Example: Start/stop (1 signal) and reversal
This example shows a simple control option via two switches which should be sufficient for many applications:
–
The switch S1 starts the motor in the forward direction of rotation. The switch S1 in the initial position stops the motor again.
–
The switch S2 switches the direction of rotation.
|
Connection diagram
|
Function
|
||
|
|
|
Switch S1
|
Run
|
|
Switch S2
|
Reverse rotational direction
|
||
|
Parameter
|
Name
|
Setting for this example
|
|
Plug X3.1 configuration
|
DI2 + DI1 [1]
|
|
|
Enable inverter
|
Constant TRUE [1]
|
|
|
Run
|
Digital input 1 [11]
|
|
|
Reset fault
|
Not connected [0]
|
|
|
Reverse rotational direction
|
Digital input 2 [12]
|
|
|
Frequency control: Default setpoint source
|
Frequency preset 2 [12]
|
|
|
Frequency setpoint presets: Preset 2
|
40.0 Hz
|
|
The status signals can be assigned to digital outputs.
Configure digital outputs |
|
|
|
|
|
①
|
If the inverter is enabled and no error is active, the motor can be started with the "Run" function in forward rotating direction.
|
|
②
|
If "Run" is set to FALSE, the motor is stopped with the stop method set in 0x2838:003. In the example: Stop with standard ramp.
|
Configure digital outputs