Configure digital inputs

With the "DIx" function assignment for the X3 connectors, the inverter provides normal digital inputs. These inputs can be used for control tasks.
 
Preconditions
–
The function assignment of the connectors must be configured accordingly. Configure function assignment 
 
–
The digital inputs available depend on the type of control connections:
 
–
Standard-I/O: Digital input 1 ... digital input 4 (DI1 ... DI4)
 
–
Application-I/O: Digital input 1 ... digital input 8 (DI1 ... DI8)
 
–
Extended-I/O: Digital input 1 ... digital input 5 (DI1 ... DI5)
 
 
 
Details
The digital inputs are used for control tasks. For this purpose, the digital inputs are available as selectable triggers for functions.
The following settings are possible for the digital inputs:
–
Logic level "HIGH active" or "LOW active" ①
 
–
Debounce time ②
 
–
Inversion ③
 
Diagnostic parameters:
–
The logic status of the digital inputs is displayed in 0x60FD.
 
 
Logic level "HIGH active" or "LOW active"
The digital inputs can be configured in 0x2630:001 HIGH active (default setting) or LOW active:
HIGH active (default setting):
–
Internally, the digital input terminals are set to LOW level via pull-down resistors.
 
–
The current flows from the current supply (e.g. terminal X3/24 V) through the contact to the digital input terminal (and internally via the pull-down resistor to GND).
 
–
If the contact is closed, the digital input is set to HIGH level and is thus HIGH active.
 
LOW active:
–
Internally, the digital input terminals are set to HIGH level via pull-up resistors.
 
–
The current flows from the digital input terminal through the contact to GND.
 
–
If the contact is closed, the digital input is set to LOW level and is thus LOW active.
 
 
Debounce time
For minimizing interference pulses, a debounce time of 1 ms is set for all digital inputs. Via »EASY Starter« (or network), the debounce time for can be increased individually for each digital input to max. 50 ms.
 
Inversion
Each digital input can be configured in such a way that the state pending at the terminal is logically inverted internally. This way, a closed contact, for instance, serves to deactivate an assigned function instead of activating it. In this way, the control of the inverter can be flexibly adapted to the needs of the actual application.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2630:001
Settings for digital inputs: Assertion level
Definition of the internal hardware interconnection of the digital inputs.
0
LOW active
Digital inputs are internally set to HIGH level via pull-up resistors.
1
HIGH active
Digital inputs are internally set to LOW level via pull-down resistors.
0x2632:001
Inversion of digital inputs: Digital input 1
Inversion of digital input 1
0
Not inverted
1
Inverted
0x2632:002
Inversion of digital inputs: Digital input 2
Inversion of digital input 2
0
Not inverted
1
Inverted
0x2632:003
Inversion of digital inputs: Digital input 3
Inversion of digital input 3
0
Not inverted
1
Inverted
0x2632:004
Inversion of digital inputs: Digital input 4
Inversion of digital input 4
0
Not inverted
1
Inverted
0x2632:005
Inversion of digital inputs: Digital input 5
Inversion of digital input 5
0
Not inverted
1
Inverted
0x2632:006
Inversion of digital inputs: Digital input 6
Inversion of digital input 6
0
Not inverted
1
Inverted
0x2632:007
Inversion of digital inputs: Digital input 7
Inversion of digital input 7
0
Not inverted
1
Inverted
0x2632:008
Inversion of digital inputs: Digital input 8
Inversion of digital input 8
0
Not inverted
1
Inverted
0x2633:001
Digital input debounce time: Digital input 1
1 ... [1] ... 50 ms
Debounce time of digital input 1
0x2633:002
Digital input debounce time: Digital input 2
1 ... [1] ... 50 ms
Debounce time of digital input 2
0x2633:003
Digital input debounce time: Digital input 3
1 ... [1] ... 50 ms
Debounce time of digital input 3
0x2633:004
Digital input debounce time: Digital input 4
1 ... [1] ... 50 ms
Debounce time of digital input 4
0x2633:005
Digital input debounce time: Digital input 5
1 ... [1] ... 50 ms
Debounce time of digital input 5
0x2633:006
Digital input debounce time: Digital input 6
1 ... [1] ... 50 ms
Debounce time of digital input 6
0x2633:007
Digital input debounce time: Digital input 7
1 ... [1] ... 50 ms
Debounce time of digital input 7
0x2633:008
Digital input debounce time: Digital input 8
1 ... [1] ... 50 ms
Debounce time of digital input 8
0x4015:001
Digital input status: Level of digital input 1
–
Read only
 
Display of the level at the digital input.
0x4015:002
Digital input status: Level of digital input 2
–
Read only
 
0x4015:003
Digital input status: Level of digital input 3
–
Read only
 
0x4015:004
Digital input status: Level of digital input 4
–
Read only
 
0x4015:005
Digital input status: Level of digital input 5
–
Read only
 
0x4015:006
Digital input status: Level of digital input 6
–
Read only
 
0x4015:007
Digital input status: Level of digital input 7
–
Read only
 
0x4015:008
Digital input status: Level of digital input 8
–
Read only
 
0x4015:017
Digital input status: Level from digital input 1
–
Read only
 
Display of the level at the digital input, taking into account any inversion that may have been set.
0x4015:018
Digital input status: Level from digital input 2
–
Read only
 
0x4015:019
Digital input status: Level from digital input 3
–
Read only
 
0x4015:020
Digital input status: Level from digital input 4
–
Read only
 
0x4015:021
Digital input status: Level from digital input 5
–
Read only
 
0x4015:022
Digital input status: Level from digital input 6
–
Read only
 
0x4015:023
Digital input status: Level from digital input 7
–
Read only
 
0x4015:024
Digital input status: Level from digital input 8
–
Read only
 
 
Example: Activating two functions simultaneously via digital input 4
The principle of assigning triggers to functions also enables a digital input to be assigned to several functions. The wiring complexity is reduced since there is no necessity to interconnect several digital inputs.
If, for instance, the frequency preset 1 is to be selected via the digital input 4 and a change-over to the acceleration time 2 and deceleration time 2 is to take place at the same time, this can be easily realised by the following parameter setting:
Parameter
Designation
Setting for this example
Activate preset (bit 0)
Digital input 4 [14]
Activate ramp 2
Digital input 4 [14]
In order to achieve the desired behaviour, the digital input 4 must not be assigned to any further functions!