Configure HTL output

With the “pulse train" function assignment for connector X3.1, the inverter provides an HTL output. The inverter can output a reference frequency ("pulse train") via this output. Other inverters can interpret this signal as a setpoint signal, for example.
 
Preconditions
–
The function assignment of the X3.1 connector must be configured accordingly. Configure function assignment 
 
–
The "Pulse Train" function is available for all device variants.
 
For the output of an internal variable, the HTL output must be connected to the additional function "Analog signal scaling".
 
 
Restrictions
–
The maximum output frequency of the HTL output is 10 kHz.
 
 
Details
Typical applications:
a.
An inverter acts as a master and transfers its actual output frequency in the form of a pulse train signal to one or several other inverters (slaves). The slaves use the pulse train signal with a corresponding scaling as a frequency setpoint.
 
b.
The inverter transmits the current torque or another internal variable as a pulse train signal to a higher-level controller. The controller can then evaluate the signal accordingly.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2644:003
DO1 frequency setup: Function
Selection of the signal to be provided at the digital output 1 as pulse train.
0
Not active
No signal assigned.
3
Analog input 1
Input signal of analog input 1 (resolution: 0.1 %).
4
Analog input 2
Input signal of analog input 2 (resolution: 0.1 %).
210
IOL1 AI1 scaled value
Value is specified as process data object via IO-Link.
–
The function assignment of the connectors must be configured accordingly.
 
–
The IO-Link ports are only available on the inverter with Application-I/O.
 
211
IOL1 AI2 scaled value
212
IOL2 AI1 scaled value
213
IOL2 AI2 scaled value
214
IOL3 AI1 scaled value
215
IOL3 AI2 scaled value
216
IOL4 AI1 scaled value
217
IOL4 AI2 scaled value
230
Scaling1 value
Output values of the "Analog signal scaling" function. This function is used to scale internal analog signals (analog parameter values) for use within the inverter.
231
Scaling2 value
0x2646:001
DO actual frequency: Digital output 1
–
Read only: x.x Hz
 
Display of the current frequency of the pulse train signal at the digital output 1.