Flexible I/O configuration of the start, stop and rotating direction commands

Configuration of the triggers for the basic functions for controlling the motor.
 
Details
The following table contains a short overview of the basic functions. For more details see the following parameter descriptions.
Function
Information
Enable inverter
Enable/disable operation.
–
The function must be set to TRUE to start the motor. Either via a digital input or the default setting "Constant TRUE [1]".
 
–
If the function is set to FALSE, the inverter is disabled. The motor has no torque (is coasting).
 
Run
Function 1: Start / stop motor (default setting)
–
Function 1 is active if no further start commands (start forward/start reverse) have been connected to triggers and no network control is active.
 
TRUE: Let motor rotate forward (CW).
FALSE: Stop the motor.
Function 2: Start enable/stop motor
–
Function 2 is active if further start commands have been connected to triggers or network control is active.
 
TRUE: Start commands of the active control source are enabled.
FALSE: Stop the motor.
Activate quick stop
Bring the motor to a standstill in best time.
Start forward (CW)
Start the motor edge-controlled.
–
In order to be able to start the motor, the "Run" function must be set to TRUE.
 
–
The motor is stopped by resetting the "Run" function to FALSE.
 
–
The functions are deactivated for network control.
 
Start reverse (CCW)
Run forward (CW)
Let the motor rotate in a status-controlled way.
–
In order to be able to start the motor, the "Run" function must be set to TRUE.
 
–
The functions are deactivated for network control.
 
Run reverse (CCW)
Jog forward (CW)
Jog operation: Let the motor rotate in a status-controlled way with setpoint preset.
CAUTION!
The jog operation has a higher priority than the "Run" function, all other start commands.
–
If the jog operation is active, the motor cannot be stopped with the previously mentioned functions!
 
–
However, jog operation can be interrupted by the "Quick stop" function.
 
–
Jog operation can always be activated, even in case of network control.
 
Jog reverse (CCW)
Reverse rotational direction
Invert the frequency setpoint.
–
The function can be used in combination with all start commands.
 
–
The function is deactivated in the case of network control.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2631:001
Function list: Enable inverter
–
Setting can only be changed if the inverter is disabled.
 
–
Further possible settings: Trigger list 
 
Assignment of a trigger for the "Enable inverter" function.
Trigger = TRUE: The inverter is enabled (unless there is another cause for inverter disable).
Trigger = FALSE: The inverter is disabled.
Notes:
–
This function must be set to TRUE to start the motor. The signal TRUE is activated either via an assigned digital input or the default setting "Constant TRUE [1]".
 
–
Changing to the inhibited state causes an immediate stop of the motor, regardless of the stop method set in 0x2838:003. The motor has no torque and coasts down.
 
–
The cause(s) for the inhibited state are shown in 0x282A:001.
 
1
Constant TRUE
Trigger is constantly TRUE.
0x2631:002
Function list: Run
–
Setting can only be changed if the inverter is disabled.
 
–
Further possible settings: Trigger list 
 
Assignment of a trigger to the "Run".
Function 1: Start / stop motor (default setting)
Function 1 is active if no further start commands (start forward/start reverse) have been connected to triggers and no network control is active.
Trigger = TRUE: Let motor rotate forward (CW).
Trigger = FALSE: Stop motor.
Notes to function 1:
–
If "Enable inverter" 0x2631:001 = "Constant TRUE [1]", only a digital input is permissible as trigger for this function in order that the motor can be stopped again any time.
Exception: If the "Safe torque off (STO)" safety function is available, both functions "Enable inverter" and "Run" can be set to "Constant TRUE [1]". The inverter is then controlled via the STO signal unless no other start commands (start forward/start reverse) have been connected to triggers.
 
–
The stop method can be selected in 0x2838:003.
 
–
The function also serves to realize an automatic start after switch-on. Start behavior
 
Function 2: Start enable/stop motor
Function 2 is active if further start commands have been connected to triggers or network control is active.
Trigger = TRUE: Start commands of the active control source are enabled.
Trigger = FALSE: Stop motor.
Notes to function 2:
–
If no separate start enable is required for the application, the trigger "Constant TRUE [1]" must be set.
 
–
The stop method can be selected in 0x2838:003.
 
11
Digital input 1
State of X3/DI1, taking an inversion set in 0x2632:001 into consideration.
0x2631:003
Function list: Activate quick stop
–
Setting can only be changed if the inverter is disabled.
 
