Load loss detection

Parameter
Address
Name / setting range / [default setting]
Information
0x4006:001
Load loss detection: Threshold
0.0 ... [0.0] ... 200.0 %
Threshold for load loss detection.
–
100 % = rated motor current 0x6075
 
0x4006:002
Load loss detection: Delay time
0.0 ... [0.0] ... 300.0 s
Tripping delay for load loss detection.
0x4006:003
Load loss detection: Error response
Selection of the response following the detection of a load loss.
Associated event ID:
–
65336 | 0xFF38 - Load loss detected
 
0
No response
11
Information
12
Warning
16
Trouble
23
Fault > inverter disabled