Standard setpoint source

The selected "setpoint source" serves to provide the inverter with its setpoint. The setpoint source can be selected individually for each operating mode.
Possible setpoint sources:
–
Parameterizable setpoints (presets)
 
–
Network
 
–
IO-Link ports
 
–
"Motor potentiometer" function
 
–
"Analog signal scaling" function
 
 
Details
–
For applications only requiring one setpoint, it is sufficient to define the standard setpoint source in 0x2860:001.
 
–
For applications requiring a change-over of the setpoint source during operation, the functions for setpoint change-over have to be configured accordingly. Changing the setpoint source during operation 
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2860:001
Frequency control: Default setpoint source
Selection of the standard setpoint source for operating mode "MS: Velocity mode".
–
The selected standard setpoint source is always active in the operating mode 0x6060 = "MS: Velocity mode [-2]" when no setpoint change-over to another setpoint source via corresponding triggers/functions is active.
 
2
Analog input 1
The setpoint is defined as analog signal via the analog input 1.
3
Analog input 2
The setpoint is defined as analog signal via the analog input 2.
5
Network
The setpoint is defined as process data object via the network.
11
Frequency preset 1
For the setpoint selection, preset values can be parameterised and selected.
12
Frequency preset 2
13
Frequency preset 3
14
Frequency preset 4
15
Frequency preset 5
16
Frequency preset 6
17
Frequency preset 7
18
Frequency preset 8
19
Frequency preset 9
20
Frequency preset 10
21
Frequency preset 11
22
Frequency preset 12
23
Frequency preset 13
24
Frequency preset 14
25
Frequency preset 15
50
Motor potentiometer
The setpoint is generated by the "motor potentiometer" function. This function can be used as an alternative setpoint control which is controlled via two signals: "MOP setpoint up" and "MOP setpoint down".
190
Logic PLC output value 1
Output values of the integrated Logic PLC.
–
These selection options are only available for the I65AMxxxxxxxxxP product variant.
 
191
Logic PLC output value 2
210
IOL1 AI1 scaled value
Value is specified as process data object via IO-Link.
–
The function assignment of the connectors must be configured accordingly.
 
–
The IO-Link ports are only available on the inverter with Application-I/O.
 
211
IOL1 AI2 scaled value
212
IOL2 AI1 scaled value
213
IOL2 AI2 scaled value
214
IOL3 AI1 scaled value
215
IOL3 AI2 scaled value
216
IOL4 AI1 scaled value
217
IOL4 AI2 scaled value
230
Scaling1 value
Output values of the "Analog signal scaling" function. This function is used to scale internal analog signals (analog parameter values) for use within the inverter.
231
Scaling2 value