Options for optimizing the control loops
Various options are available for optimizing the control:
a.
b.
c.
d.
Details
The option to be selected depends on the respective application. Depending on the selected option, different procedures become active and thus different parameter groups are influenced:
–
Rated motor data
–
Inverter characteristic
–
Motor equivalent circuit diagram data
–
Motor controller settings
–
Speed controller settings
Performing optimization with engineering tool
The following flow diagram shows the optimization process with an engineering tool (e. g. »EASY Starter«):
|
|
|
|
a)
|
The relevant motor data must be set first. You benefit from very precise motor equivalent circuit diagram data by selecting the motor from the motor catalogue.
|
|
b)
|
Manually set the motor data in accordance with the manufacturer's information / motor data sheet when a third-party motor is connected to the inverter.
|
|
c)
|
The speed controller must be first reinitialised alone if the load adjustment in the optimized system has changed.
|
|
d)
|
If the application enables you to energise the system during the optimization procedure, carry out an automatic identification. This procedure results in the best possible parameter settings.
|
|
e)
|
If the application does not enable you to energise the system during the optimization procedure, carry out an automatic calibration.
|
Select motor from motor catalog