Ramp times

The frequency setpoint is internally guided via a ramp generator. The acceleration time and the deceleration time are independently adjustable.
 
Details
–
The acceleration time set in 0x291D:001 refers to an acceleration from standstill to the maximum frequency set in 0x2916. At a low setpoint selection, the real acceleration time decreases accordingly.
 
–
The set deceleration time set in 0x291D:002 refers to the period of deceleration from the set maximum frequency to standstill. In the case of a lower actual frequency, the actual deceleration time is reduced accordingly.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x291C
Quick stop deceleration time
0.0 ... [1.0] ... 3600.0 s
Quick stop deceleration time for the operating mode "MS: Velocity mode".
–
If the "Quick stop" function is activated, the motor is brought to a standstill within the deceleration time set here.
 
–
The deceleration time set refers to the deceleration from the maximum frequency set to standstill. In the case of a lower actual frequency, the actual deceleration time is reduced accordingly.
 
–
Setting is not effective in the operating mode 0x6060 = "CiA: Velocity mode (vl) [2]".
 
0x291D:001
Ramp times: Acceleration time 1
0.00 ... [5.00] ... 655.35 s
Acceleration time 1 for the operating mode "MS: Velocity mode".
–
The acceleration time set refers to the acceleration from standstill to the maximum frequency set. In the case of a lower setpoint selection, the actual acceleration time is reduced accordingly.
 
–
Setting is not effective in the operating mode 0x6060 = "CiA: Velocity mode (vl) [2]".
 
0x291D:002
Ramp times: Deceleration time 1
0.00 ... [5.00] ... 655.35 s
Deceleration time 1 for the operating mode "MS: Velocity mode".
–
The deceleration time set refers to the deceleration from the maximum frequency set to standstill. In the case of a lower actual frequency, the actual deceleration time is reduced accordingly.
 
–
Setting is not effective in the operating mode 0x6060 = "CiA: Velocity mode (vl) [2]".
 
0x291E:001
S-Ramp characteristic: Smoothing factor
0.0 ... [0.0] ... 100.0 %
Factor for S-rounding of the acceleration/deceleration ramps.
–
With the setting "0.0", the S-rounding is deactivated and acceleration/deceleration with linear ramps is carried out.
 
–
The smoothing factor increases the ramp time as follows:
50 % --> 1.5 x configured ramp time
100 % --> 2 x configured ramp time
 
0x291E:002
S-Ramp characteristic: Target window
0.0 ... [1.0] ... 599.0 Hz