Configure HTL input

With the "Pulse-In" function assignment for connector X3.2, the inverter provides an HTL input. Via this input, the inverter can evaluate the signal of a low-cost HTL encoder or a reference frequency ("pulse train") and accept it as a setpoint signal. The detection of a direction signal ("Pulse-Direction") is also supported.
 
Preconditions
–
The function assignment of the X3.2 connector must be configured accordingly. Configure function assignment 
 
–
For inverters with Application-I/O, the X3.3 connector can alternatively be configured for the "Pulse-In" and "Pulse-Direction" functions.
 
 
To be able to use the HTL input as a setpoint source, the input frequency must be connected to the additional function "Analog signal scaling".
In the default setting, the input frequency is already set as input value for the scaling "Analog signal 1".
 
If the HTL encoder is to be used as a motor encoder for feedback of the motor speed for the most accurate speed control, connector X3.2 must be configured as an encoder input instead.
 
 
Details
a.
Pulse-In" function without "Pulse-Direction" (0x2630:011 = selection 16, 17, 18):
The frequency input signal (pulse train) is acquired via pin 2 of X3.2.
 
b.
Pulse-In + Pulse-Direction" function (0x2630:011 = selection 19):
The frequency input signal (pulse train) is acquired via pin 2 of X3.2.
The direction signal is also acquired via pin 4 of X3.2.
 
Input frequency
The current input frequency is displayed in 0x2642:001. If pin 4 is used to detect the direction signal, the value of the input frequency becomes negative depending on the pulse train or direction signal!
Filter
The input frequency is filtered. The filter time constant is adjustable. 0x2640:009
Monitoring
In addition, it is possible for the inverter to monitor the HTL input and generate a response when the input frequency falls below and/or rises above a predetermined frequency value.
Configuration of inverter monitoring:
–
Set minimum frequency threshold to the lowest valid input frequency (in Hz). 0x2641:001
 
–
Set maximum frequency threshold to the highest valid input frequency (in Hz). 0x2641:003
 
–
Set minimum delay threshold to the amount of time the input frequency must fall below the minimum threshold to cause an error condition. 0x2641:002
 
–
Set maximum delay threshold to the amount of time that the input frequency must rise above the maximum threshold to cause an error condition. 0x2641:004
 
–
Set monitoring conditions. 0x2641:005
 
–
Set error response. 0x2641:006
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2640:009
HTL input settings: IN1 Filter time constant
0 ... [10] ... 10000 ms
PT1 time constant for low-pass filter.
0x2640:019
HTL input settings: IN2 Filter time constant
0 ... [10] ... 10000 ms
0x2641:001
HTL input monitoring: IN1 Minimal frequency threshold
-214748364.8 ... [0.0] ... 214748364.7 Hz
Setting for the minimum frequency threshold for the monitoring of the HTL input.
0x2641:002
HTL input monitoring: IN1 Minimum delay threshold
0.0 ... [5.0] ... 300.0 s
Setting for the minimum delay threshold for the monitoring of the HTL input.
0x2641:003
HTL input monitoring: IN1 Maximal frequency threshold
-214748364.8 ... [0.0] ... 214748364.7 Hz
Setting for the maximum frequency threshold for the monitoring of the HTL input.
0x2641:004
HTL input monitoring: IN1 Maximum delay threshold
0.0 ... [5.0] ... 300.0 s
Setting for the maximum delay threshold for the monitoring of the HTL input.
0x2641:005
HTL input monitoring: IN 1Monitoring conditions
–
If the selected condition is fulfilled, the response set in 0x2641:006 takes place.
 
1
Below minimum frequency
Input frequency < "Minimum frequency threshold" longer than the "Minimum delay threshold".
2
Above maximum frequency
Input frequency > "Maximum frequency threshold" longer than the "Maximum delay threshold".
3
Below min. or above max. frequency
Input frequency < "Minimum frequency threshold" longer than the "Minimum delay threshold" OR input frequency > "Maximum frequency threshold" longer than the "Maximum delay threshold".
0x2641:006
HTL input monitoring: IN1 Error response
Selection of the response to the triggering of the HTL input monitoring.
Associated event ID:
–
28803 | 0x7083 - HTL input fault
 
0
No response
11
Information
12
Warning
16
Trouble
23
Fault > inverter disabled
0x2641:011
HTL input monitoring: IN2 Minimal frequency threshold
-214748364.8 ... [0.0] ... 214748364.7 Hz
Setting for the minimum frequency threshold for the monitoring of the HTL input.
0x2641:012
HTL input monitoring: IN2 Minimum delay threshold
0.0 ... [5.0] ... 300.0 s
Setting for the minimum delay threshold for the monitoring of the HTL input.
0x2641:013
HTL input monitoring: IN2 Maximal frequency threshold
-214748364.8 ... [0.0] ... 214748364.7 Hz
Setting for the maximum frequency threshold for the monitoring of the HTL input.
0x2641:014
HTL input monitoring: IN2 Maximum delay threshold
0.0 ... [5.0] ... 300.0 s
Setting for the maximum delay threshold for the monitoring of the HTL input.
0x2641:015
HTL input monitoring: IN2 Monitoring conditions
–
If the selected condition is met, the reaction selected in " 0x2641:016 " will occur.
 
1
Below minimum frequency
Input frequency < "Minimum frequency threshold" longer than the "Minimum delay threshold".
2
Above maximum frequency
Input frequency > "Maximum frequency threshold" longer than the "Maximum delay threshold".
3
Below min. or above max. frequency
Input frequency < "Minimum frequency threshold" longer than the "Minimum delay threshold" OR input frequency > "Maximum frequency threshold" longer than the "Maximum delay threshold".
0x2641:016
HTL input monitoring: IN2 Error response
Associated event ID:
–
28804 | 0x7084 - HTL input fault IN2
 
0
No response
11
Information
12
Warning
16
Trouble
23
Fault > inverter disabled
0x2642:001
HTL input diagnostics: Input frequency
–
Read only: x.x Hz
 
Display of the current input value at the HTL input.
0x2642:011
HTL input diagnostics: IN2 Input frequency
–
Read only: x.x Hz