0x2D84:001
|
Heatsink temperature: Heatsink temperature
|
Display of the current heatsink temperature.
|
|
0x2D84:002
|
Heatsink temperature: Warning threshold
50.0 ... [0.0] ... 100.0 °C
|
Warning threshold for temperature monitoring.
–
If the heatsink temperature exceeds the threshold set here, the inverter outputs a warning.
–
The warning is reset with a hysteresis of approx. 5 °C.
–
If the heatsink temperature increases further and exceeds the non-adjustable error threshold (100 °C), the inverter
changes to the "Fault" device status. The inverter is disabled and thus any further operation is stopped.
|
|
0x2D84:003
|
Heatsink temperature: Fan on threshold
0.0 ... [0.0] ... 100.0 °C
|
Switch-on threshold for device fans.
|
|
0x2D84:004
|
Heatsink temperature: Fan off threshold
0.0 ... [0.0] ... 100.0 °C
|
Switch-off threshold for device fans.
–
If the heatsink temperature falls below the threshold set here, the device fan is switched off. This only happens if the switch-off threshold is parameterized lower than the switch-on threshold.
–
Larger designs of the inverter also have an internal fan. This is controlled in parallel with the heatsink fan and has no switch-on or switch-off thresholds of its own.
|