile (bit 3)
131
Active profile (bit 4)
132
Positioning profile active
133
Positioning profile done
134
Negative hardware limit switch active
135
Positive hardware limit switch active
136
Touch probe detected
137
External position active
155
STO active
TRUE if the integrated safety system has triggered the "Safe torque off (STO)" function and if the safe inputs SIA and SIB = LOW (simultaneously). Otherwise FALSE.
169
Logic PLC Out bit 0
Binary values output by the integrated Logic PLC.
–
These selection options are only available for the I65AMxxxxxxxxxP product variant.
 
170
Logic PLC Out bit 1
171
Logic PLC Out bit 2
172
Logic PLC Out bit 3
173
Logic PLC Out bit 4
174
Logic PLC Out bit 5
175
Logic PLC Out bit 6
176
Logic PLC Out bit 7
177
Logic PLC Out bit 8
178
Logic PLC Out bit 9
179
Logic PLC Out bit 10
180
Logic PLC Out bit 11
181
Logic PLC Out bit 12
182
Logic PLC Out bit 13
183
Logic PLC Out bit 14
184
Logic PLC Out bit 15
0x2634:003
Digital outputs function: Digital output 2
–
For further possible settings, see parameter 0x2634:002.
 
Assignment of a trigger to digital output 2.
Trigger = FALSE: X3/DO2 set to LOW level.
Trigger = TRUE: X3/DO2 set to HIGH level.
Notes:
–
An inversion set in 0x2635:003 is taken into consideration here.
 
56
Fault active
TRUE if error is active. Otherwise FALSE.
0x2634:004
Digital outputs function: Digital output 3
–
For further possible settings, see parameter 0x2634:002.
 
Assignment of a trigger to digital output 3.
Trigger = FALSE: X3/DO3 set to LOW level.
Trigger = TRUE: X3/DO3 set to HIGH level.
Notes:
–
An inversion set in 0x2635:004 is taken into consideration here.
 
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2634:005
Digital outputs function: Digital output 4
–
For further possible settings, see parameter 0x2634:002.
 
Assignment of a trigger to digital output 4.
Trigger = FALSE: X3/DO4 set to LOW level.
Trigger = TRUE: X3/DO4 set to HIGH level.
Notes:
–
An inversion set in 0x2635:005 is taken into consideration here.
 
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2635:002
Inversion of digital outputs: Digital output 1
Inversion of digital output 1
0
Not inverted
1
Inverted
0x2635:003
Inversion of digital outputs: Digital output 2
Inversion of digital output 2
0
Not inverted
1
Inverted
0x2635:004
Inversion of digital outputs: Digital output 3
Inversion of digital output 3
0
Not inverted
1
Inverted
0x2635:005
Inversion of digital outputs: Digital output 4
Inversion of digital output 4
0
Not inverted
1
Inverted
0x401A:001
Digital output configuration: DO1 switch-off delay
0.000 ... [0.000] ... 65.535 s
0x401A:002
Digital output configuration: DO1 switch-on delay
0.000 ... [0.000] ... 65.535 s
0x401A:003
Digital output configuration: DO1 terminal state
–
Read only
 
0x401A:004
Digital output configuration: DO1 trigger signal state
–
Read only
 
0x401A:011
Digital output configuration: DO2 switch-off delay
0.000 ... [0.000] ... 65.535 s
0x401A:012
Digital output configuration: DO2 switch-on delay
0.000 ... [0.000] ... 65.535 s
0x401A:013
Digital output configuration: DO2 terminal state
–
Read only
 
0x401A:014
Digital output configuration: DO2 trigger signal state
–
Read only
 
0x401A:021
Digital output configuration: DO3 switch-off delay
0.000 ... [0.000] ... 65.535 s
0x401A:022
Digital output configuration: DO3 switch-on delay
0.000 ... [0.000] ... 65.535 s
0x401A:023
Digital output configuration: DO3 terminal state
–
Read only
 
0x401A:024
Digital output configuration: DO3 trigger signal state
–
Read only
 
0x401A:031
Digital output configuration: DO4 switch-off delay
0.000 ... [0.000] ... 65.535 s
0x401A:032
Digital output configuration: DO4 switch-on delay
0.000 ... [0.000] ... 65.535 s
0x401A:033
Digital output configuration: DO4 terminal state
–
Read only
 
0x401A:034
Digital output configuration: DO4 trigger signal state
–
Read only