Example: Use HTL input as setpoint source
For this example, we imagine the following use case: We have two motors and two inverters. One motor is to follow the other.
Solution: There is an HTL encoder mounted on the first motor, which is connected to X3.2 on the second inverter. X3.2 is configured as HTL input so that the input frequency can be used as frequency setpoint for the second motor.
–
The example applies to an HTL encoder with 128 increments.
–
Scaling of the input frequency and provision as a selectable frequency setpoint is performed via the additional function "Analog signal scaling".
–
By default, the scaling for "Analog signal 1" is preset to be used for the frequency input.
Required wiring (second inverter)
–
Track A of the HTL encoder is connected to X3.2/Pin 4.
–
Track B of the HTL encoder is connected to X3.2/Pin 2.
Parameterization (second inverter)
1.
Set function for connector X3.2: 0x2630:011 = "Pulse in + Pulse direction [19]"
2.
Adjust scaling for "Analog signal 1".
The following presets can be kept:
The following settings must be made by the user:
The following presets can be kept:
–
0x2654:001: Input value = input frequency (0x2642:001)
–
0x2654:005: Input value is signed
–
0x2654:006: Length of the input value = 32 bits
–
0x2654:009: Output value is signed
–
0x2654:010: Length of the output value = 32 bits
–
0x2654:007 / 0x2654:008: -32000/32000 (min./max. input value)
(note: The input frequency is scaled with 0.1).
à
max. frequency = (max. speed [rpm] / 60) * incrementsà
max. frequency = (1500 / 60) * 128 = 3200 Hz(note: The input frequency is scaled with 0.1).
–
0x2654:011 / 0x2654:012: -5000/5000 (min./max. output value)
(note: The internal frequency value is scaled with 0.01).
à
-50 Hz/50 Hz(note: The internal frequency value is scaled with 0.01).
3.
To apply the settings made, set "Active [1]" in 0x2654:015.
4.
Set output signal of scaling "Analog signal 1" as setpoint source for frequency control: 0x2860:001 = "Scaling1 value [230]"
After enabling both inverters, both motors should run at the same speed.
Notes
As an alternative to the direct selection of "Scaling1 value [230]" in 0x2860:001, the scaled value can be mapped to any other mappable parameter by setting a target address in0x2654:003. For example, if the scaled value is mapped to 0x400B:003 ...005, then the selection "Network [5]" must be set in 0x2860:001. In this case, the minimum/maximum output value must be adjusted to the scaling factor of the mapped parameter.