Example: Changeover to network control

–
The control is executed primarily via the control connections. The switch S1 serves to start and stop the motor.
 
–
The network control can be activated via the S2 switch. When network control is activated, the motor can only be started via the network control word. However, the condition is that the switch S1 is closed.
 
–
If the switch S1 is opened again, the motor is stopped (irrespective of the active control source).
 
Connection diagram
Function
Switch S1
Run
Switch S2
Activate network control
Parameter
Name
Setting for this example
Plug X3.1 configuration
DI2 + DI1 [1]
Enable inverter
Constant TRUE [1]
Run
Digital input 1 [11]
Reset fault
Not connected [0]
Activate network control
Digital input 2 [12]
Frequency control: Default setpoint source
Frequency preset 2 [12]
Frequency setpoint presets: Preset 2
40.0 Hz
The status signals can be assigned to digital outputs. Configure digital outputs 
①
When changing over to another control source, the motor is first stopped with the stop method set in 0x2838:003.
②
The motor will also be stopped if the "Run" function is deactivated (irrespective of the active control source).
③
Commands via the network are ignored if the network control is not active.