Trigger action if a frequency threshold is exceeded

As a function of the current output frequency, the adjustable frequency threshold serves to trigger a certain function or set a digital output.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x4005
Frequency threshold
0.0 ... [0.0] ... 1000.0 Hz
Threshold for the "Frequency threshold exceeded [70]" trigger.
–
The "Frequency threshold exceeded [70]" trigger is TRUE if the current output frequency is higher than the set threshold.
 
–
The trigger can be assigned to a function or to a digital output.
 
 
Example for operating mode
In the following example, the digital output 1 is set to TRUE if the output frequency is higher than 20 Hz.
–
As standard setpoint source, preset 1 (40 Hz) is set.
 
–
Switch S1 starts the motor in forward direction of rotation. Switch S1 in initial position stops the motor again.
 
Connection diagram
Function
Switch S1
Run
Parameter
Name
Setting for this example
Plug X3.1 configuration
DI2 + DO1 [2]
Enable inverter
Constant TRUE [1]
Run
Digital input 1 [11]
Digital outputs function: Digital output 1
Frequency threshold exceeded [70]
Frequency control: Default setpoint source
Frequency preset 2 [12]
Frequency setpoint presets: Preset 2
40.0 Hz
Acceleration time 1
9.00 s
Deceleration time 1
3.00 s
Frequency threshold
20.0 Hz
 
The status signals can be assigned to digital outputs. Configure digital outputs
①
Frequency threshold 0x4005
②
Frequency threshold exceeded: Via trigger "Frequency threshold exceeded [70]", the digital output 1 is set to TRUE.