Changing the control source during operation

The term "control sources" in this connection refers to the digital signal sources from which the inverter receives its start, stop, and reversal commands.
Possible control sources:
–
Digital inputs
 
–
Network
 
 
Details
The "Activate network control" function can be used to switch from the "Digital inputs" control source to the "Network" control source during operation. The motor is then started via the network control word. The inverter not only supports such a changeover via its digital inputs, but also as a function of internal inverter states.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2631:037
Function list: Activate network control
–
Further possible settings: Trigger list 
 
Assignment of a trigger for the "Activate network control" function.
Trigger = TRUE: Activate network control.
Trigger = FALSE: no action / deactivate network control again.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
114
Network control active
TRUE if the network control is requested via bit 5 of the AC drive control word 0x400B:001. Otherwise FALSE.
Notes:
–
Set this selection if the network control is to be activated via bit 5 of the AC drive control word.
 
–
The AC drive control word can be used with any communication protocol.
 
 
Notes:
In case of an activated network control, the "Enable inverter" 0x2631:002 function must be set to "TRUE" to start the motor in addition to the "Run", either via digital input or by the "Constant TRUE [1]" setting.
In case of an activated network control, the following functions are still active:
–
0x2631:001: Enable inverter
 
–
 
–
0x2631:003: Activate quick stop
 
–
0x2631:004: Reset error
 
–
0x2631:005: DC braking
 
–
0x2631:010: Jog forward (CW)
 
–
0x2631:011: Jog reverse (CCW)*
 
–
0x2631:037: Activate network control*
 
–
0x2631:043: Activate error 1
 
–
0x2631:044: Activate error 2
 
(*Not active in case of network operation in CiA402 mode 0x6060=2).
All other functions configurable via 0x2631:xxx are deactivated in case of network control.