Example: Output scalable analog signal at HTL output
For this example, we imagine the following use case: We have two motors and two inverters. One motor is to follow the other.
Solution: The current output frequency of the first inverter is output via the HTL output. The HTL output is connected to the HTL input of the second inverter so that it can use the input frequency as the frequency setpoint for the second motor.
–
The output frequency is scaled via the “Analog signal 2" of the additional function "Analog signal scaling".
–
The " Analog signal 2 " is again assigned to the HTL output as a signal source.
Required wiring
–
The HTL output (X3.1/Pin 4) of the first inverter is connected to the HTL input (X3.2/Pin 2) of the second inverter.
Parameterization (first inverter)
1.
Set function for connector X3.1: 0x2630:010 = "DI2 + Pulse train [4]"
2.
Make the following settings for "Analog signal 2":
If scaling is required, it can be set via the following parameters:
–
0x2654:016: Input value = "0x2DDD0010" (current output frequency 0x2DDD)
–
0x2654:020: Input value is signed [0]
–
0x2654:024: Output value is signed [0]
–
0x2654:025: Length of the output value = 32 bits
3.
To apply the settings made, set "Active [1]" in 0x2654:030.
4.
Set output signal of scaling "Analog signal 2" for the HTL output: 0x2644:003 = "Scaling2 value [231]"
Parameterization (second inverter)
Configure the HTL input on the second inverter.
For details, see
Example: Use HTL input as setpoint source
Example: Use HTL input as setpoint source