Trigger action if a frequency threshold is exceeded
As a function of the current output frequency, the adjustable frequency threshold serves to trigger a certain function or set a digital output.
Parameter
Example for operating mode
In the following example, the digital output 1 is set to TRUE if the output frequency is higher than 20 Hz.
–
As standard setpoint source, preset 1 (40 Hz) is set.
–
Switch S1 starts the motor in forward direction of rotation. Switch S1 in initial position stops the motor again.
|
Connection diagram
|
Function
|
||
|
|
|
Switch S1
|
Run
|
|
Parameter
|
Name
|
Setting for this example
|
|
Plug X3.1 configuration
|
DI2 + DO1 [2]
|
|
|
Enable inverter
|
Constant TRUE [1]
|
|
|
Run
|
Digital input 1 [11]
|
|
|
Digital outputs function: Digital output 1
|
Frequency threshold exceeded [70]
|
|
|
Frequency control: Default setpoint source
|
Frequency preset 2 [12]
|
|
|
Frequency setpoint presets: Preset 2
|
40.0 Hz
|
|
|
Acceleration time 1
|
9.00 s
|
|
|
Deceleration time 1
|
3.00 s
|
|
|
Frequency threshold
|
20.0 Hz
|
|
The status signals can be assigned to digital outputs.
Configure digital outputs |
|
|
|
|
|
①
|
Frequency threshold 0x4005
|
|
②
|
Frequency threshold exceeded: Via trigger "Frequency threshold exceeded [70]", the digital output 1 is set to TRUE.
|
Configure digital outputs