Change over to ramp 2 during operation

Two different ramps can be parameterised for the frequency setpoint. The change-over to the ramp 2 can be initiated manually or automatically.
 
Details
For ramp 2, the acceleration time 2 set in 0x291D:003 and the deceleration time 2 set in 0x291D:004 apply.
The change-over to ramp 2 is effected automatically if the frequency setpoint (absolute value) ≥ auto-changeover threshold 0x291B.
The "Activate ramp 2" 0x2631:039 function serves to manually activate the acceleration time 2 and the deceleration time 2.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x291B
Auto-changeover threshold of ramp 2
0.0 ... [0.0] ... 599.0 Hz
Threshold for the automatic change-over to acceleration time 2 and deceleration time 2.
–
The change-over is effected if the frequency setpoint (absolute value) ≥ auto change-over threshold.
 
–
With the setting 0, the automatic change-over function is deactivated.
 
0x291D:003
Ramp times: Acceleration time 2
0.00 ... [5.00] ... 655.35 s
Acceleration time 2 for the operating mode "MS: Velocity mode".
–
The acceleration time set refers to the acceleration from standstill to the maximum frequency set. In the case of a lower setpoint selection, the actual acceleration time is reduced accordingly.
 
–
The acceleration time 2 is active if the frequency setpoint (absolute value) ≥ auto switching threshold 0x291B or the trigger assigned to the function "Activate ramp 2" in 0x2631:039 = TRUE.
 
–
Setting is not effective in the operating mode 0x6060 = "CiA: Velocity mode (vl) [2]".
 
0x291D:004
Ramp times: Deceleration time 2
0.00 ... [5.00] ... 655.35 s
Deceleration time 2 for the operating mode "MS: Velocity mode".
–
The set deceleration time refers to the period of deceleration from the set maximum frequency to standstill. In the case of a lower actual frequency, the actual deceleration time is reduced accordingly.
 
–
The deceleration time 2 is active if the frequency setpoint (absolute value) ≥ auto changeover threshold 0x291B or the trigger assigned to the function "Activate ramp 2" in 0x2631:039 = TRUE.
 
–
Setting is not effective in the operating mode 0x6060 = "CiA: Velocity mode (vl) [2]".
 
0x2631:039
Function list: Activate ramp 2
–
Further possible settings: Trigger list 
 
Assignment of a trigger for the "Activate ramp 2" function.
Trigger = TRUE: activate acceleration time 2 and deceleration time 2 manually.
Trigger = FALSE: no action / deactivate function again.
Notes:
–
If the function is used and the assigned trigger = TRUE, the auto changeover threshold 0x291B for ramp 2 is deactivated.
 
–
Acceleration time 2 can be set in 0x291D:003.
 
–
Deceleration time 2 can be set in 0x291D:004.
 
0
Not connected
No trigger assigned (trigger is constantly FALSE).
 
Example for operating mode
–
Switch S1 starts the motor in forward direction of rotation. Switch S1 in initial position stops the motor again.
 
–
Switch S2 activates the acceleration time 2 and deceleration time 2.
 
Connection diagram
Function
Switch S1
Run
Switch S2
Activate ramp 2
Parameter
Name
Setting for this example
Plug X3.1 configuration
DI2 + DI1 [1]
Enable inverter
Constant TRUE [1]
Run
Digital input 1 [11]
Reset fault
Not connected [0]
Activate ramp 2
Digital input 2 [12]
Stop method
Standard ramp [1]
Frequency control: Default setpoint source
Frequency preset 2 [12]
Frequency setpoint presets: Preset 2
40.0 Hz
Acceleration time 1
10.00 s
Deceleration time 1
10.00 s
Acceleration time 2
5.00 s
Deceleration time 2
5.00 s
 
The status signals can be assigned to digital outputs. Configure digital outputs
①
Change-over to deceleration time 2 during the deceleration phase.
②
Changeover to acceleration time 1 during the acceleration phase.