Brake energy management

Parameter
Address
Name / setting range / [default setting]
Information
0x2541:001
Brake energy management: Operating mode
Selection of the braking method.
–
The braking method(s) selected is/are activated if the DC-bus voltage exceeds the voltage threshold for the braking operation shown in 0x2541:002.
 
1
Ramp function generator stop (RFGS)
The deceleration ramp function generator is stopped.
 
3
Inverter motor brake (IMB) + RFGS
Braking with the "Inverter motor brake" braking method in connection with "Deceleration ramp function generator stop" is executed.
255
Disabled
0x2541:002
Brake energy management: Active threshold
–
Read only: x V
 
Display of the active voltage threshold for the braking operation.
–
The voltage threshold shown depends on the mains voltage selected in 0x2540:001 and the voltage value set in 0x2541:003.
 
–
The voltage threshold must be higher than the stationary DC voltage in the DC bus.
 
0x2541:003
Brake energy management: Reduced threshold
0 ... [0] ... 100 V
The voltage threshold for the braking operation is reduced by the voltage value set here.
0x2541:005
Brake energy management: Deceleration override time
0.0 ... [2.0] ... 60.0 s
Maximum permissible time for the deceleration override by means of the braking method selected in 0x2541:001.
–
If the DC-bus voltage does not fall below the voltage threshold for braking operation shown in 0x2541:002 within this time, the motor is decelerated further.
 
–
The time is only reset if the voltage threshold shown in 0x2541:002 is not reached.