Analog input 2

With the "AI2" function assignment for connector X3.1, the inverter provides an analog input.
 
Preconditions
–
The function assignment of the X3.1 connector must be configured accordingly. Configure function assignment 
 
–
The "AI2" function is available only on inverters with Extended-I/O.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2637:001
Analog input 2: Input range
Definition of the input range.
0
0 ... 10 VDC
1
0 ... 5 VDC
2
2 ... 10 VDC
3
-10 ... +10 VDC
4
4 ... 20 mA
5
0 ... 20 mA
0x2637:002
Analog input 2: Min frequency value
-1000.0 ... [0.0] ... 1000.0 Hz
Scaling of the input signal to the frequency value.
–
Direction of rotation according to sign.
 
–
The standard setpoint source for operating mode 0x6060 = "MS: Velocity mode [-2]" is selected in 0x2860:001.
 
0x2637:003
Analog input 2: Max frequency value
-1000.0 ... [60.0] ... 1000.0 Hz
0x2637:004
Analog input 2: Min PID value
-300.00 ... [0.00] ... 300.00 PID unit
Scaling of the input signal to the PID value.
–
The standard setpoint source for the reference value of PID control is selected in 0x2860:002.
 
0x2637:005
Analog input 2: Max PID value
-300.00 ... [100.00] ... 300.00 PID unit
0x2637:006
Analog input 2: Filter time
0 ... [10] ... 10000 ms
PT1 time constant for low-pass filter.
–
By the use of a low-pass filter, the impacts of noise to an analog signal can be minimised.
 
–
For an optimum filter effect, first the noise frequency has to be determined. The time constant then has to be set so that it equals the reciprocal value of the double frequency.
 
0x2637:007
Analog input 2: Dead band
0.0 ... [0.0] ... 100.0 %
Optional setting of a dead band that is placed symmetrically around the frequency zero point.
–
If the analog input value is within the dead band, the output value for the motor control is set to "0".
 
–
100 % = maximum value of analog input (0x2636:003, 0x2636:005, 0x2636:012)
 
–
Example: Dead band 10 % of 50 Hz: -10 V … 10 V, Dead band -5 Hz … 5 Hz, 0 V… 10 V, Dead band 0 Hz … 5 Hz
 
0x2637:008
Analog input 2: Monitoring threshold
-100.0 ... [10.0] ... 100.0 %
Monitoring threshold for analog input 2.
–
100 % = 10 V (with configuration as voltage input)
 
–
100 % = 20 mA (with configuration as current loop)
 
Exception: In the case of a configured input range 4...20 mA (0x2636:001 [4]), the monitoring is triggered at 2 mA with a monitoring threshold of 0.0 %.
0x2637:009
Analog input 2: Monitoring condition
Monitoring condition for analog input 2.
–
If the selected condition is met, the "Error of analog input 2 active [82]" trigger is set to TRUE. The trigger can be assigned to a function or a digital output.
 
–
If the selected condition is met for at least 500 ms, the error response set in 0x2637:010 takes place.
 
0
Input value < trigger threshold
1
Input value > trigger threshold
0x2637:010
Analog input 2: Error response
Error response for analog input 2.
–
The selected response takes place if the monitoring condition selected in 0x2637:009 is met for at least 500 ms.
 
Associated event ID:
–
28802 | 0x7082 - Analog input 2 fault
 
0
No response
11
Information
12
Warning
16
Trouble
23
Fault > inverter disabled
0x2637:011
Analog input 2: Min torque value
-400.0 ... [0.0] ... 400.0 %
Scaling of the input signal to the torque value.
–
100 % = permissible maximum torque 0x6072
 
–
Direction of rotation according to sign.
 
–
The standard setpoint source for operating mode 0x6060 = "MS: Torque mode [-1]" is selected in 0x2860:003.
 
0x2637:012
Analog input 2: Max torque value
-400.0 ... [100.0] ... 400.0 %
0x2637:015
Analog input 2: Error response AI2
Response when an error is detected on analog input 2 (0x2DA5:016, bits 9, 10, 11).
Associated event ID:
–
28809 | 0x7089 - Analog input 2 fault
 
0
No response
11
Information
12
Warning
16
Trouble
23
Fault > inverter disabled