–
Further possible settings: Trigger list 
 
Assignment of a trigger for the "Activate quick stop" function.
Trigger = TRUE: Activate quick stop.
Trigger = FALSE: Deactivate quick stop.
Notes:
–
The "Quick stop" function brings the motor to a standstill within the deceleration time set in 0x291C.
 
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2631:006
Function list: Start forward (CW)
–
Setting can only be changed if the inverter is disabled.
 
–
Further possible settings: Trigger list 
 
Assignment of a trigger for the "Start forward (CW)" function.
Trigger = FALSE
↗
TRUE (edge): Let motor rotate forward.
Trigger = TRUE
↘
FALSE (edge): No action.
Notes:
–
In order to start the motor, "Enable inverter" 0x2631:001 and "Run" 0x2631:002 must be set to TRUE.
 
–
After the start, the motor runs until "Run" is set to FALSE, another stop command is given or the inverter is disabled.
 
–
In the case of a bipolar setpoint selection (e.g. 
±
10 V), the function is executed independent of the direction of rotation. The rotating direction is determined by the sign of the setpoint.
 
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2631:007
Function list: Start reverse (CCW)
–
Setting can only be changed if the inverter is disabled.
 
–
Further possible settings: Trigger list 
 
Assignment of a trigger for the "Start reverse (CCW)" function
Trigger = FALSE
↗
TRUE (edge): Let motor rotate backward.
Trigger = TRUE
↘
FALSE (edge): No action.
Notes:
–
In order to start the motor, "Enable inverter" 0x2631:001 and "Run" 0x2631:002 must be set to TRUE.
 
–
After the start, the motor runs until "Run" is set to FALSE, another stop command is given or the inverter is disabled.
 
–
In the case of a bipolar setpoint selection (e.g. 
±
10 V), the function is executed independent of the direction of rotation. The rotating direction is determined by the sign of the setpoint.
 
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2631:008
Function list: Run forward (CW)
–
Setting can only be changed if the inverter is disabled.
 
–
Further possible settings: Trigger list 
 
Assignment of a trigger for the "Run forward (CW)" function.
Trigger = TRUE: Let motor rotate forward.
Trigger = FALSE: Stop motor.
Notes:
–
In order to start the motor, "Enable inverter" 0x2631:001 and "Run" 0x2631:002 must be set to TRUE.
 
–
The inverter always responds to the run command detected last. A start enable must exist.
 
–
The stop method can be selected in 0x2838:003.
 
–
In the case of a bipolar setpoint selection (e.g. 
±
10 V), the function is executed independent of the direction of rotation. The rotating direction is determined by the sign of the setpoint.
 
–
The "Run forward (CW)" function also serves to realise an automatic start after switch-on. Start behavior
 
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2631:009
Function list: Run reverse (CCW)
–
Setting can only be changed if the inverter is disabled.
 
–
Further possible settings: Trigger list 
 
Assignment of a trigger for the "Run reverse (CCW)" function.
Trigger = TRUE: Let motor rotate backward.
Trigger = FALSE: Stop motor.
Notes:
–
In order to start the motor, "Enable inverter" 0x2631:001 and "Run" 0x2631:002 must be set to TRUE.
 
–
The inverter always responds to the run command detected last. A start enable must exist.
 
–
The stop method can be selected in 0x2838:003.
 
–
In the case of a bipolar setpoint selection (e.g. 
±
10 V), the function is executed independent of the direction of rotation. The rotating direction is determined by the sign of the setpoint.
 
–
The "Run reverse (CCW)" function also serves to realise an automatic start after switch-on. Start behavior
 
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2631:010
Function list: Jog forward (CW)
–
Setting can only be changed if the inverter is disabled.
 
Assignment of a trigger for the "Jog forward (CW)" function.
Trigger = TRUE: Let motor rotate forward with preset 5.
Trigger = FALSE: Stop motor.
CAUTION!
The jog operation has a higher priority than the "Run" function, all other start commands.
–
If jog operation is active, the motor cannot be stopped with the previously mentioned functions!
 
–
However, jog operation can be interrupted by the "Quick stop" function.
 
Notes:
–
The preset 5 can be set in 0x2911:005.
 
–
The stop method can be selected in 0x2838:003.
 
–
If "Jog forward (CW)" and "Jog reverse (CCW)" are activated at the same time, the motor is stopped using the set stop method and jog operation must be triggered again.
 
