Activating DC braking manually

By means of the "Activate DC braking" function, DC braking can be activated manually.
 
Preconditions
The current for DC braking must be set > 0 % so that the function can be executed.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2631:005
Function list: Activate DC braking
–
Further possible settings: Trigger list 
 
Assignment of a trigger for the "Activate DC braking" function.
Trigger = TRUE: Activate DC braking.
Trigger = FALSE: Deactivate DC braking.
CAUTION!
DC braking remains active as long as the trigger is set to TRUE.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
 
Example for operating mode
–
Switch S1 starts the motor in forward direction of rotation. Switch S1 in initial position stops the motor again.
 
–
Switch S2 activates DC braking.
 
Connection diagram
Function
Switch S1
Run
Switch S2
Activate DC braking
Parameter
Name
Setting for this example
Plug X3.1 configuration
DI2 + DI1 [1]
Enable inverter
Constant TRUE [1]
Run
Digital input 1 [11]
Reset fault
Not connected [0]
Activate DC braking
Digital input 2 [12]
Stop method
Standard ramp [1]
Frequency control: Default setpoint source
Frequency preset 2 [12]
Frequency setpoint presets: Preset 2
40.0 Hz
DC braking: Current
10%
 
The status signals can be assigned to digital outputs. Configure digital outputs
①
If DC braking is activated while the motor is running, the output pulses of the inverter are disabled immediately. For stopping the motor, the current set in 0x2B84:001 is injected. The exact drive behavior depends on the settings for the "DC braking" function and the load properties.