–
Jog operation cannot be started automatically. The "Start at power-up" option in 0x2838:002 does not apply to jog operation.
 
0
Not connected
No trigger assigned (trigger is constantly FALSE).
11
Digital input 1
State of X3/DI1, taking an inversion set in 0x2632:001 into consideration.
12
Digital input 2
State of X3/DI2, taking an inversion set in 0x2632:002 into consideration.
13
Digital input 3
State of X3/DI3, taking an inversion set in 0x2632:003 into consideration.
14
Digital input 4
State of X3/DI4, taking an inversion set in 0x2632:004 into consideration.
15
Digital input 5
State of X3/DI5, taking an inversion set in 0x2632:005 into consideration.
16
Digital input 6
State of X3/DI6, taking an inversion set in 0x2632:006 into consideration.
17
Digital input 7
State of X3/DI7, taking an inversion set in 0x2632:007 into consideration.
18
Digital input 8
State of X3/DI8, taking an inversion set in 0x2632:008 into consideration.
50
Running
TRUE if inverter and start are enabled and output frequency > 0 Hz. Otherwise FALSE.
Exception, quick stop mode: TRUE if inverter and start are enabled and output frequency > 0.2 Hz. Otherwise FALSE.
51
Ready for operation
TRUE if inverter is ready for operation (no error active, no STO active and DC-bus voltage ok). Otherwise FALSE.
53
Stop active
TRUE if inverter is enabled and motor is not started and output frequency = 0.
54
Quick stop active
TRUE if quick stop is active. Otherwise FALSE.
58
Device warning active
TRUE if warning is active. Otherwise FALSE.
–
A warning has no impact on the operating status of the inverter.
 
–
A warning is reset automatically if the cause has been eliminated.
 
59
Device trouble active
TRUE if a fault is active. Otherwise FALSE.
–
In the event of a fault, the motor is brought to a standstill with the quick stop ramp. The inverter is then disabled.
 
–
Exception: In case of a serious fault, the inverter is disabled immediately. The motor has no torque (coasts).
 
–
The error state will be left automatically if the error condition is not active anymore.
 
–
The restart behaviour after trouble can be configured. Automatic restart after a fault 
 
60
Heatsink temperature warning active
TRUE if current heatsink temperature > warning threshold for temperature monitoring. Otherwise FALSE.
–
Display of the current heatsink temperature in 0x2D84:001.
 
–
Setting of the warning threshold in 0x2D84:002.
 
68
Stop command active
TRUE if delay to standstill active. Otherwise FALSE.
69
Rotational direction reversed
TRUE if output frequency is negative. Otherwise FALSE.
70
Frequency threshold exceeded
TRUE if current output frequency > frequency threshold. Otherwise FALSE.
–
Display of the current output frequency in 0x2DDD.
 
–
Setting Frequency threshold in 0x4005.
 
71
Actual speed = 0
TRUE if actual output frequency = 0 Hz (
±
0.3 Hz), irrespective of the operating mode. Otherwise FALSE.
–
Display of the current output frequency in 0x2DDD.
 
78
Current limit reached
TRUE if current motor current
≥
maximum current. Otherwise FALSE.
–
Display of the present motor current in 0x2D88.
 
–
Setting for the maximum current in 0x6073.
 
79
Torque limit reached
TRUE if torque limit has been reached or exceeded. Otherwise FALSE.
–
Setting "Actual positive torque limit" in 0x2949:003.
 
–
Setting "Actual negative torque limit" in 0x2949:004.
 
81
Error of analog input 1 active
TRUE if the monitoring of the input signal at the analog input 1 has responded. Otherwise FALSE.
This trigger is set as a function of the following settings:
–
Monitoring threshold 0x2636:008
 
–
Monitoring condition 0x2636:009
 
The setting of the Error response in 0x2636:010 has no effect on this trigger.
82
Error of analog input 2 active
TRUE if the monitoring of the input signal at the analog input 2 has responded. Otherwise FALSE.
This trigger is set as a function of the following settings:
–
Monitoring threshold 0x2637:008
 
–
Monitoring condition 0x2637:009
 
The setting of the Error response in 0x2637:010 has no effect on this trigger.
83
Load loss detected
TRUE if actual motor current < threshold for load loss detection after delay time of the load loss detection has elapsed. Otherwise FALSE.
–
Display of the actual current in 0x6078.
 
–
Setting Threshold in 0x4006:001.
 
–
Setting Delay time in 0x4006:002.
 
84
Heavy load monitoring
TRUE if the actual apparent current of the motor exceeds the threshold for longer than the delay time.
FALSE if the actual apparent current of the motor falls below the threshold value minus 5 % (hysteresis).
120
Homing active
Status signals output by the "Table positioning" function.
–
These selection options are only available for the I65AMxxxxxxxxxP product variant.
 
121
Homing done
122
Manual jog active
123
Halt active
124
Motor control in limitation
125
Set position reached
126
Abort active
127
Standstill
128
Active profile (bit 1)
129
Active profile (bit 2)
130
Active profile (bit 3)
131
Active profile (bit 4)
132
Positioning profile active
133
Positioning profile done
134
Negative hardware limit switch active
135
Positive hardware limit switch active
136
Touch probe detected
137
External position active
169
Logic PLC Out bit 0
Binary values output by the integrated Logic PLC.
–
These selection options are only available for the I65AMxxxxxxxxxP product variant.
 
170
Logic PLC Out bit 1
171
Logic PLC Out bit 2
172
Logic PLC Out bit 3
173
Logic PLC Out bit 4
174
Logic PLC Out Bit 5
175
Logic PLC Out Bit 6
176
Logic PLC Out bit 7
177
Logic PLC Out bit 8
178
Logic PLC Out bit 9
179
Logic PLC Out bit 10
180
Logic PLC Out bit 11
181
Logic PLC Out bit 12
182
Logic PLC Out bit 13
183
Logic PLC Out bit 14
184
Logic PLC Out bit 15
224
IOL1 BI1 value
Binary values received via IO-Link corresponding to the binary input configuration for the respective IO-Link port.
–
The function assignment of the connectors must be configured accordingly.
 
–
The IO-Link ports are only available on the inverter with Application-I/O.
 
225
IOL1 BI2 value
226
IOL1 BI3 value
227
IOL1 BI4 value
228
IOL1 BI5 value
229
IOL1 BI6 value
230
IOL1 BI7 value
231
IOL1 BI8 value
232
IOL2 BI1 value
233
IOL2 BI2 value
234
IOL2 BI3 value
235
IOL2 BI4 value
236
IOL2 BI5 value
237
IOL2 BI6 value
238
IOL2 BI7 value
239
IOL2 BI8 value
240
IOL3 BI1 value
241
IOL3 BI2 value
242
IOL3 BI3 value
243
IOL3 BI4 value
244
IOL3 BI5 value
245
IOL3 BI6 value
246
IOL3 BI7 value
247
IOL3 BI8 value
248
IOL4 BI1 value
249
IOL4 BI2 value
250
IOL4 BI3 value
251
IOL4 BI4 value
252
IOL4 BI5 value
253
IOL4 BI6 value
254
IOL4 BI7 value
255
IOL4 BI8 value
0x2631:011
Function list: Jog reverse (CCW)
–
Setting can only be changed if the inverter is disabled.
 
–
For further possible settings, see parameter 0x2631:010.
 
Assignment of a trigger for the "Jog reverse (CCW)" function.
Trigger = TRUE: Let motor rotate backward with preset 6.
Trigger = FALSE: Stop motor.
CAUTION!
The jog operation has a higher priority than the "Run" function, all other start commands.
–
If jog operation is active, the motor cannot be stopped with the previously mentioned functions!
 
–
However, jog operation can be interrupted by the "Quick stop" function.
 
Notes:
–
The preset 6 can be set in 0x2911:006.
 
–
The stop method can be selected in 0x2838:003.
 
–
If "Jog forward (CW)" and "Jog reverse (CCW)" are activated at the same time, the motor is stopped using the set stop method and jog operation must be triggered again.
 
–
Jog operation cannot be started automatically. The "Start at power-up" option in 0x2838:002 does not apply to jog operation.
 
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2631:013
Function list: Reverse rotational direction
–
Setting can only be changed if the inverter is disabled.
 
–
Further possible settings: Trigger list 
 
Assignment of a trigger for the "Reverse rotational direction" function.
Trigger = TRUE: the setpoint specified is inverted (i. e. the sign is inverted).
Trigger = FALSE: no action / deactivate function again.
13
Digital input 3
State of X3/DI3, taking an inversion set in 0x2632:003 into consideration.